9
00253
It is essential that the installation of the AGDS-M is carried out in the order given
below to ensure the correct operation of the system.
First read the system description sheet before following the
instructions below
1.
Connect any additional EM stop buttons or thermal links in series to the terminals marked “EM stop” (
6
)
2.
Each detector/device has a rotary address switch, each switch should be set to a different number 1-4. Then connect the gas
detectors to terminals marked “detectors” on the panel. Detectors are wired in parallel. “Daisy chain” (
08 & 09
)
3.
Connect fire alarm, ensure volt free n/c (
7
)
4.
Ensure any BMS connections are made to the relays (
4 & 5
)
5.
Connect the 3 amp fused spur 240 volt supply to marked terminals.
6.
Once power is connected to the panel the detectors will flash the green LEDs for 90 seconds after which the LEDs will be on
continuously.
7.
Press the “learn field button” (
13
) this is on the main circuit board on the right hand side, just over half way up the board
pressing this once allows the panel to learn how many and which type of detectors are fitted.
8.
Press and keep pressed the “display detectors1-2 or 3-4” button whilst checking on the display that all the detectors have
been recognised by the panel.
9.
At this point press the “reset” button, the panel will open the gas valve.
Checklist
AGDS-M
Please do not hesitate to call for advice on the
following number:
0161 233 0600 office hours
In the event of any alert the system will always give a reason on screen as to the
cause.
Common messages you may receive are shown below with further explanation.
If you require any help or if anything is unclear then please contact technical support on 0161 233 0600
messages
Detector fault XX
The system believes it has lost connection to a detector on address XX, verify detector addresses and press the “learn button”
(23)
.
Verify all connected detectors are being registered by using the “Show Dets” buttons 14 & 15. If you have no detectors connected to
the system pressing the learn button will clear the error message.