HM500 DISPLAY PANEL OF GENERATOR CONTROLLER USER MANUAL
22
4
Rated frequency
40.0-80.0Hz
(50.0Hz)
Setting generator rated frequency to
choose the meter range and calculate the
alarm value.
5
Rated
phase
voltage
80-360V
(230V)
Setting generator phase voltage to choose
the meter range and calculate the alarm
value.
6
Rated
phase
current
5-6000A
(500A)
Setting generator phase current to choose
the meter range and calculate the alarm
value.
7
Rated total
power
5-2000Kw
(
276Kw
)
Set total power of generator to choose the
meter range and calculate the average
loading rate and alarm value.
8 Rated battery
voltage
8.0-36.0V
(24.0V)
Choose the meter range and calculate the
alarm value.
9 Rated RPM
500-4500RPM
(1500)
Choose the meter range and calculate the
alarm value.
10 Flywheel teeth 0-300
(0)
If the setting is 0, (RPM sensor Disabled),
then RPM is resulted by Hz.
11 Oil pressure
sensor
0: Disable
1: User defined-Resistance
2: User defined-Voltage
3: Volt In 1MPa-0-5V
4: Volt In 1MPa-0.5-4.5V
5: VDO 0-10Bar
6: MEBAY-003B
7: SGH
8: SGD
9: SGX
10: CURTIS
11:DATCON 10Bar
12: VOLVO-EC
13: 3015237
14: WEICHAI 0-0.6MPa
15:
GENCON 0-10Bar
Choose the usual oil pressure sensor, if
the sensor users choose is not the 9
types, it can be User-defined.
12 Temperature
sensor
0: Disable
1: User-defined
2: VDO 40-120
℃
3: MEBAY-001B
4: SGH
5: SGD
6: SGX
7: CURTIS
8: DATCON
9: VOLVO-EC
10: 3015238
11:PT100
12: MEBAY-Mier
13: WEICHAI 40-120
℃
14:
GENCON 40-120
℃
Choose the usual temperature sensor, if
the sensor users choose is not the 11
types, it can be User-defined.
13 Fuel level
0: Disable
If the sensor users choose is not the 3