McQuay T170 Скачать руководство пользователя страница 9

McQuay IM 846

9

Optional Occupancy Detection Equipment Operation

Optional Occupancy Detection Equipment Operation

The T170 thermostat can be used with optional S200 series 
occupancy detection equipment. Purchasing and installing this 
equipment to compliment the thermostat adds energy savings 
by setting back HVAC operation during occupied and 
unoccupied times. Optional detection equipment 
configurations and operation are described below.

SB200-001 Occupancy Sensor

The SB200-001 occupancy sensor (Figure 10) serves as an 
occupancy sensor for automatic control of a guest room HVAC 
system. It incorporates an innovative dual delay processor 
which allows the sensor to verify the nature of occupancies, 
and is capable of eliminating unnecessary actuations of the 
HVAC device due to unintentional passages or short time 
occupancies. The sensor may also serve as a slave sensor 
(Figure 11 on page 10). 

The sensor switch is open in occupied mode and closed in 
unoccupied mode. An optional door and/or window switch 
(Figure 10) is open when the door/window is open and is 
closed when the door/window is closed.

Note –

To use this configuration, a jumper must be installed to 

JP3 to allow occupancy input. 

Note –

An optional door and/or window switch (Figure 10) can be 

added for use with the SB200-001 sensor.

Operation

In an occupied mode, the thermostat operates normally and 
looks for a door open signal. When the door opens, the 
thermostat waits for a door close signal. If the door is open for 
more than two minutes, the thermostat turns the HVAC system 
outputs to OFF. During this two minute period, if any button is 
pressed on the keypad, the time delay is extended to ten 
minutes. The time delay can only be extended once. Once the 
HVAC outputs transition to OFF, a door closure is required to 
re-enable the outputs. When the door closes, the thermostat 
starts a two minute timer and tries to detect occupancy. If the 
timer expires and no occupancy is detected, the thermostat 
transitions to an unoccupied state. If occupancy is detected 
while the timer is running, the thermostat will remain in the 
occupied mode.

In an unoccupied mode, the thermostat sets heating and 
cooling set points to setback values as determined by factory 
or user settings. The fan is automatically set to cycle with 
demand. The thermostat continually monitors the occupancy 
sensor and will enter into occupied mode if occupancy is 
detected.

If the installation is only using a door/window switch, the 
thermostat will disable the HVAC outputs if this output is open 
for longer than two minutes. 

To enable door/window switch only operation, install a jumper 
to JP3 (see “Mounting and Wiring the Thermostat” on page 3) 
and the occupancy input must be shorted to circuit common.

Figure 10: Optional equipment configuration #1

Содержание T170

Страница 1: ...llation and Maintenance Manual IM 846 Group Fan Coil Part Number IM 846 Date July 2006 T170 Thermostat 24 VAC 120 277 VAC 3 Speed Fan Control Continuous or Cycling or Staged Fan Control 2006 McQuay In...

Страница 2: ...TB170 001 5 Verifying Thermostat Operation 5 Thermostat Menu Functions 6 Menu Function Access 6 Menu Functions 6 Condensate Overflow Interrupt 6 Fan Operation 7 Standard Fan Configuration TA170 001 7...

Страница 3: ...y from its base to gain access to the circuit board Figure 2 Figure 2 Circuit board WARNING BEFORE ATTEMPTING TO INSTALL OPERATE OR SERVICE THIS THERMOSTAT CAREFULLY READ THESE INSTRUCTIONS Failure to...

Страница 4: ...d into the cover and is not dislodged 10 Install the cover assembly to the base pressing firmly to engage the cover locking snaps CAUTION Before applying power the voltage selection switch must be in...

Страница 5: ...on Figure 4 to control operation of the fan In the ON position the fan output operates continuously In the AUTO position the output cycles with demand In the OFF position all outputs are off Note Mode...

Страница 6: ...ase the value press the up or down arrow button 6 Set back heat When this function is selected the current temperature range adjustment the SET BACK icon and the HEAT icon appear To increase or decrea...

Страница 7: ...tion may be provided for minimum heating and cooling requirements Using this configuration the HEAT and COOL outputs are automatically cycled on at the heat setback limit Your thermostat may not have...

Страница 8: ...urge cycle operation is as follows 1 The thermostat has a call for heat or cooling Note If at any time the call goes away the thermostat stops the purge cycle 2 The thermostat checks the pipe sensor t...

Страница 9: ...1 sensor Operation In an occupied mode the thermostat operates normally and looks for a door open signal When the door opens the thermostat waits for a door close signal If the door is open for more t...

Страница 10: ...d to allow setback input Note An optional door and or window switch Figure 11 and slave sensor can be added for use with the SD200 001 sensor Operation In an occupied mode the SD200 001 occupancy sens...

Страница 11: ...cupancy status as well as selectable high low temperature setback form C output and a five minute door open HVAC shut off This system provides basic room setback and is ideal for control of HVAC in co...

Страница 12: ...training or call 540 248 9646 and ask for the Training Department Warranty All McQuay equipment is sold pursuant to its standard terms and conditions of sale including Limited Product Warranty Consul...

Отзывы: