Detector Information 

Detector location will vary dependant on the individual characteristics of the target gas that is being monitored for.  
The descriptions below describe the position for each detector after considering these characteristics.  
 
For proper function care must be taken not to site a detector in a “dead space” or in the flow of any ventilation. 
 

Natural Gas/Methane 

Natural gas detectors should be mounted at high level on a wall approximately 150mm from the ceiling height and avoiding 
corners and potential dead air areas. 
 
Natural gas detectors should not be mounted below the height of the top of a doorway for example. This is because as the gas 
is slightly lighter than air it will rise filling the room from the ceiling down and will spill through the top of a door opening into the 
next room. If the detectors are mounted below this height then it will take longer the gas to reach the detector. 
 

LPG /Propane 

LPG gas is heavier than air so detectors need to be mounted at low level 100mm from the floor, consideration should be given 
to any potential mopping or wet floor height. 
 

Carbon Monoxide  

Carbon Monoxide is similarly weighted to air so detectors should be mounted between 1 to 2 meters from the floor. 
 

Carbon Dioxide  

Carbon Dioxide detectors should be installed so they monitor the general level of CO2 within the area. They should be mounted 
above standing head height and between 1m and 3m from the potential source. Care should be taken so they are not located 
close to the edge of a canopy or in direct flow of the supply or extract ventilation. 
 

For additional information or guidance on site specific requirements please don’t hesitate to contact us. 

Each detector has  its own Bi-Colour LED which is used to indicate the status of that detector. 
 
Not Lit:  

 

No power/comm’s. These a four wire units and all connections are required, check the polarity of both the 

 

 

 

power and the comm’s (MA/MB) terminals are correct. 

 

Flashing Green: 

Detector is warming up, the detectors will flash green on power up for 90 seconds while the sensor  

 

 

 

elements stabilize. The system will ignore any detectors while flashing.  

 
Solid Green:   

Detector is powered and active. 

Note

The detectors will still require correctly addressing (using the address 

 

 

 

selector pot) and learning by the system using button  

(13, see page 4)

 

Flashing Red:  

Low level alarm. All detectors have both a low and high level alarm, low level alarms serve as a warning 

 

 

 

that an unsafe condition maybe building and gives chance to intervene before loss of gas service. 

 
Solid Red 

 

High level alarm. An unsafe level of the target gas have been reached and the system will isolate the  

 

 

 

gas supply. The cause of the alarm will require identifying and resolving before  the gas supply can be re-

 

 

 

established. 

 
After installation a simple bump test can be performed by using an appropriate level test gas in order to check operation. Full 
testing and calibration checking takes place during a Medem commissioning. 

AGDS-M 

    Detector Location 

    Detector Indications 

Содержание AGDS-M

Страница 1: ... this safety system is installed and commissioned to the satisfaction of the manufacturer A commissioning certificate must be issued to the end user along with instructions for the operation of the equipment As the Manufacturer Medem UK should commission this safety system whereupon a commissioning report will be forwarded to the installing agent who should provide a copy to the end user At the po...

Страница 2: ...h that they only require to be connected to the panel and functionally tested The system is designed to auto reset from a high alarm condition after the target gas has fallen below the alarm level In the event of a high alarm from one of the sensors the system will indicate locally and provides contacts for remote monitoring The system will automatically restart after a power failure Control Panel...

Страница 3: ...ygen Temperature 10 Panel Mode switches factory set do not alter 11 Internal tone on off 12 Spare 13 Learn field device button press once only when all detectors are connected and powered 14 Display detector information 1 2 on screen 15 Display detector information 3 4 on screen 16 BMS Relay setting see page 4 for details Power at 230 volts from a 3amp fused spur 16 1 2 3 4 5 7 8 9 10 11 12 13 14 ...

Страница 4: ...e commissioned a er installa on by Medem UK This will extend the warranty period from 5 years to 10 years and ensure the system is working as designed Please see warranty condi ons that came with the main panel 16 Learn Dets Any gas detectors connected to the system will require learning First ensure all detectors are set to a unique ID address using the selector switch on the detectors themselves...

Страница 5: ...uctions for more guidance AGDS M Detector Information VE supply Comm s From either the main panel or an extender Detectors are wired in parallel and can be connected to one another daisy chain Address Selector Each detector must be set to its own address 1 4 and then learnt using button 13 see page 4 Connection and addressing Status LED All current wiring regulations must be followed with referenc...

Страница 6: ...nd between 1m and 3m from the potential source Care should be taken so they are not located close to the edge of a canopy or in direct flow of the supply or extract ventilation For additional information or guidance on site specific requirements please don t hesitate to contact us Each detector has its own Bi Colour LED which is used to indicate the status of that detector Not Lit No power comm s ...

Страница 7: ...ld be wired in series with the EM stop buttons To EM Stop connections in the panel Indicator bar shows when pressed Normal EM Stop Activated Multiple Stop Buttons Single Stop Buttons Resetting indicator bar The stop buttons supplied by Medem are of a Push Glass key resettable style when activated a yellow indicator bar will show and the unit will require resetting using the key provided Multiple s...

Страница 8: ...ier Medem UK will exchange faulty valves for return to the manufacturer 5 Where a Medem UK engineer or another company appointed by Medem UK commission and installed system then that system will carry a ten year warranty This applies to the main panel and the sender unit At the time of commissioning a security label with a serial number will be attached to the main panel box photographs and a comp...

Страница 9: ...in circuit board on the right hand side just over half way up the board pressing this once allows the panel to learn how many and which type of detectors are fitted 8 Press and keep pressed the display detectors1 2 or 3 4 button whilst checking on the display that all the detectors have been recognised by the panel 9 At this point press the reset button the panel will open the gas valve Checklist ...

Отзывы: