5.7  Fan-lock Protection

Figure 5

-

3

 

 There is a built-in fan-lock protection circuit. The output of all modules will shut off when the DC fan stops operating (fan-lock, loose 

 connector, or broken wires). Please turn off the AC power and remove the conditions causing fan-lock. If there are no observable 

 causes for fan-lock, please remove the unit from your system and send back to our local distributor or MEAN WELL for repair.

5.8

 

 Remote Control

 There are built-in remote ON/OFF controls for Front-End and individual output modules.

 Connection diagram and control logics are shown below.

 Figure 5-4 shows RC1 (CN32 PIN6) and GND-P (CN32 PIN3) connection diagram.

5.6  Over Temperature Protection (OTP) and T-Alarm

 The Front-End has built-in thermal detection circuit. Once the internal temperature exceeds a preset value, there will be a “HIGH” 

 When the internal temperature is within a normal value, the T-Alarm signal will be a “LOW” signal (-0.1~0.5V).

.

 T-Alarm's maximum sourcing current is 10mA

 Figure 5-3 shows T-Alarm (CN32 PIN5) and GND-PC (CN32 PIN3 or 4) connection diagram.

 signal (4.5~5.5V) sent out through T-ALARM for end system to respond. If the internal temperature continues to increase and exceeds 

 the “safe limit” value, then the output will shut down automatically. Please switch off the AC input, remove all possible causes, and 

 then leave the unit to cool down to a normal working temperature (approximately 10 minutes ~ 1 hour) before re-power on.

T-Alarm Signal Voltage

Internal Temperature (U702)

4.5~5.5V
4.5~5.5V

0~0.5V

Exceeds the limit of T-Alarm

Exceeds the "safe limit"

The internal temperature is normal

Output Status

OFF

ON
ON

NMP1K2

1

T-Alarm

( PIN5)

GND-P

( PIN3 or 4)

5

2

6

CN32

CN32

6

6

5

5

2

2

1

1

TB1

TB1

N

N

L

L

+5V

-AUX-P

+5V

-AUX-P

RC1

GND-P

T-Alarm

GND-P

CN32

NMP650

NMP1K2

NMP650

1

GND-P

(PIN3)

CN32

RC1

(PIN6)

5

2

6

5.8.1

 ON / OFF

 

Global

Connection Status

Output Status

Open

 (SW OFF)

Short

 (SW ON)

OFF

ON

CN32

CN32

6

6

5

5

2

2

1

1

TB1

TB1

N

N

L

L

+5V

-AUX-P

GND-P

+5V

-AUX-P

GND-P

RC1

T-Alarm

SW

Figure 5

-

4

Figure 5

-

5

Connection Status

Output Module Status

Short (SW ON)

Open (SW OFF)

OFF

ON

5.8.2

 

 Local ON/OFF

The NMS-240 modules can be turned ON/OFF individually by using the “local ON/OFF” function.

Figure 5-5 shows RC2 (CN81 PIN3) and GND (CN81 PIN1 or 2) connection diagram.

 The CN32 connection accessory (included in packaging) must be connected when using the local ON/OFF function.

NMS-240

GND

( PIN1 or 2)

RC2

( PIN3)

GND

1

GND

2

RC2

VCC2

CS

DC_OK

PC

CN81

PV

+S

-S

9

10

SW

+V

-V

-

+

LOAD

CN81

4 6 810

9

7

5

3

2

1

VR60

LED

Содержание NMP1K2

Страница 1: ...NMP650 1K2 Instruction Manual...

Страница 2: ...ns 5 1 Input Voltage 5 2 Inrush Current Limiting 6 1 Assembly Procedures 7 1 Front End Mounting 7 2 Output Wiring Guidelines 7 3 De rating 7 4 Warranty 5 3 Output Voltage Current Adjustment 5 4 Short...

Страница 3: ...tive current sharing and parallel control capabilities Output voltage programmable PV Constant current level programmable PC Global or Local ON OFF control Remote sense for output module DC OK signal...

Страница 4: ...ption code 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 Code 00 31 for NMP1K2 Code 00 01 02 03 06 07 10 16 for NMP650 NMP1K2 Code 01 00 02 03 04 05 06 07 08 09 10 11 12 13 14 15 SLOT 1 SLOT 2 SLOT...

Страница 5: ...2 2 2 1 1 1 1 2 SLOT1 2 3 4 5V 36A 12V 20A 24V 10A 24V 10A SLOT1 SLOT2 SLOT3 SLOT4 V V CN81 48V 5A SLOT5 48V 5A SLOT6 5 6 2 3 4 5V 36A 12V 20A 24V 10A 48V 5A SLOT1 V V CN81 SLOT1 SLOT2 SLOT3 SLOT4 Mod...

Страница 6: ...High 4 5 5 5V When the internal temperature exceeds the limit safe limit of temperature alarm Low 0 0 5V When the internal temperature is normal 3 4 GND P Ground 6 RC1 Turns the output on and off by...

Страница 7: ...ANDARDS WORKING TEMP WORKING HUMIDITY STORAGE TEMP HUMIDITY TEMP COEFFICIENT VIBRATION FUNCTION 30 70 Derate at 50 refer to Derating Curve 20 90 RH non condensing RC RC Short Power ON RC RC Open Power...

Страница 8: ...ower on to recover Protection type constant current limiting protection 6 1 8V 15 1 20V 6 15V 30 1 37V 15 30V 56 66V 30 55V REMOTE ON OFF CONTROL REMOTE SENSE OUTPUT VOLTAGE PROGRAMMABLE PV OUTPUT CUR...

Страница 9: ...of the units Since the inrush limiting circuit mainly consists of thermistors and a relay inrush current will be much higher than the specified value if input thermistor is not allowed sufficient tim...

Страница 10: ...mperature continues to increase and exceeds the safe limit value then the output will shut down automatically Please switch off the AC input remove all possible causes and then leave the unit to cool...

Страница 11: ...e Remote Sense When using this function the sensing wires should either be twisted or shielded to prevent external noise interference refer to Figure 5 6 Built in remote sense circuit that is able to...

Страница 12: ...LED V V V V V V V V V V V V CN81 CN81 CN81 CN81 CN81 CN81 NMS 240 NMS 240 NMS 240 NMS 240 NMS 240 NMS 240 CS PIN6 GND PIN1 or 2 GND GND GND GND GND GND 9 9 9 9 9 9 10 10 10 10 10 10 GND GND GND GND GN...

Страница 13: ...All 6 pins must be inserted into the correct sockets Grab the circled location and lift module The power supply unit may remain hot after power off please leave the unit to cool for at least 5 minutes...

Страница 14: ...e all modules are slotted into the notches circled in red securing the top cover ensure all modules are held secure by the notches and screws Please set the electric screw driver s torque setting to 6...

Страница 15: ...ll decrease the voltage Once the output voltages of all modules have been tested and adjusted to the desired values the output configuration is done 10 Higher output voltage can be acquired by connect...

Страница 16: ...ay be connected in parallel Before making the parallel connection adjust the voltage of each modules individually to the desired voltage and ensure the difference in voltages is less than 0 2V The com...

Страница 17: ...ot 1 and slot 2 is less than 0 2V Use two 2 unit parallel copper plates accessory FAP 009 to connect the V and V terminals of slot 1 and slot 2 and use accessory and GND pins of CN81 in parallel d App...

Страница 18: ...o the product otherwise the warranty shall be void When the ambient temperature is high or input AC voltage is low the power supply needs to be de rated according to curves shown below Derating Curve...

Страница 19: ...HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS DF11 10DS HRS...

Страница 20: ...le Green Blue Brown PIN NO Blank Plate Accessory BLANK NMS240 A1 3 V Series Connection Accessory A1 4 Front End Accessory Series Connection Accessory FAS 005 For 1 slot modules NMS 240 200mm NMP CN32...

Страница 21: ...No 28 Wuquan 3rd Rd Wugu Dist New Taipei City 248 Taiwan...

Отзывы: