Technical Manual Glass Room Temp. Contr. SCN-RT1Gx.01
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Tel.: +49-2263-
880 • Fax: +49
-2263-4588
• [email protected] • www.mdt.de
44
6.3.2.7 Operating mode after reset
The following figure shows the available settings for the operating mode after reset:
Figure 11: Settings operating mode after reset
The following table shows the available settings for the operating mode after reset:
ETS-text
Dynamic range
[default value]
comment
Operating mode after reset
Comfort with
parameterized setpoint
Standby with
parameterized setpoint
Hold old state and setpoint
Adjustment, which operating mode shall
be switched on after a bus power return
Table 33: Operating mode after reset
This parameter defines the operating mode, which shall be adjusted after a bus power return:
Comfort with parameterized setpoint
After a bus power return, comfort is activated with the setpoint, which was set by the ETS.
Standby with parameterized setpoint
After a bus power return, standby is activated with the setpoint, which was set by the ETS
(Comfort-Setpoint
–
Standby reduction).
Hold old state and setpoint
The temperature controller calls the setpoint and mode, which was set before bus power
down.