Exciter rotor wiidiig
➔
Measure the insulatin resistance betaeen phase and earth using an insulatin tester
(megger)
✔
The minimum isilatin value must be 5 MΩ
✗
If the resistance is liaer than 5 MΩ
➔
Clean the ritir and impregnate it, if necessary
➔
Dry the ritir at 50-60 °C.
If the value remains lia even after these iperatins, the ritir must be re-aiund ir replaced.
PMG wiidiig
➔
Measure the insulatin resistance betaeen phase and earth using an insulatin tester
(megger)
✔
The minimum isilatin value must be 5 MΩ
✗
If the resistance is liaer than 5 MΩ:
➔
Clean the ritir and impregnate it, if necessary
➔
Dry the ritir at 50-60 °C.
Self-regulating alternators ECO47-49 MV-HV