background image

4

 

 

System details

 

SEC-K 

18.

Timer adjustment for fan commissioning, allows timed period for gas installation commissioning. 

19.

Auto stop timer to isolate gas after set length of time. Factory set for model & use 

20.

CO2 alarm level adjustment depending on application. Factory set for model & use 

21.

High pressure low cut out adjustment 

Gas Fill Time.  

The Fill Time should be set such that there is sufficient time to fill an empty pipe work system to 

full / normal pressure while ensuring a minimum escape of gas where a leak exists. 
 

Gas Prove Time. 

This should be set such that the smallest leak can be detected. This time can be set up to a 

maximum of 99 seconds. Increasing this time effectively makes the system more sensitive to gas leaks. 
(Factory default setting is 50 seconds). An extra 60 seconds prove time can be added onto the 99 seconds 
by adjusting the DIP switch under the options bank, see 

No 16

15.

BMS Relay PCB. Two relays, for connection to a BMS to indicate, high & low alarm, gas on, EM stop. (One selectable from each 

relay)     Max switching 48 volts 1 amp 

HAL - High alarm  
GON - Gas On 
EST - Emergency stop 
ALT - Low Alarm  

Fan comm. 

To enable the commissioning of the gas portion of the system before the ventilation interlock is completed to you may temporarily 
disable the interlocking by pressing button 22. This will bypass the ventilation interlock allowing the gas to be tested, the system 
must not be left in this state and as such is only this for a maxim 24hour period but auto exiting. 

While in commissioning mode the 

display will show the message “Not to current standards”

.  Pressing the button again at anytime will cancel commissioning mode. 

 
Learn Field devices 

Any gas detectors connected to the system will require “learning”. First ensure all detectors are set to a unique ID address using 
the selector switch on the detectors themselves. Having addressed each detector press the learn field devices button (23), the sys-
tem will scan and store any connected detectors. To verify that all detectors have been successfully learnt press the “blind button 
B” on the front panel to view address details.  

A                                 B 

Press button A  

To display the gas pressures and view the set pressure proving set times. 
 

Press button B 

To display the gas installed gas detectors 1-8 press A & B together to view 9-16. 

 
Fire Test Mode (Press button B three times) 

When connected to a fire alarm panel using the fire alarm terminal (no.13) the system will isolate the gas during an fire alarm. 
If for the purposes of a fire test you wish to temporarily disable this interlock the SEC system can be put into a “fire test mode” by 
pressing blind button 

B

 three times in quick succession. This is a timed feature and will auto clear after 45mins. Press again three 

times to manually clear and return to normal running.  

Содержание SEC-K

Страница 1: ...The Home of Control Automation in Ireland SEC K Multi Function Control System for Kitchens...

Страница 2: ...use Each services can be individually controlled using the tactile buttons on the panel with overall secure isolation provided by the main on off switch Gas detectors for carbon dioxide and temperatur...

Страница 3: ...by testing for leaks and open appliances before allowing gas available by using Medem patented true differential gas pressure measuring across the solenoid valve This eliminates nuisance tripping of t...

Страница 4: ...Gas Pressure Proving Using the patented differential pressure proving method the SEC K can test for low pressure natural LPG gas pipe work or can pressure prove a variety of gas delivery lines includ...

Страница 5: ...d extra low voltage The connections marked CM2 or PD switches are for the connection of a current monitor or pressure switches for interlocking fans with the gas supply The connections marked detector...

Страница 6: ...13 Fire alarm input signal N C contact required 14 0 10 volt output to fan speed controllers based on CO2 and temperature levels 15 Two relays for connection to a BMS to indicate high alarm gas on EM...

Страница 7: ...present within the panel N L To Contactor Coil Method 2 IMPORTANT If wired this way a warning notice must be attached to the panel to indicate that there are two separate mains feeds L N Supply in Co...

Страница 8: ...pur 230v EM Stop Buttons TT 70c Series connected Addressable Gas detector Addressable Gas detector 6 core low voltage cable Sender unit Mounts on the gas valve Requires a volt free NC contact 0 10v ou...

Страница 9: ...a Medem engineer this can be increased to 10 years and includes a 24hr helpline During the commissioning process a Medem engineer would attend site to ensure full and correct operation of the supplie...

Страница 10: ...nough to ensure the downstream pipe work comes up to pressure factory default 5 seconds The prove time should be set at installation to find the smallest possible leak factory default 50 seconds To te...

Страница 11: ...ational test on any installed Emergency stop buttons which when operated will isolate the gas supply and remain isolated until a manual reset is completed If utilized an auto stop time out will isolat...

Страница 12: ...r Medem UK should commission this safety system whereupon a commissioning report will be forwarded to the installing agent who should provide a copy to the end user At the point of our commissioning a...

Страница 13: ...ing light yellow B blind button for displaying connected devices detectors temperature on the LCD screen LCD display For displaying system status during both installation and normal use also for displ...

Страница 14: ...evels 15 Two relays for connection to a BMS to indicate high alarm gas on EM stop low alarm One selectable for each relay 16 OPTA Over pressure check will isolate gas supply if pressure exceeds 70 mba...

Страница 15: ...sing button 22 This will bypass the ventilation interlock allowing the gas to be tested the system must not be left in this state and as such is only this for a maxim 24hour period but auto exiting Wh...

Страница 16: ...s Connect multiple detector in parallel fans Medem CM2 2 channel current Monitor 6 core low voltage 1 x 12v fans Fan speed controls Fan Supply 6 core low voltage cable Earth Connections not shown Fan...

Страница 17: ...present within the panel N L To Contactor Coil Method 2 IMPORTANT If wired this way a warning notice must be attached to the panel to indicate that there are two separate mains feeds L N Supply in Co...

Страница 18: ...ble Gas detector 6 core low voltage cable Sender unit Mounts on the gas valve Requires a volt free NC contact 0 10v output for connecting to a fan speed controller fans Medem CM2 2 channel current Mon...

Страница 19: ...ections in the panel TB2 TB1 TB3 Use terminals TB2 A and TB2 C TB2 TB1 TB3 Use terminals TB2 A and TB2 C Multiple Switches Wire in series Remote stop buttons can be connected to the panel terminal mar...

Страница 20: ...alled so they monitor the general level of CO2 within the cooking area They should be mounted above standing head height and between 1m and 3m from the cooking line Care should be taken so they are no...

Страница 21: ...Limited Otter House Naas Road Clondalkin Dublin 22 Tel 00353 1 461 4300 E sales modernplant ie W www modernplant ie Please do not hesitate to call for advice on the following number 00353 1 461 4300...

Страница 22: ...Correct Incorrect Incorrect Never mount the valve such that the Solenoid or Sender Unit are below the horizontal In addition check that the valve is correctly installed with regard to the direction o...

Страница 23: ...IT ON VALVE WALL MOUNTING STRAP PRESSURE SENDER UNIT NOTES Solenoid coil of the valve should never be mounted below the horizontal Pressure sender unit should never be mounted upside down to protect f...

Страница 24: ...safety product range Both companies work closely to ensure the products remain best in class We stock a comprehensive range of Haws AG emergency equipment We also supply special models to the highest...

Отзывы: