Medallion MBN10LA Скачать руководство пользователя страница 10

10

105717

VENT-FREE NATURAL GAS HEATER

 MBN10LA AND MBN6LA

CHECKING GAS
CONNECTIONS

 WARNING: Test all gas pip-

ing and connections for leaks
after installing or servicing. Cor-
rect all leaks at once.

 WARNING: Never use an open

flame to check for a leak. Apply a
mixture of liquid soap and water
to all joints. Bubbles forming show
a leak. Correct all leaks at once.

Pressure Testing Gas Supply
Piping System

Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)

1.

Disconnect appliance with its appliance
main gas valve (control valve) and equip-
ment shutoff valve from gas supply pip-
ing system. Pressures in excess of 1/2 psig
will damage heater regulator.

2.

Cap off open end of gas pipe where
equipment shutoff valve was connected.

3.

Pressurize supply piping system by either
using compressed air or opening main gas
valve located on or near gas meter.

4.

Check all joints of gas supply piping
system. Apply mixture of liquid soap
and water to gas joints. Bubbles form-
ing show a leak.

5.

Correct all leaks at once.

6.

Reconnect heater and equipment
shutoff valve to gas supply. Check re-
connected fittings for leaks.

Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)

1.

Close equipment shutoff valve (see Fig-
ure 13).

2.

Pressurize supply piping system by either
using compressed air or opening main gas
valve located on or near gas meter.

3.

Check all joints from gas meter to equip-
ment shutoff valve (see Figure 14). Ap-
ply mixture of liquid soap and water to
gas joints. Bubbles forming show a leak.

4.

Correct all leaks at once.

Pressure Testing Heater Gas
Connections

1.

Open equipment shutoff valve (see Fig-
ure 13).

2.

Open main gas valve located on or near
gas meter.

3.

Make sure control knob of heater is in
the OFF position.

4.

Check all joints from equipment shutoff
valve to control valve (see Figure 14).
Apply mixture of liquid soap and wa-
ter to gas joints. Bubbles forming show
a leak.

5.

Correct all leaks at once.

6.

Light heater (see Operating Heater).
Check the rest of the internal joints for
leaks.

7.

Turn off heater (see To Turn Off Gas to
Appliance
, page 11).

8.

Replace front panel.

ON

POSIT

PO

Figure 13 - Equipment Shutoff Valve

Equipment
Shutoff
Valve

Open

Closed

Control Valve Location

Gas Meter

Equipment Shutoff Valve

Figure 14 - Checking Gas Joints

OPERATING
HEATER

FOR YOUR SAFETY

READ BEFORE

LIGHTING

A. This appliance has a pilot which must

be lighted by hand. When lighting the
pilot, follow these instructions exactly.

B. BEFORE LIGHTING smell all

around the appliance area for gas. Be
sure to smell next to the floor because
some gas is heavier than air and will
settle on the floor.

WHAT TO DO IF YOU SMELL
GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do

not use any phone in your building.

• Immediately call your gas supplier

from a neighbor’s phone. Follow
the gas supplier’s instructions.

• If you cannot reach your gas sup-

plier, call the fire department.

C. Use only your hand to push in or turn

the gas control knob. Never use tools.
If the knob will not push in or turn
by hand, don’t try to repair it, call a
qualified service technician or gas
supplier. Force or attempted repair
may result in a fire or explosion.

D. Do not use this appliance if any part

has been under water. Immediately
call a qualified service technician to
inspect the appliance and to replace
any part of the control system and
any gas control which has been un-
der water.

 WARNING: If you do not fol-

low these instructions exactly, a
fire or explosion may result caus-
ing property damage, personal
injury or loss of life.

INSTALLATION

Continued

Содержание MBN10LA

Страница 1: ...service agency or the gas supplier WARNING Improper installa tion adjustment alteration ser vice ormaintenancecancause injury or property damage Re fer to this manual for correct installation and ope...

Страница 2: ...o run properly This heater has an oxygen depletion sensor ODS pilot light safety system The ODS shuts down the heater if not enough fresh air is available See Fresh Air for Combus tion and Ventilation...

