McQuay T170 Скачать руководство пользователя страница 4

4

McQuay IM 846

Installation Instructions

5

On the circuit board, set the voltage selection switch 
(Figure 2) to the appropriate voltage for the application

24 V = 24 VAC

110–277 V = 120, 240, or 277 VAC

.

Note: 

The circuit board is shipped with the voltage selection switch 

in the 110-227 V position. For 24 VAC use, the switch must 
be in the 24 V position.

6

The circuit board is also equipped with configuration 
jumpers (JP1, JP3, and JP4 in Figure 2). Depending on the 
application, it may be necessary to reconfigure the 
following jumpers:

• JP4:

 2/4 Pipe Sensor Jumper - This jumper selects 

between 2-pipe (jumper ON) and 4-pipe (jumper OFF) 
operation (see “Fan Operation” on page 7).

• JP3:

 Door/Window Switch Jumper - This jumper is 

shipped normally open. Placement of a jumper allows 
for occupancy detection and door/window switch only 
operation (see “Optional Occupancy Detection 
Equipment Operation” on page 9
).

• JP1:

 Removal of this jumper allows the sensor to be 

located in a remote location.

7

Connect the color coded thermostat wires (Figure 3) to the 
line voltage wires located in the mud ring/connection box 
and secure the connections with wire nuts.

Figure 3: Wiring diagram 

8

Install the thermostat base to the mud ring/outlet box using 
two furnished mounting screws. Tighten the screws evenly 
but do not over tighten. 

Note: 

An output ratings chart (Table 3) is located on the 

inside of the base.

Table 3: Output ratings

9

With the base now secured, verify that the circuit board is 
firmly snapped into the cover and is not dislodged. 

10

Install the cover assembly to the base, pressing firmly to 
engage the cover locking snaps.

CAUTION

Before applying power, the voltage selection switch must be in 
the appropriate position. Failure to select the correct voltage 
can cause thermostat malfunction or permanently damage the 
thermostat.

CAUTION

To use a remote sensor on units with local sensing capability, 
remove jumper JP1 to disable local sensing. Failure to remove 
JP1 can cause improper operation of the thermostat with a 
remote probe installed.

CAUTION

Use copper wire only. Insulate or wire nut all unused leads.
Avoid electrostatic discharge to the thermostat. 
Failure to do so can cause thermostat malfunction or 
permanently damage the thermostat.

Output ratings

Voltage

Inductive

Resistive 

amps

Pilot duty

HP

FLA

LRA

24 VAC

NA

NA

NA

24 VA

NA

120 VAC

5.8

34.8

6.0

125 VA

1/4

240 VAC

2.9

17.4

5.0

125 VA

1/4

277 VAC

2.4

14.4

4.2

125 VA

1/4

DANGER

Hazardous voltage. Combined load current is not to exceed 20 
amps. Mount only to a grounded metallic box.
Low voltage wiring is Class 2. To avoid electrical shock or 
damage to equipment, disconnect power before installing or 
servicing. Failure to follow these instructions will result in death 
or serious injury.

THERMOST

AT

CONNECTIONS

LOW

V

OL

T

A

GE

LINE

V

OL

T

A

GE

White/Black 

White/Yellow 

White/Violet 

White/Blue 

White/Gray 

White/Brown 

White/Red 

White/Orange 

 

Yellow 

Blue 

Red 

Black 

Brown 

Setback input/door switch 

Remote probe 

Circuit common 

Pipe sensor 

L2/Neutral 

Occupacy detector 

L1 

Outputs 

(see ratings) 

Accessories

available

from

McQuay

Cool 

(main output) 

Heat 

(secondary output) 

Fan low 

Fan medium 

Fan high 

Outside air 

Содержание T170

Страница 1: ...llation and Maintenance Manual IM 846 Group Fan Coil Part Number IM 846 Date July 2006 T170 Thermostat 24 VAC 120 277 VAC 3 Speed Fan Control Continuous or Cycling or Staged Fan Control 2006 McQuay In...

Страница 2: ...TB170 001 5 Verifying Thermostat Operation 5 Thermostat Menu Functions 6 Menu Function Access 6 Menu Functions 6 Condensate Overflow Interrupt 6 Fan Operation 7 Standard Fan Configuration TA170 001 7...

Страница 3: ...y from its base to gain access to the circuit board Figure 2 Figure 2 Circuit board WARNING BEFORE ATTEMPTING TO INSTALL OPERATE OR SERVICE THIS THERMOSTAT CAREFULLY READ THESE INSTRUCTIONS Failure to...

Страница 4: ...d into the cover and is not dislodged 10 Install the cover assembly to the base pressing firmly to engage the cover locking snaps CAUTION Before applying power the voltage selection switch must be in...

Страница 5: ...on Figure 4 to control operation of the fan In the ON position the fan output operates continuously In the AUTO position the output cycles with demand In the OFF position all outputs are off Note Mode...

Страница 6: ...ase the value press the up or down arrow button 6 Set back heat When this function is selected the current temperature range adjustment the SET BACK icon and the HEAT icon appear To increase or decrea...

Страница 7: ...tion may be provided for minimum heating and cooling requirements Using this configuration the HEAT and COOL outputs are automatically cycled on at the heat setback limit Your thermostat may not have...

Страница 8: ...urge cycle operation is as follows 1 The thermostat has a call for heat or cooling Note If at any time the call goes away the thermostat stops the purge cycle 2 The thermostat checks the pipe sensor t...

Страница 9: ...1 sensor Operation In an occupied mode the thermostat operates normally and looks for a door open signal When the door opens the thermostat waits for a door close signal If the door is open for more t...

Страница 10: ...d to allow setback input Note An optional door and or window switch Figure 11 and slave sensor can be added for use with the SD200 001 sensor Operation In an occupied mode the SD200 001 occupancy sens...

Страница 11: ...cupancy status as well as selectable high low temperature setback form C output and a five minute door open HVAC shut off This system provides basic room setback and is ideal for control of HVAC in co...

Страница 12: ...training or call 540 248 9646 and ask for the Training Department Warranty All McQuay equipment is sold pursuant to its standard terms and conditions of sale including Limited Product Warranty Consul...

Отзывы: