9

 

 

Detector Information 

SEC-K 

Detector Location 

 
Detector location will vary dependant on the individual characteristics of the target gas that is being monitored for. The descrip-
tions below describe the position for each detector after considering these characteristics.  
 
Natural Gas 
Natural gas detectors should be mounted at high level on a wall approximately 150mm from the ceiling height and avoiding 
corners and potential dead air areas. 
 
Natural gas detectors should not be mounted below the height of the top of a doorway for example. This is because as the 
gas is slightly lighter than air it will rise filling the room from the ceiling down and will spill through the top of a door opening 
into the next room. If the detectors are mounted below this height then it will take longer the gas to reach the detector. 
 
LPG  
LPG gas is heavier than air so detectors need to be mounted at low level 100mm from the floor, consideration should be given 
to any potential mopping or wet floor height. 
 
Carbon Monoxide  
Carbon Monoxide is similarly weighted to air so detectors should be mounted between 1 to 2 meters from the floor. 
 
Carbon Dioxide  

Classroom

 Carbon Dioxide detectors under guidance from IGEM/UP11/Edition2 should be mounted at a seated head height. 

However following onsite experience this mounting height can make detectors susceptible to false readings due to direct 
breath contact. We would suggest following the guidance for mounting as per a commercial kitchen to reduce the potential for 
false alarm readings.  
 

Commercial kitchen

 Carbon Dioxide detectors should be installed so they monitor the general level of CO2 within the cooking 

area. They should be mounted above standing head height and between 1m and 3m from the cooking line. Care should be 
taken so they are not located close to the edge of a canopy or in direct flow of the supply or extract ventilation. 
 

For additional information or guidance on site specific requirements please don’t hesitate to contact us. 

Detector Testing 

 
Any installed gas detector can be tested by allowing a small amount of the target gas onto the detector head until a change of 
state is registered on the control panel. 
 
If the level of gas applied is of the set low alarm level, the LED on the detector will change from a solid green to a flashing red. 
An LED* or LCD* message indicating a low level alarm detection combined with an audible alarm on the panel will begin.  
 
If the level of gas drops below the set low alarm level the detector LED will return to a solid green and the panels audible alarm 
and LED* or LCD* message will clear.  
 
Should an emergency shut-off valve be connected to the panel this will remain open during a low alarm level detection. 
 
If the level of gas applied is of the high alarm level or above, the LED on the detector will change from a solid green to a solid 
red. An LED* or LCD* message indicating a high level alarm detected combined with an audible alarm on the panel will begin. 
  
Should an emergency shut-off valve be connected to the panel this will automatically close.  
 
Once the level of gas drops below the high alarm level the audible alarm will continue and the high alarm LED* or LCD* mes-
sage will remain.  
 
The valve cannot be reinstated until the gases have been cleared and the control panel reset.   
 

*LED, LCD or both visual outputs will change dependant on the control panel connected. 

Содержание SEC-K

Страница 1: ...The Home of Control Automation in Ireland SEC K Multi Function Control System for Kitchens...

Страница 2: ...use Each services can be individually controlled using the tactile buttons on the panel with overall secure isolation provided by the main on off switch Gas detectors for carbon dioxide and temperatur...

Страница 3: ...by testing for leaks and open appliances before allowing gas available by using Medem patented true differential gas pressure measuring across the solenoid valve This eliminates nuisance tripping of t...

Страница 4: ...Gas Pressure Proving Using the patented differential pressure proving method the SEC K can test for low pressure natural LPG gas pipe work or can pressure prove a variety of gas delivery lines includ...

Страница 5: ...d extra low voltage The connections marked CM2 or PD switches are for the connection of a current monitor or pressure switches for interlocking fans with the gas supply The connections marked detector...

Страница 6: ...13 Fire alarm input signal N C contact required 14 0 10 volt output to fan speed controllers based on CO2 and temperature levels 15 Two relays for connection to a BMS to indicate high alarm gas on EM...

Страница 7: ...present within the panel N L To Contactor Coil Method 2 IMPORTANT If wired this way a warning notice must be attached to the panel to indicate that there are two separate mains feeds L N Supply in Co...

Страница 8: ...pur 230v EM Stop Buttons TT 70c Series connected Addressable Gas detector Addressable Gas detector 6 core low voltage cable Sender unit Mounts on the gas valve Requires a volt free NC contact 0 10v ou...

Страница 9: ...a Medem engineer this can be increased to 10 years and includes a 24hr helpline During the commissioning process a Medem engineer would attend site to ensure full and correct operation of the supplie...

Страница 10: ...nough to ensure the downstream pipe work comes up to pressure factory default 5 seconds The prove time should be set at installation to find the smallest possible leak factory default 50 seconds To te...

Страница 11: ...ational test on any installed Emergency stop buttons which when operated will isolate the gas supply and remain isolated until a manual reset is completed If utilized an auto stop time out will isolat...

Страница 12: ...r Medem UK should commission this safety system whereupon a commissioning report will be forwarded to the installing agent who should provide a copy to the end user At the point of our commissioning a...

Страница 13: ...ing light yellow B blind button for displaying connected devices detectors temperature on the LCD screen LCD display For displaying system status during both installation and normal use also for displ...

Страница 14: ...evels 15 Two relays for connection to a BMS to indicate high alarm gas on EM stop low alarm One selectable for each relay 16 OPTA Over pressure check will isolate gas supply if pressure exceeds 70 mba...

Страница 15: ...sing button 22 This will bypass the ventilation interlock allowing the gas to be tested the system must not be left in this state and as such is only this for a maxim 24hour period but auto exiting Wh...

Страница 16: ...s Connect multiple detector in parallel fans Medem CM2 2 channel current Monitor 6 core low voltage 1 x 12v fans Fan speed controls Fan Supply 6 core low voltage cable Earth Connections not shown Fan...

Страница 17: ...present within the panel N L To Contactor Coil Method 2 IMPORTANT If wired this way a warning notice must be attached to the panel to indicate that there are two separate mains feeds L N Supply in Co...

Страница 18: ...ble Gas detector 6 core low voltage cable Sender unit Mounts on the gas valve Requires a volt free NC contact 0 10v output for connecting to a fan speed controller fans Medem CM2 2 channel current Mon...

Страница 19: ...ections in the panel TB2 TB1 TB3 Use terminals TB2 A and TB2 C TB2 TB1 TB3 Use terminals TB2 A and TB2 C Multiple Switches Wire in series Remote stop buttons can be connected to the panel terminal mar...

Страница 20: ...alled so they monitor the general level of CO2 within the cooking area They should be mounted above standing head height and between 1m and 3m from the cooking line Care should be taken so they are no...

Страница 21: ...Limited Otter House Naas Road Clondalkin Dublin 22 Tel 00353 1 461 4300 E sales modernplant ie W www modernplant ie Please do not hesitate to call for advice on the following number 00353 1 461 4300...

Страница 22: ...Correct Incorrect Incorrect Never mount the valve such that the Solenoid or Sender Unit are below the horizontal In addition check that the valve is correctly installed with regard to the direction o...

Страница 23: ...IT ON VALVE WALL MOUNTING STRAP PRESSURE SENDER UNIT NOTES Solenoid coil of the valve should never be mounted below the horizontal Pressure sender unit should never be mounted upside down to protect f...

Страница 24: ...safety product range Both companies work closely to ensure the products remain best in class We stock a comprehensive range of Haws AG emergency equipment We also supply special models to the highest...

Отзывы: