5

Pin No. Function Description

9

5

+S

DC OK

Positive sensing for remote sense.

“DC OK” signal is a TTL level, referenced to pin 1&2 (GND).
Output modules turn on=4.5~5.5V, turn off=0~0.5V. The maximum sourcing current is 10mA (4.5~5.5V).

8

PV

Connection for output voltage programming, referenced to pin 1&2 (GND)

6

3

10

CS

RC2

-S

Current sharing signal. When units are connected in parallel , the CS pins of the units should be connected to allow for current balance 
between units. Referenced to pin 1&2 (GND)

Negative sensing for remote sense.

Turns the output on and off by electrical or dry contact between pin 3(RC2) and pin 1&2(GND).
Open: Power ON; Short: Power OFF.

2

4

1

GND

Vcc 2

GND

Ground.

Auxiliary voltage output, 4.5~5.5V, referenced to pin 1&2 (GND).The maximum load current is 10mA.

Ground.

7

PC

Connection for output current programming, referenced to pin 1&2 (GND)

Function Description of CN81

4.

Product Specifications

4.1  Front-End Specification

NMP650 (4 Slots)

NMP1K2 (6 Slots)

MODEL

VOLTAGE RANGE         

Note.6

FREQUENCY RANGE

POWER FACTOR

EFFICIENCY(Typ.)        

Note.4

AC CURRENT

INPUT

INRUSH CURRENT

LEAKAGE CURRENT

90 ~ 264VAC          120 ~370VDC

47 ~ 63Hz

PF>0.95/230VAC          PF>0.98/115VAC at full load

6.7A/230VAC          13.5A/115VAC

40A/230VAC          25A/115VAC

3.5A/230VAC          7.5A/115VAC

88.5%, full case load with each type of module at nominal voltage

91%, full case load with H / K module at nominal 24V / 48V only

40A/230VAC          25A/115VAC

Earth leakage current <400uA / 264VAC, Touch current <100uA/264VAC

1200W max.

5V @ 2A; tolerance 

±

10%; ripple: 50mVp-p(max.)

REMOTE CONTROL

ALARM SIGNAL

AUXILIARY POWER(AUX)

SAFETY STANDARDS

WORKING TEMP.

WORKING HUMIDITY

STORAGE TEMP., HUMIDITY

TEMP. COEFFICIENT

VIBRATION

FUNCTION

-30 ~ +70

 (Derate at 50

, refer to "Derating Curve")

20 ~ 90% RH non-condensing

RC+/RC-: Short, Power ON          RC+/RC-: Open, Power OFF

TTL signal output for over temperature alarm. Please refer to the Function Manual.

5V @ 1.5A ; tolerance 

±

10%; ripple: 50mVp-p (max.)

-40 ~ +85

, 10 ~ 95% RH non-condensing

±

0.03%/

 (0 ~ 50

)

10~500Hz, 2G 10min./1 cycle, 60 min. each along X, Y, Z axes.

ANSI/AAMI ES60601-1, Ed. 3.1,UL62368-1; TUV EN60601-1, Ed. 3.1, TUV EN62368-1; IEC 60601-1, Ed. 3.1, IEC 62368-1, 
IEC60950-1; EAC TP TC 004 approved

ISOLATION LEVEL

WITHSTAND VOLTAGE

Primary-Secondary: 2x MOPP, Primary-Earth: 1x MOPP

I/P-O/P: 4KVAC     I/P-FG: 2KVAC     O/P-FG: 0.5KVAC

ENVIRONMENT

SAFETY &

OUTPUT

650W max.

Shut down o/p voltage, recovers automatically after temperature goes down

TOTAL OUTPUT POWER

PROTECTION OVER TEMPERATURE

ISOLATION RESISTANCE

I/P-O/P, I/P-FG, O/P-FG: 100M Ohms / 500VDC / 25

/ 70% RH

EMC

(Note 5)

OTHERS

DIMENSION

PACKING

250*89*41mm (L*W*H)

250*127*41mm (L*W*H)

1.45Kg  (typ.); 9pcs / 14Kg / 0.98CUFT

2Kg (typ.); 6pcs / 13Kg / 0.88CUFT

Parameter

Parameter

ESD 

RF field

EFT/ Burst

Surge

Conducted

Magnetic Field

Voltage Dips and Interruptions

Conducted

Radiated

Harmonic Current 

Voltage Flicker

Standard

Standard

EN55032 (CISPR32) / EN55011 (CISPR11)

EN55032 (CISPR32) / EN55011 (CISPR11)

EN61000-3-2

EN61000-3-3

EN61000-4-2

EN61000-4-3

EN61000-4-4

EN61000-4-5

EN61000-4-6

EN61000-4-8

EN61000-4-11

Test Level / Note

Test Level / Note

Class B

Class B

Class A

-----

EMC IMMUNITY

EMC EMISSION

EN60601-1-2, EN55024

Level 4, 15KV air; Level 4, 8KV contact

Level 3, 10V/m  

Level 3, 2KV

Level 4, 4KV/Line-FG; 2KV/Line-Line

Level 2, 3V

Level 4, 30A/m

100% dip 1 periods, 30% dip 25 periods, 
100% interruptions 250 periods

90.5%, full case load with H / K module at nominal 24V / 48V only

Содержание NMP1K2

Страница 1: ...NMP650 1K2 Instruction Manual...

Страница 2: ...ns 5 1 Input Voltage 5 2 Inrush Current Limiting 6 1 Assembly Procedures 7 1 Front End Mounting 7 2 Output Wiring Guidelines 7 3 De rating 7 4 Warranty 5 3 Output Voltage Current Adjustment 5 4 Short...

Страница 3: ...tive current sharing and parallel control capabilities Output voltage programmable PV Constant current level programmable PC Global or Local ON OFF control Remote sense for output module DC OK signal...

Страница 4: ...ption code 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 Code 00 31 for NMP1K2 Code 00 01 02 03 06 07 10 16 for NMP650 NMP1K2 Code 01 00 02 03 04 05 06 07 08 09 10 11 12 13 14 15 SLOT 1 SLOT 2 SLOT...

Страница 5: ...2 2 2 1 1 1 1 2 SLOT1 2 3 4 5V 36A 12V 20A 24V 10A 24V 10A SLOT1 SLOT2 SLOT3 SLOT4 V V CN81 48V 5A SLOT5 48V 5A SLOT6 5 6 2 3 4 5V 36A 12V 20A 24V 10A 48V 5A SLOT1 V V CN81 SLOT1 SLOT2 SLOT3 SLOT4 Mod...

Страница 6: ...High 4 5 5 5V When the internal temperature exceeds the limit safe limit of temperature alarm Low 0 0 5V When the internal temperature is normal 3 4 GND P Ground 6 RC1 Turns the output on and off by...

Страница 7: ...ANDARDS WORKING TEMP WORKING HUMIDITY STORAGE TEMP HUMIDITY TEMP COEFFICIENT VIBRATION FUNCTION 30 70 Derate at 50 refer to Derating Curve 20 90 RH non condensing RC RC Short Power ON RC RC Open Power...

Страница 8: ...ower on to recover Protection type constant current limiting protection 6 1 8V 15 1 20V 6 15V 30 1 37V 15 30V 56 66V 30 55V REMOTE ON OFF CONTROL REMOTE SENSE OUTPUT VOLTAGE PROGRAMMABLE PV OUTPUT CUR...

Страница 9: ...of the units Since the inrush limiting circuit mainly consists of thermistors and a relay inrush current will be much higher than the specified value if input thermistor is not allowed sufficient tim...

Страница 10: ...mperature continues to increase and exceeds the safe limit value then the output will shut down automatically Please switch off the AC input remove all possible causes and then leave the unit to cool...

Страница 11: ...e Remote Sense When using this function the sensing wires should either be twisted or shielded to prevent external noise interference refer to Figure 5 6 Built in remote sense circuit that is able to...

Страница 12: ...LED V V V V V V V V V V V V CN81 CN81 CN81 CN81 CN81 CN81 NMS 240 NMS 240 NMS 240 NMS 240 NMS 240 NMS 240 CS PIN6 GND PIN1 or 2 GND GND GND GND GND GND 9 9 9 9 9 9 10 10 10 10 10 10 GND GND GND GND GN...

Страница 13: ...All 6 pins must be inserted into the correct sockets Grab the circled location and lift module The power supply unit may remain hot after power off please leave the unit to cool for at least 5 minutes...

Страница 14: ...e all modules are slotted into the notches circled in red securing the top cover ensure all modules are held secure by the notches and screws Please set the electric screw driver s torque setting to 6...

Страница 15: ...ll decrease the voltage Once the output voltages of all modules have been tested and adjusted to the desired values the output configuration is done 10 Higher output voltage can be acquired by connect...

Страница 16: ...ay be connected in parallel Before making the parallel connection adjust the voltage of each modules individually to the desired voltage and ensure the difference in voltages is less than 0 2V The com...

Страница 17: ...ot 1 and slot 2 is less than 0 2V Use two 2 unit parallel copper plates accessory FAP 009 to connect the V and V terminals of slot 1 and slot 2 and use accessory and GND pins of CN81 in parallel d App...

Страница 18: ...o the product otherwise the warranty shall be void When the ambient temperature is high or input AC voltage is low the power supply needs to be de rated according to curves shown below Derating Curve...

Страница 19: ...HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS...

Страница 20: ...le Green Blue Brown PIN NO Blank Plate Accessory BLANK NMS240 A1 3 V Series Connection Accessory A1 4 Front End Accessory Series Connection Accessory FAS 005 For 1 slot modules NMS 240 200mm NMP CN32...

Страница 21: ...No 28 Wuquan 3rd Rd Wugu Dist New Taipei City 248 Taiwan...

Отзывы: