6.4.3 PI control switching (PWM)
The following settings are available at the ETS-Software (here for controller type heating):
Figure 23: PI control switching (PWM)
The PI control switching is a development of the PI control continuous. All settings of the continuous
control are also available at the PI control switching. Additional a PWM cycletime can be adjusted.
The following chart shows the dynamic range for this parameter:
ETS-text
Dynamic range
[default value]
comment
Direction of controller
normal
inverted
indicates the controlling behavior at
rising temperature (4.5.5)
Max value of control value
100%; 90%; 80%; 75%; 70%; 60%;
50%; 40%; 30%; 25%; 20%; 10%; 0%
[100%]
indicates the output power at maximum
amount
Heating system
Warm water heating (5K/150
min)
Underfloor heating (5K/240
min)
Split Unit (4K/90min)
Adjustment via control
parameter
Adjustment of the used heating system
Individual parameterization available by
Adjust e t ia o t ol pa a ete