HM500 DISPLAY PANEL OF GENERATOR CONTROLLER USER MANUAL
24
19
Action if fuel
Level
sensor
disconnected
Disable
Warning
Alarm and stop
Action if Fuel level sensor disconnected.
20 Pressure/Tempe
rature unit
℃
/KPA
℃
/BAR
℃
/PSI
℉
/KPA
℉
/BAR
℉
/PSI
Unit display.
2)Basic Setting 2
No Parameter
Range
(defaults)
Notes
1 Primary Modes
STOP
Manual
Auto
Auto save
The primary modes on power, easy for
user operation.
Note: auto record function can’t record
the mode with load.
2 Manual crank times
1-30
(1 time)
Crank times under mode and test mode.
3 Auto start crank times 1-30
(3 times)
Crank times under auto mode.
4 E.T.S. hold times
1-10
(2 times)
The max E.T.S. hold on power shall be
canceled once stop success under auto
mode. the output interval time is " Fail to
stop ".
5 Crank disconnect
RPM
Hz
Oil pressure(delay)
D+
RPM/Frequency
RPM/Oil Pressure
RPM/ D+
Frequency/Oil
Pressure
Frequency / D+
Oil pressure/ D+
RPM/Frequency/Oil
press.
Frequency/oil
Press/D+
Oil pressure/D+/RPM
D+/Frequency/RPM
RPM/Freq./Oil
Press/D+
1.If there is no oil pressure sensor,
please don’t choose the type.
2.If there is no oil pressure sensor (only
with low oil pressure switch), RPM,
voltage, the user can choose Charge D+
as the crank condition, please choose
oil pr Charge D+ as conditions
in order to keep the engine running
safely.
Oil pressure switch input is not the crank
condition
Please check if the running status, stop
condition are according with crank
condition.
Means either of the conditions can be
acceptable as crank condition. But all of
them should be meet together to regard
as stop condition.
6 Frequency disconnect 0-200%
(28%)
Rated frequency multiplying by this
value is regarded as crank success
condition. When the gens frequency is
over the condition value, then system
regards it as crank success.
7 Oil pressure disconnect 0-400kpa
(200kpa)
When the engine oil pressure is over
the condition value, then system regards