![MDV M0BA30-11CFN1-MQ0W Скачать руководство пользователя страница 70](http://html1.mh-extra.com/html/mdv/m0ba30-11cfn1-mq0w/m0ba30-11cfn1-mq0w_technical-manual_1757523070.webp)
Installation
Page 70
water might penetrated into pipeline.
3. Construction period is long, and rain water might
penetrated into pipeline.
4. Rain water might penetrate into pipeline during
construction.
Procedures of special vacuum drying are as follows:
1. Vacuum drying for 1 hour.
2. Vacuum damage, filling nitrogen to reach 0.5Kgf/cm2 .
Because nitrogen is dry gas, vacuum damage could
achieve the effect of vacuum drying, but this method
could not achieve drying thoroughly when there is too
much moisture. Therefore, special attention shall be drawn
to prevent the entering of water and the formation of
condensate water.
3. Vacuum drying again for half an hour.
If the pressure reached -755mmHg, start to pressure
leakage test. If it cannot reached the value, repeat vacuum
damage and vacuum drying again for 1 hour.
4. Leakage test: After the vacuum degree reaches
-755mmHg, stop vacuum drying and keep the pressure for
1 hour. If the indicator of vacuum gauge does not go up,
it is qualified. If going up, it indicates that there is moisture
or leak source.
7. Additional Refrigerant Charge
•
After the vacuum drying process is carried out, the
additional refrigerant charge process need to be
performed.
•
The outdoor unit is factory charged with refrigerant.
The additional refrigerant charge volume is decided
by the diameter and length of the liquid pipe be-
tween indoor and outdoor unit. Refer the following
formula to calculate the charge volume.
Diameter of liquid pipe (mm)
Formula
6.35
V=15g/m×(L-5)
9.52
V=30g/m×(L-5)
V:
Additional refrigerant charge volume (g).
L :
The length of the liquid pipe (m).
Note:
•
Refrigerant may only be charged after performed
the vacuum drying process.
•
Always use gloves and glasses to protect your hands
and eyes during the charge work.
•
Use electronic scale or fluid infusion apparatus to
weight refrigerant to be recharged. Be sure to avoid
extra refrigerant charged, it may cause liquid ham-
mer of the compressor or protections.
•
Use supplementing flexible pipe to connect refriger-
ant cylinder, pressure gauge and outdoor unit. And
The refrigerant should be charged in liquid state.
Before recharging, The air in the flexible pipe and
manifold gauge should be exhausted.
•
After finished refrigerant recharge process, check
whether there is refrigerant leakage at the connec-
tion joint part.(Using gas leakage detector or soap
water to detect).
Содержание M0BA30-11CFN1-MQ0W
Страница 1: ...TM_AB_R410A_INV_US_NA_2009 R410A INVERTER CONTROL TECHNICAL MANUAL...
Страница 14: ...Specifications Page 14 MSABB 11CRFN1 BT0W MSABB 11CRFN1 MT0W MSABD 17CRFN1 MQ0W...
Страница 15: ...Specifications Page 15 MSABE 22CRDN1 MS0W...
Страница 17: ...Specifications Page 17 MOBA30 12CFN1 BP0W MOX130 11CFN1 MT0W...
Страница 18: ...Specifications Page 18 MOX130 11CFN1 BT0W MOBA30 09CFN1 MQ0W M0BA30 11CFN1 MQ0W...
Страница 19: ...Specifications Page 19 MOBA30 17CFN1 MR0W MOCA30 22CFN1 MR0W...
Страница 43: ...Specifications Page 43 MSABB 12CRDN1 BP0W MSABB 11CRFN1 BT MSABA 09CRDN1 MP0W MSABB 12CRDN1 MP0W...
Страница 44: ...Specifications Page 44 MSABB 11CRFN1 MT0W MSABD 17CRFN1 MQ0W MSABE 22CRDN1 MS0W 7 2 Outdoor Unit...
Страница 46: ...Specifications Page 46 MOBA30 12CFN1 BP0W MOX130 11CFN1 BT0W MOBA30 09CFN1 MQ0W M0BA30 11CFN1 MQ0W...
Страница 47: ...Specifications Page 47 MOX130 11CFN1 MT0W MOBA30 17CFN1 MR0W MOCA30 22CFN1 MR0W...