HM500 DISPLAY PANEL OF GENERATOR CONTROLLER USER MANUAL
31
13.
Mains un/loading input:
connect to
auxiliary point of mains loading switch.
14.
Shades status input
.
15.
Auto start disabled:
gens will not start if
there is signal input whatever mains
normal or not.
16.Auto stop disabled: gens will not stop if
there is signal input whatever mains
normal or not.
17.
Stop by radiator if high temperature:
The controller will shutdown the gens after
high speed cooling down delay when
temperature is too high if this signal is valid
and gens under normal running the
controller will shutdown the gens directly if
the signal is not valid.
18.
Remote start (with load):
the gens comes
into start procession if this signal is valid
and under auto mode.
19.
Soundproof alarm:
audio alarm output is
disabled if there is signal output.
20.
Front face button disabled:
any button
except for page button is disabled if there
is signal output.
21.
Meter mode:
all output are disabled, alarm
and warns are invalid. any button except
for page button is disabled.
22.
Remote control mode:
any button except
for page button is disabled if the input is
valid, LCD will display remote mode.
remote control module can start/stop and
monitor parameters through front face
buttons.
23.– 40. Reserved.
6
AUX.INPUT 1
valid
0- Normal close
1-
Normal open
The status of switch value input valid.
8
AUX.INPUT 2
valid
0- Normal close
1-
Normal open
10
AUX.INPUT 3
valid
0- Normal close
1-
Normal open
12
AUX.INPUT 4
valid
0- Normal close
1-
Normal open
14
AUX.INPUT 5
valid
0- Normal close
1-
Normal open
7)Working plan and maintenance setting
No Parameter
Range
(defaults)
Notes
1 Working plan format
Disable
Every month
Every week
This mode must be under auto mode.
Working plan is disabled once setting as
disable.