McQuay T170 Скачать руководство пользователя страница 8

8

McQuay IM 846

Operation

Fancoil Operation

Fancoil operation is either a 2-pipe or 4-pipe configuration 
which is determined by jumper selection JP4 (see “Mounting 
and Wiring the Thermostat” on page 3).

2-Pipe Operation

In this configuration, the thermostat permanently disables the 
secondary output and disables the fan from cycling in an 
invalid mode. The main output configuration is dependent on 
the pipe sensor input. With a pipe sensor connected, the 
thermostat automatically selects heating or cooling depending 
on the sensed water temperature. If the pipe sensor input is 
open (unconnected), the main output only cools. If the pipe 
sensor input is shorted, the main output only heats. Normal 
thermostat default is for 4-pipe operation. For 2-pipe 
operation, install a jumper on JP4.

4-Pipe Operation

In this configuration, both the main output (COOL) and the 
secondary output (HEAT) are available. These both cycle ON 
depending on the mode of the thermostat. With a pipe sensor 
connected, the thermostat automatically changes the main 
output to heat and disables the secondary output if the main 
coil water is hot. For 4-pipe operation, the JP4 jumper is 
removed.

Pipe Sensor Operation 

A pipe sensor can be connected when the thermostat is 
configured for either 2-pipe or 4-pipe configuration. The pipe 
sensor is used to determine the water temperature in the main 
coil, which should be connected to the primary output.

Pipe sensor input—use a 10K Remote Probe or a standard ON-
Off Aquastat for summer/winter changeover.

Purge Cycle

With a pipe sensor connected, the thermostat initiates a purge 
cycle if the sensed water temperature is ambiguous (not 
adequately hot or cold). The sequence for purge cycle 
operation is as follows:

1

The thermostat has a call for heat or cooling.

Note: 

If at any time the call goes away, the thermostat 

stops the purge cycle.

2

The thermostat checks the pipe sensor to verify water 
temperature.

3

If the water temperature is beyond 15°F of the set point, 
normal HVAC control occurs.

4

If the water temperature is not beyond 15°F of the set point, 
the thermostat checks to see if the water temperature is 
above 80°F or below 60°F. 

If yes, normal HVAC control occurs. 

If no, the thermostat opens the main output (COOL) for 
three minutes.

5

After the three minute purge cycle occurs, the thermostat 
checks to see if the water temperature is more than 15°F 
from the set point, or above 80°F, or below 60°F.

If yes, normal HVAC operation occurs.

If no, the valve is left open and the thermostat continues to 
search for a valid reading.

Note –

If at any time the demand goes away, the thermostat will 

stop the purge cycle.

Table 4 shows output operation, depending on the sensed 
water temperature.

Setback Operation

In this configuration, the low level switch input normally is 
open. To enable setback operation, the JP3 jumper is removed 
(see “Mounting and Wiring the Thermostat” on page 3). The 
input will close and the thermostat heating and cooling setback 
limits can then be used as temperature control points. Fan 
operation in setback is cycled with demand. Press any 
thermostat key to override setback for one hour. Setback 
overrides any user setting except if the control is turned to 
OFF.

Table 4: Output operation

2-Pipe/4-Pipe 

selection

Water 

temperature

Output operation

Main output

Secondary 

output

2-pipe

JP4 ON

Cold

Cooling only

The fan does not cycle on 

with a heat demand.

Disabled

Hot

Heating only

The fan does not cycle on 

with a cool demand.

Disabled

4-pipe

JP4 OFF

Cold

Cooling

Heating

Hot

Heating only

The fan does not cycle on 

with a cool demand.

Disabled

Содержание T170

Страница 1: ...llation and Maintenance Manual IM 846 Group Fan Coil Part Number IM 846 Date July 2006 T170 Thermostat 24 VAC 120 277 VAC 3 Speed Fan Control Continuous or Cycling or Staged Fan Control 2006 McQuay In...

Страница 2: ...TB170 001 5 Verifying Thermostat Operation 5 Thermostat Menu Functions 6 Menu Function Access 6 Menu Functions 6 Condensate Overflow Interrupt 6 Fan Operation 7 Standard Fan Configuration TA170 001 7...

Страница 3: ...y from its base to gain access to the circuit board Figure 2 Figure 2 Circuit board WARNING BEFORE ATTEMPTING TO INSTALL OPERATE OR SERVICE THIS THERMOSTAT CAREFULLY READ THESE INSTRUCTIONS Failure to...

Страница 4: ...d into the cover and is not dislodged 10 Install the cover assembly to the base pressing firmly to engage the cover locking snaps CAUTION Before applying power the voltage selection switch must be in...

Страница 5: ...on Figure 4 to control operation of the fan In the ON position the fan output operates continuously In the AUTO position the output cycles with demand In the OFF position all outputs are off Note Mode...

Страница 6: ...ase the value press the up or down arrow button 6 Set back heat When this function is selected the current temperature range adjustment the SET BACK icon and the HEAT icon appear To increase or decrea...

Страница 7: ...tion may be provided for minimum heating and cooling requirements Using this configuration the HEAT and COOL outputs are automatically cycled on at the heat setback limit Your thermostat may not have...

Страница 8: ...urge cycle operation is as follows 1 The thermostat has a call for heat or cooling Note If at any time the call goes away the thermostat stops the purge cycle 2 The thermostat checks the pipe sensor t...

Страница 9: ...1 sensor Operation In an occupied mode the thermostat operates normally and looks for a door open signal When the door opens the thermostat waits for a door close signal If the door is open for more t...

Страница 10: ...d to allow setback input Note An optional door and or window switch Figure 11 and slave sensor can be added for use with the SD200 001 sensor Operation In an occupied mode the SD200 001 occupancy sens...

Страница 11: ...cupancy status as well as selectable high low temperature setback form C output and a five minute door open HVAC shut off This system provides basic room setback and is ideal for control of HVAC in co...

Страница 12: ...training or call 540 248 9646 and ask for the Training Department Warranty All McQuay equipment is sold pursuant to its standard terms and conditions of sale including Limited Product Warranty Consul...

Отзывы: