VENT-FREE NATURAL GAS HEATER

 MBN10LA AND MBN6LA

AIR FOR
COMBUSTION AND
VENTILATION

Today’s homes are built more energy effi-
cient than ever. New materials, increased
insulation, and new construction methods
help reduce heat loss in homes. Home owners
weather strip and caulk around windows and
doors to keep the cold air out and the warm air
in. During heating months, home owners
want their homes as airtight as possible.

While it is good to make your home energy
efficient, your home needs to breathe. Fresh
air must enter your home. All fuel-burning
appliances need fresh air for proper com-
bustion and ventilation.

Exhaust fans, fireplaces, clothes dryers, and
fuel burning appliances draw air from the
house to operate. You must provide ad-
equate fresh air for these appliances. This
will insure proper venting of vented fuel-
burning appliances.

PROVIDING ADEQUATE
VENTILATION

The following are excerpts from National
Fuel Gas Code. NFPA 54/ANS Z223.1, Sec-
tion 5.3, Air for Combustion and Ventilation.

All spaces in homes fall into one of the three
following ventilation classifications:

1.

Unusually Tight Construction

2.

Unconfined Space

3.

Confined Space

The information on pages 5 and  6 will help
you classify your space and provide ad-
equate ventilation.

Unusually Tight Construction

The air that leaks around doors and win-
dows may provide enough fresh air for
combustion and ventilation. However, in
buildings of unusually tight construction,
you must provide additional fresh air.

Unusually tight construction is de-
fined as construction where:

a.

walls and ceilings exposed to the
outside atmosphere have a con-
tinuous water vapor retarder with
a rating of one perm (6 x 10

-11

 kg

per pa-sec-m

2

) or less with open-

ings gasketed or sealed 

and

b. weather stripping has been

added on openable windows and
doors 

and

c.

caulking or sealants are applied
to areas such as joints around
window and door frames, be-
tween sole plates and floors, be-
tween wall-ceiling joints, be-
tween wall panels, at penetra-
tions for plumbing, electrical, and
gas lines, and at other openings.

If your home meets all of the three
criteria above, you must provide ad-
ditional fresh air. See 

Ventilation Air

From Outdoors, page 6.

If your home does not meet all of the
three criteria above, proceed 

Deter-

mining Fresh-Air Flow for Heater
Location, page 5.

Confined and Unconfined Space

The National Fuel Gas Code ANS Z223.1
defines a confined space as a space whose
volume is less than 50 cubic feet per 1,000
Btu per hour (4.8 m

3

 per kw) of the aggre-

gate input rating of all appliances installed
in that space and an unconfined space as a
space whose volume is not less than 50
cubic feet per 1,000 Btu per hour (4.8 m

3

 per

kw) of the aggregate input rating of all
appliances installed in that space. Rooms
communicating directly with the space in
which the appliances are installed*, through
openings not furnished with doors, are con-
sidered a part of the unconfined space.

This heater shall not be installed in a con-
fined space or unusually tight construction
unless provisions are provided for adequate
combustion and ventilation air.

* Adjoining rooms are communicating only
if there are doorless passageways or ventila-
tion grills between them.

 WARNING: This heater shall

not be installed in a confined space
or unusually tight construction
unless provisions are provided
for adequate combustion and ven-
tilation air. Read the following in-
structions to insure proper fresh
air for this and other fuel-burning
appliances in your home.

Содержание MBN10LA

Страница 1: ...service agency or the gas supplier WARNING Improper installa tion adjustment alteration ser vice ormaintenancecancause injury or property damage Re fer to this manual for correct installation and ope...

Страница 2: ...o run properly This heater has an oxygen depletion sensor ODS pilot light safety system The ODS shuts down the heater if not enough fresh air is available See Fresh Air for Combus tion and Ventilation...

Страница 3: ...or Button 1 Remove heater from carton 2 Remove all protective packaging ap plied to heater for shipment 3 Check heater for any shipping damage If heater is damaged promptly inform dealer where you bou...

Страница 4: ...rating of one perm 6 x 10 11 kg per pa sec m2 or less with open ings gasketed or sealed and b weather stripping has been added on openable windows and doors and c caulking or sealants are applied to...

Страница 5: ...l fuel burning appliances in the space Vent free heater _____________ Btu Hr Gas water heater _____________ Btu Hr Gas furnace _____________ Btu Hr Vented gas heater _____________ Btu Hr Gas fireplace...

Страница 6: ...ls or ducts Figure 2 Ventilation Air from Inside Building WARNING Rework work sheet adding the space of the adjoining unconfined space The combined spaces must have enough fresh air to supply all appl...

Страница 7: ...rents move heat to wall sur faces next to heater Installing heater next to vinyl or cloth wall coverings or operating heater where impurities such as to bacco smoke aromatic candles cleaning fluids oi...

Страница 8: ...lls 1 4 to 1 2 thick Figure 7 Popping Open Anchor Wings For Thin Walls Figure 6 Folding Anchor Placing Heater On Mounting Screws 1 Locate two keyhole slots on back panel of heater see Figure 9 2 Place...

Страница 9: ...ible location The equip ment shutoff valve is for turning on or shutting off the gas to the appliance Installsedimenttrapinsupplylineasshown in Figure 12 Locate sediment trap where it is within reach...

Страница 10: ...heater is in the OFF position 4 Check all joints from equipment shutoff valve to control valve see Figure 14 Apply mixture of liquid soap and wa ter to gas joints Bubbles forming show a leak 5 Correct...

Страница 11: ...tton until pilot lights Note If pilot does not stay lit refer to Troubleshooting pages 13 through 15 Also contact a qualified service personorgassupplierforrepairs Un til repairs are made light pilot...

Страница 12: ...circu lating air passageways of heater clean Inspect these areas of heater before each use Have heaterinspectedyearlybyaquali fied service person Heater may need more frequent cleaning due to excessiv...

Страница 13: ...ully open 4 Thermocouple connection loose at con trol valve 5 Pilot flame not touching thermocouple which allows thermocouple to cool causing pilot flame to go out This prob lem could be caused by one...

Страница 14: ...e 1 When heated vapors from furniture pol ish wax carpet cleaners etc turn into white powder residue REMEDY 1 Clean burner orifice see Cleaning and Maintenance page 12 or replace burner orifice 2 Repl...

Страница 15: ...Gas Connections page 10 1 Refer to Fresh Air for Combustion and Ventilation requirements page 4 OBSERVED PROBLEM Heater produces a clicking ticking noise just after burner is lit or shut off Heater pr...

Страница 16: ...16 105717 VENT FREE NATURAL GAS HEATER MBN10LA AND MBN6LA 12 2 12 1 ILLUSTRATED PARTS LIST MBN10LA MBN6LA 10 12 11 1 2 3 4 5 6 7 9 8 10 13 14 15 17 18 21 22 25 20 24 23 19 26 27 16...

Страница 17: ...01 098249 01 Nut M5 2 12 099440 03 100701 03 ODS Pilot Assembly 1 12 1 098514 01 098514 01 Thermocouple 1 12 2 098594 01 098594 01 Ignitor Electrode 1 13 104263 01 104263 01 Burner 1 14 099387 05 099...

Страница 18: ...e part to the factory PARTS NOT UNDER WARRANTY Contact authorized dealers of this product If they cannot supply original replacement part s contact Cans Unlimited Incorpo rated Parts Department at 1 8...

Страница 19: ...___________________ _______________________________________________________________________________________________ ____________________________________________________________________________________...

Страница 20: ...furnished with the unit This warranty does not apply to parts that are not in original condition because of normal wear and tear or parts that fail or become damaged as a result of misuse accidents la...

Отзывы: