OWNER’S MANUAL

OBSERVED PROBLEM

When ignitor button is pressed, there is no
spark at ODS/pilot

When ignitor button is pressed, there is
spark at ODS/pilot but no ignition

ODS/pilot lights but flame goes out when
control knob is released

Burner does not light after ODS/pilot is lit

Delayed ignition of burner

TROUBLESHOOTING

 WARNING: Turn off and un-

plug heater and let cool before
servicing. Only a qualified ser-
vice person should service and
repair heater.

Note: 

 All troubleshooting items are listed

in order of operation.

  CAUTION: Never use a wire,

needle, or similar object to clean
ODS/pilot. This can damage ODS/
pilot unit.

POSSIBLE  CAUSE

1. Ignitor electrode positioned wrong
2. Ignitor electrode broken
3. Ignitor electrode not connected to

ignitor cable

4. Ignitor cable pinched or wet

5. Broken ignitor cable
6. Bad piezo ignitor

1. Gas supply turned off or manual shutoff

valve closed

2. Control knob not in PILOT position
3. Control knob not pressed in while in

PILOT position

4. Air in gas lines when installed

5. ODS/pilot is clogged

6. Gas regulator setting is not correct

1. Control knob not fully pressed in
2. Control knob not pressed in long enough

3. Manual shutoff valve not fully open
4. Thermocouple connection loose at con-

trol valve

5. Pilot flame not touching thermocouple,

which allows thermocouple to cool, caus-
ing pilot flame to go out. This problem
could be caused by one or both of the
following:
A) Low gas pressure
B) Dirty or partially clogged ODS/pilot

6. Thermocouple damaged
7. Control valve damaged

1. Burner orifice is clogged

2. Burner orifice diameter is too small
3. Inlet gas pressure is too low

1. Manifold pressure is too low
2. Burner orifice is clogged

3. Inlet gas pressure is too low

REMEDY

1. Replace ignitor
2. Replace ignitor
3. Reconnect ignitor cable

4. Free ignitor cable if pinched by any metal

or tubing. Keep ignitor cable dry

5. Replace ignitor cable
6. Replace piezo ignitor

1. Turn on gas supply or open manual shutoff

valve

2. Turn control knob to PILOT position
3. Press in control knob while in PILOT

position

4. Continue holding down control knob.

Repeat igniting operation until air is re-
moved

5. Clean ODS/pilot (see Cleaning and Main-

tenance, page 12) or replace ODS/pilot
assembly

6. Replace gas regulator

1. Press in control knob fully
2. After ODS/pilot lights, keep control knob

pressed in 30 seconds

3. Fully open manual shut-off valve
4. Hand tighten until snug, then tighten 1/4

turn more

5. A) Contact local natural gas company

B) Clean ODS/pilot (see Cleaning and
Maintenance
, page 12) or replace ODS/
pilot assembly

6. Replace thermocouple
7. Replace control valve

1. Clean burner (see Cleaning and Mainte-

nance, page 12) or replace burner orifice

2. Replace burner orifice
3. Contact local natural gas company

1. Co. natural gas company
2. Clean burner (see Cleaning and Mainte-

nance, page 12) or replace burner orifice

3. Contact local natural gas company

Continued

Содержание MBN20LB

Страница 1: ...ervice agency or the gas supplier MBN20LB This appliance may be installed in an aftermarket manufactured mobile home where not prohibited by state or local codes Aftermarket Completion of sale not for...

Страница 2: ...lot light safety system The ODS shuts down the heater if not enough fresh air is available See Air for Combustion and Ventilation pages 4 through 6 6 Keep all air openings in front and bot tom of heat...

Страница 3: ...al Fire Protection Association Inc Batterymarch Park Quincy MA 02269 UNPACKING 1 Remove heater from carton 2 Remove all protective packaging ap plied to heater for shipment 3 Check heater for any ship...

Страница 4: ...ating of one perm 6 x 10 11 kg per pa sec m2 or less with open ings gasketed or sealed and b weather stripping has been added on openable windows and doors and c caulking or sealants are applied to ar...

Страница 5: ...el burning appliances in the space Vent free heater ___________________Btu Hr Gas water heater ___________________Btu Hr Gas furnace ___________________Btu Hr Vented gas heater ___________________Btu...

Страница 6: ...FPA 54 ANS Z223 1 Section5 3 AirforCombustionand Ventilation for required size of ventilation grills or ducts IMPORTANT Do not provide openings for inlet or outlet air into attic if attic has a thermo...

Страница 7: ...furniture clothing or other flammable objects are less than 36 inches from the front top or sides of the heater as a fireplace insert in high traffic areas in windy or drafty areas You can locate mode...

Страница 8: ...acing Heater On Mounting Bracket 1 Locate two horizontal slots on back panel of heater 2 Place heater onto mounting bracket Slide horizontal slots onto stand out tabs on mounting bracket INSTALLATION...

Страница 9: ...is will prevent excess sealant from going into pipe Excess sealant in the pipe could result in clogged heater valves Typical Inlet Pipe Diameters 20 000 Btu Hr models 3 8 or greater 30 000 Btu Hr mode...

Страница 10: ...gas supply Check reconnected fittings for leaks TestPressuresEqualToorLessThan 1 2 PSIG 1 Close manual shutoff valve see Fig ure 13 2 Pressurize supply piping system by ei ther using compressed air or...

Страница 11: ...rol knob pressed in for five 5 seconds see Figure 15 Note You may be running this heater for the first time after hook ing up to gas supply If so the con trol knob may need to be pressed in for 30 sec...

Страница 12: ...ect Pilot Flame Pattern BURNER FLAME PATTERN Figure 19 shows a correct burner flame pattern Figure20showsanincorrectburner flame pattern The incorrect burner flame patternshowsyellowtippingoftheflame...

Страница 13: ...t flame to go out This problem could be caused by one or both of the following A Low gas pressure B Dirty or partially clogged ODS pilot 6 Thermocouple damaged 7 Control valve damaged 1 Burner orifice...

Страница 14: ...er blocked 4 Dirty or partially clogged burner orifice 1 When heated vapors from furniture pol ish wax carpet cleaners etc turn into white powder resdue REMEDY 1 Clean burner see Cleaning and Mainte n...

Страница 15: ...Control valve defective 1 Foreign matter between control valve and burner 2 Gas leak See Warning statement above 1 Not enough combustion ventilation air OBSERVED PROBLEM Heater produces a clicking tic...

Страница 16: ...heater will not produce specified heat When Gas Quality Is Bad pilot will not stay lit burner will produce flames and soot heater will backfire when lit You may feel your gas pressure is too low or g...

Страница 17: ...00A Includes ON OFF switch Note Use only original replacement parts Thiswillprotectyourwarrantycoveragefor parts replaced under warranty PARTS UNDER WARRANTY Contact authorized dealers of this product...

Страница 18: ...18 105735 VENT FREE NATURAL GAS HEATERS BLUE FLAME MBN20LB 12 1 12 2 ODS Pilot 1 2 3 4 5 6 8 8 9 10 10 11 12 13 14 17 19 25 21 23 24 7 22 27 26 20 16 18 15 MBN20LB ILLUSTRATED PARTS BREAKDOWN...

Страница 19: ...49 01 Nut M5 2 12 100701 01 ODS Pilot Assembly 1 12 1 098514 01 Thermocouple 1 12 2 098594 01 Ignitor Electrode 1 13 103446 01 Burner 1 14 099387 05 3 16 Pilot Tubing 1 15 103845 06 Injector 1 16 0990...

Страница 20: ...hed with the unit This warranty does not apply to parts that are not in original condition because of normal wear and tear or parts that fail or become damaged as a result of misuse accidents lack of...

Отзывы: