OWNER’S MANUAL

AIR FOR
COMBUSTION
AND VENTILATION

Continued

 WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space

or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of
the methods described in the 

National Fuel Gas Code, ANS Z223.1, 1992, Section 5.3 or applicable local codes.

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined space.

Space

: Includes the room in which you will install heater plus any adjoining rooms with doorless

passageways or ventilation grills between the rooms.

1.

Determine the volume of the space (length x width x height).

Length x Width x Height = ___________________ cu. ft. (volume of space)

Example:

 Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of
the space.

2.

Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

__________________  (volume of space) 

÷

 50 cu. ft. = (Maximum Btu/Hr the space can support)

Example:

 2560 cu. ft. (volume of space) 

÷

 50 cu. ft. = 51.2 or 51,200 (maximum Btu/Hr the space can support)

3.

Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

___________________ Btu/Hr

Gas water heater*

___________________ Btu/Hr

Gas furnace

___________________ Btu/Hr

Vented gas heater

___________________ Btu/Hr

Gas fireplace logs

___________________ Btu/Hr

Other gas appliances*___________________ Btu/Hr
Total

___________________ Btu/Hr

* Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.

Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_____________________ Btu/Hr (maximum the space can support)

_____________________ Btu/Hr (actual amount of Btu/Hr used)

Example:

51,200 Btu/Hr (maximum the space can support)

60,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support.
You must provide additional fresh air. Your options are as follows:

A. Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin-

ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.

B. Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 6.

C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no
additional fresh air ventilation.

Example:

Gas water heater

40,000

Btu/Hr

Vent-free heater

+

20,000

Btu/Hr

Total

=

60,000

Btu/Hr

Continued

Содержание MBN20LB

Страница 1: ...ervice agency or the gas supplier MBN20LB This appliance may be installed in an aftermarket manufactured mobile home where not prohibited by state or local codes Aftermarket Completion of sale not for...

Страница 2: ...lot light safety system The ODS shuts down the heater if not enough fresh air is available See Air for Combustion and Ventilation pages 4 through 6 6 Keep all air openings in front and bot tom of heat...

Страница 3: ...al Fire Protection Association Inc Batterymarch Park Quincy MA 02269 UNPACKING 1 Remove heater from carton 2 Remove all protective packaging ap plied to heater for shipment 3 Check heater for any ship...

Страница 4: ...ating of one perm 6 x 10 11 kg per pa sec m2 or less with open ings gasketed or sealed and b weather stripping has been added on openable windows and doors and c caulking or sealants are applied to ar...

Страница 5: ...el burning appliances in the space Vent free heater ___________________Btu Hr Gas water heater ___________________Btu Hr Gas furnace ___________________Btu Hr Vented gas heater ___________________Btu...

Страница 6: ...FPA 54 ANS Z223 1 Section5 3 AirforCombustionand Ventilation for required size of ventilation grills or ducts IMPORTANT Do not provide openings for inlet or outlet air into attic if attic has a thermo...

Страница 7: ...furniture clothing or other flammable objects are less than 36 inches from the front top or sides of the heater as a fireplace insert in high traffic areas in windy or drafty areas You can locate mode...

Страница 8: ...acing Heater On Mounting Bracket 1 Locate two horizontal slots on back panel of heater 2 Place heater onto mounting bracket Slide horizontal slots onto stand out tabs on mounting bracket INSTALLATION...

Страница 9: ...is will prevent excess sealant from going into pipe Excess sealant in the pipe could result in clogged heater valves Typical Inlet Pipe Diameters 20 000 Btu Hr models 3 8 or greater 30 000 Btu Hr mode...

Страница 10: ...gas supply Check reconnected fittings for leaks TestPressuresEqualToorLessThan 1 2 PSIG 1 Close manual shutoff valve see Fig ure 13 2 Pressurize supply piping system by ei ther using compressed air or...

Страница 11: ...rol knob pressed in for five 5 seconds see Figure 15 Note You may be running this heater for the first time after hook ing up to gas supply If so the con trol knob may need to be pressed in for 30 sec...

Страница 12: ...ect Pilot Flame Pattern BURNER FLAME PATTERN Figure 19 shows a correct burner flame pattern Figure20showsanincorrectburner flame pattern The incorrect burner flame patternshowsyellowtippingoftheflame...

Страница 13: ...t flame to go out This problem could be caused by one or both of the following A Low gas pressure B Dirty or partially clogged ODS pilot 6 Thermocouple damaged 7 Control valve damaged 1 Burner orifice...

Страница 14: ...er blocked 4 Dirty or partially clogged burner orifice 1 When heated vapors from furniture pol ish wax carpet cleaners etc turn into white powder resdue REMEDY 1 Clean burner see Cleaning and Mainte n...

Страница 15: ...Control valve defective 1 Foreign matter between control valve and burner 2 Gas leak See Warning statement above 1 Not enough combustion ventilation air OBSERVED PROBLEM Heater produces a clicking tic...

Страница 16: ...heater will not produce specified heat When Gas Quality Is Bad pilot will not stay lit burner will produce flames and soot heater will backfire when lit You may feel your gas pressure is too low or g...

Страница 17: ...00A Includes ON OFF switch Note Use only original replacement parts Thiswillprotectyourwarrantycoveragefor parts replaced under warranty PARTS UNDER WARRANTY Contact authorized dealers of this product...

Страница 18: ...18 105735 VENT FREE NATURAL GAS HEATERS BLUE FLAME MBN20LB 12 1 12 2 ODS Pilot 1 2 3 4 5 6 8 8 9 10 10 11 12 13 14 17 19 25 21 23 24 7 22 27 26 20 16 18 15 MBN20LB ILLUSTRATED PARTS BREAKDOWN...

Страница 19: ...49 01 Nut M5 2 12 100701 01 ODS Pilot Assembly 1 12 1 098514 01 Thermocouple 1 12 2 098594 01 Ignitor Electrode 1 13 103446 01 Burner 1 14 099387 05 3 16 Pilot Tubing 1 15 103845 06 Injector 1 16 0990...

Страница 20: ...hed with the unit This warranty does not apply to parts that are not in original condition because of normal wear and tear or parts that fail or become damaged as a result of misuse accidents lack of...

Отзывы: