HM500 DISPLAY PANEL OF GENERATOR CONTROLLER USER MANUAL
20
"Louver status input"
switch is enabled, the Louver status input alarm is reported.
"
ALARM
" lights will light up, Generator stops running, displays "
Louver abnormal
"
on the current fault screen.
Emergency stop alarm
When the controller detects that the input voltage of PIN 3 is less than 2V, then start
alarm delay and the duration (Emergency delay) have not returned to normal, the
alarm of Emergency Stop is reported. "
ALARM
" lights will light up, Generator stops
running, and displays "
Emergency stop
" on the current fault screen.
Stop failure with speed alarm
When the controller detects that the speed is not "0" after the execution of the
shutdown, the alarm of stop failure is reported. "
ALARM
" lights will light up and
displays "
Stop fail-RPM
" on the current fault screen.
Stop failure with frequency alarm
When the controller detects that the frequency is not "0" after the execution of the
shutdown, the alarm of stop failure is reported. "
ALARM
" lights will light up and
displays "
Stop fail-Hz
" on the current fault screen.
Stop failure with pressure alarm
When the controller detects that the Oil
Pressure
is not "0" after the execution of the
shutdown, the alarm of stop failure is reported. "
ALARM
" lights will light up and
displays "
Stop fail-OP-A
" on the current fault screen.
Stop failure with oil pressure switch
When the controller detects that the oil pressure switch has not returned after the
stop, it will alarm, the public alarm light
“ALARM”
lights will light up, and the current
fault screen displays
“Alarm: Stop fail-OP-D”.
10. Parameters setting
Enter the edition page
Please set the parameters according to below steps:
1)In the stop mode, Press and hold the
button for more than 3 seconds, or the
button, press the
button, and then release the
button to enter the
setting menu interface;
2)Select the detailed parameter settings of the controller and press the
key to
enter the password interface;
3)The default factory password of the controller is "07623";
4)Press
and add number 1, press
to reduce number 1, press
to turn
the digit into right, press to turn the digit into left, press
once done. Then
system comes into menu after confirmation of password setting. The screen will