Information > SMS Modem Status
This page shows the Modem status when GPRS modem is connecting with NetAgent
A
Information > NetFeeler
This page shows the environmental status when USB NetFeeler/ NetFeeler II and its
accessories are connected with NetAent
A
.
Configuration > UPS Configuration
UPS Properties (Please refer to your UPS specification)
UPS Communication Type:
In order to establish theconnection between NetAgent
A
and UPS, select
the compatible protocol which your UPS supported from the list. Wrong
protocol selected would cause no communication at all. (Megatec is
default protocol)
Number of Batteries
:
Enter the number of battery that the UPS has.
Battery Full Charge Voltage (V)
:
Enter the number of the full charged voltage per battery cell. (2.267 is default, this is
recommended not to be change)
Battery Exhausted Charge Voltage(V)
:
Enter the number of exhausted voltage per battery cell. (1.667 is default, this is
recommended not to be change)
Date of Last Battery replacement(mm/dd/yyyy)
:
Enter the date of last battery replacement for record