Installation Manual
GB
Wiring diagramme – programming unit
13
Stop position 1
Lift in complete upward position
Stop position 2
Lift in complete downward position
To programme new positions use the programming unit standard
(No. 7466-100) or electronic (No. 7466-101. See optional
accessories.
a) Programming unit standard
Install the unit according to the attached wiring diagramme. Make
sure that the colours of the installation cables are identical with
the colours of the motor cable. Connect with the mains only after
completing the installation!
Adjustment end positions:
1. Press button E (2) for at least 6 sec., the motor switches into
adjustment mode. Short stop after start indicates adjustment
mode!
2. Drive to the bottom end position (projection position).
3. Press button E (2) for at least 3 sec., bottom end position is set.
4. Drive to top end position (home position) carefully.
5. Press button E (2) for at least 3 sec., top end position (home
position) is set.
6. A trial run should be carried out upon completion of adjust-
ments. Adjustments are correct when the ceiling lift stops at
the set end positions.
Note:
Make sure that the cables to the on/off switches of the lift
are not exchanged!
(brown = up, black = down)
Wiring diagramme – installation of switches
junction box
provided by the user
mains
safety switch
green/yellow
blue
brown
black
black
blue
green/yellow
blue
box for switches
provided by the user
Up/down switch
e.g. 5944-2
Cable between
junction box and
box for switches
min. 6 wires
(e.g. NYM 7x1.5mm
2
)
Adjusting the stop position of the lift
b) Electronic programming unit
Install the unit as shown in the wiring diagramme. For adjusting
the stop positions follow the instructions in the user manual of the
unit.
If it is successful, take the programming unit off the mains and
disconnect it.
box for switches
provided by the user
safety switch
black
blue
junction box
provided by the user
mains
standard mode
clamp
programming unit
7466-100 or
7466-101
green/yellow
motor
motor
connection
lift
green/yellow
blue
brown
black
programming unit
standard 7466-100
mains
programming unit
connection
lift
power control
2
1
black
brown
gr/ye
blue
Cable between
junction box and
box for switches
min. 6 wires
(e.g. NYM 7x1.5mm
2
)
Содержание 22483