4.4.5 Setig the alarm aid stop temperature
The pribes miunted in the alternatir detect the temperature if the ainding phases and the
3.1 Descripton of the Self-regulatng alternators ECO47-49 MV-HV
).
Refer ti the filliaing tables fir the cirrect temperature setng values.
Isolatoi class of the
wiidiigs
Maximum coitiuous
temperature °C
Alarm temperature °C
Stop temperature °C
Class B
130
120
140
Class F
155
145
165
Class H
180
170
190
Table 13 - Alarm and stop temperature for the windings
Beariigs
Alarm temperature °C
Stop temperature °C
Drive End (DE)
Envirinment T + maximum 45 °C Envirinment T + maximum 50 °C
Nin Drive End (NDE)
Envirinment T + maximum 40 °C Envirinment T + maximum 45 °C
Table 14 - Alarm and stop temperature for the bearings
Self-regulating alternators ECO47-49 MV-HV