4
00253
System Settings
AGDS-M
Status
AX1
AX2
AX3
AX4
EM Stop - ES
OFF
OFF
ON
OFF
Fire Panel Active -FA
ON
OFF
ON
OFF
High Alarm - HA
OFF
ON
ON
OFF
Low Alarm - LA
ON
ON
ON
OFF
Gas On/Off
OFF
OFF
OFF
ON
Detector Fault - DF
ON
OFF
OFF
ON
Generic Fault (ES, FA, HA, LA, DF)
OFF
ON
OFF
ON
There are two mains rated relays
4 & 5
, for connection to a BMS or sounder/Beacon. Each relay is able to be set to
report one of the status in the table below.
Max switching 230 volts 5amp’s
4, 5 & 16. BMS Relays and setting switch
Notes.
It is recommended that all systems are commissioned a er installa on by Medem UK. This will extend the warranty period from 5
years to 10 years and ensure the system is working as designed.
Please see warranty condi ons that came with the main panel
16
Learn Dets.
Any gas detectors connected to the system will require “learning”. First ensure all detectors are set to a
unique ID address using the selector switch on the detectors themselves (address’s 1 to 4). Having
addressed each detector, press the learn Dets button (
13
), the system will scan and store any connected
detectors.
Shows Dets 1&2, 3&4.
To verify that all detectors have been successfully learnt use the Show Dets buttons 14/15 to verify the
detectors are connected correctly.
13, 14 & 15 Learn and Display Detectors
13
14
15