Страница 3: ...or Button 1 Remove heater from carton 2 Remove all protective packaging ap plied to heater for shipment 3 Check heater for any shipping damage If heater is damaged promptly inform dealer where you bou...

Страница 4: ...rating of one perm 6 x 10 11 kg per pa sec m2 or less with open ings gasketed or sealed and b weather stripping has been added on openable windows and doors and c caulking or sealants are applied to...

Страница 5: ...l fuel burning appliances in the space Vent free heater _____________ Btu Hr Gas water heater _____________ Btu Hr Gas furnace _____________ Btu Hr Vented gas heater _____________ Btu Hr Gas fireplace...

Страница 6: ...ls or ducts Figure 2 Ventilation Air from Inside Building WARNING Rework work sheet adding the space of the adjoining unconfined space The combined spaces must have enough fresh air to supply all appl...

Страница 7: ...rents move heat to wall sur faces next to heater Installing heater next to vinyl or cloth wall coverings or operating heater where impurities such as to bacco smoke aromatic candles cleaning fluids oi...

Страница 8: ...lls 1 4 to 1 2 thick Figure 7 Popping Open Anchor Wings For Thin Walls Figure 6 Folding Anchor Placing Heater On Mounting Screws 1 Locate two keyhole slots on back panel of heater see Figure 9 2 Place...

Страница 9: ...ible location The equip ment shutoff valve is for turning on or shutting off the gas to the appliance Installsedimenttrapinsupplylineasshown in Figure 12 Locate sediment trap where it is within reach...

Страница 10: ...heater is in the OFF position 4 Check all joints from equipment shutoff valve to control valve see Figure 14 Apply mixture of liquid soap and wa ter to gas joints Bubbles forming show a leak 5 Correct...

Страница 11: ...tton until pilot lights Note If pilot does not stay lit refer to Troubleshooting pages 13 through 15 Also contact a qualified service personorgassupplierforrepairs Un til repairs are made light pilot...

Страница 12: ...circu lating air passageways of heater clean Inspect these areas of heater before each use Have heaterinspectedyearlybyaquali fied service person Heater may need more frequent cleaning due to excessiv...

Страница 13: ...ully open 4 Thermocouple connection loose at con trol valve 5 Pilot flame not touching thermocouple which allows thermocouple to cool causing pilot flame to go out This prob lem could be caused by one...

Страница 14: ...e 1 When heated vapors from furniture pol ish wax carpet cleaners etc turn into white powder residue REMEDY 1 Clean burner orifice see Cleaning and Maintenance page 12 or replace burner orifice 2 Repl...

Страница 15: ...Gas Connections page 10 1 Refer to Fresh Air for Combustion and Ventilation requirements page 4 OBSERVED PROBLEM Heater produces a clicking ticking noise just after burner is lit or shut off Heater pr...

Страница 16: ...16 105717 VENT FREE NATURAL GAS HEATER MBN10LA AND MBN6LA 12 2 12 1 ILLUSTRATED PARTS LIST MBN10LA MBN6LA 10 12 11 1 2 3 4 5 6 7 9 8 10 13 14 15 17 18 21 22 25 20 24 23 19 26 27 16...

Страница 17: ...01 098249 01 Nut M5 2 12 099440 03 100701 03 ODS Pilot Assembly 1 12 1 098514 01 098514 01 Thermocouple 1 12 2 098594 01 098594 01 Ignitor Electrode 1 13 104263 01 104263 01 Burner 1 14 099387 05 099...

Страница 18: ...e part to the factory PARTS NOT UNDER WARRANTY Contact authorized dealers of this product If they cannot supply original replacement part s contact Cans Unlimited Incorpo rated Parts Department at 1 8...

Страница 19: ...___________________ _______________________________________________________________________________________________ ____________________________________________________________________________________...

Страница 20: ...furnished with the unit This warranty does not apply to parts that are not in original condition because of normal wear and tear or parts that fail or become damaged as a result of misuse accidents la...

Отзывы: