24
SWD
S = Default, L = Loco address, S = Switch address, LS = Loco and switch address usable
CV
Description
S
L/S
Range
Note
49
MD configuration
0*
LS
bitwise programming
Bit
Value
OFF (Value 0)
ON
0
1
SW1 no defined position
SW1 defined position
1
2
SW1
def. position „straight“
SW1 def. position
„turned“
2
4
SW1 normal output
SW1 inverted output
3
8
SW1 don‘
t hold endposition
SW1 hold endposition
4
16
A1 normal output
A1 inverted output
5
32
A1 with switch address
A1 with loco address
6
64
A1 normal function
A1 flashes while switching
7
128
A1 normal function
A1 flashes with defined pos.
117
A1 for heart polarisation
0
W
0/1
0 = normal output
1 = heart polarization with relay
(Ab Version 1.1)
118
Switch position right
120
S
0
–
255
Change only, if switch cannot turn correctly!
119
Switch position left
0
S
0
–
255
120
SW1 address high
0
S
1
–
2048
121
SW1 address low
1
S
122
SW1 speed value
10
S
0
–
255
Speed value 1 ms each value
123 SW1 time for automatic switch
back function
0
S
0
–
255
0 = off
1
–
255 = time base 0,25 sec. each value
124
SW1 staytime
hold time after reach end
position
0
S
0
–
255
0 = off
1
–
255 = time base 0,1 sec. each value
important, when drives peed is small
125
A1 command allocation
7
L
see attachment 1, active if CV 49 Bit 5 = 1
126
A1 dimming value
100
LS
1
–
100
dimming value in % (1 % ca. 0,2 V)
127
A1 address high
0
S
1
–
2048
active if CV 49 Bit 5 = 0
128
A1 address low
2
S
129
A1 time for special function
2
LS
1
–
255
time base (0,1s / value)
*SWD PLUG please set CV49 Bit 2 = 1 (inverted on)
ATTACHMENT 1
–
Command allocation
Value
Application
Note
0
–
28
0 = Switch with light key
1
–
28 = Switch with F-key
+64
permanent off
+128
permanent on