background image

 IM 368 / Page 15 of 20 (Rev. 11/03)

TROUBLE

CAUSE

CURE

8. Insufficient cooling

capacity (continued).

9.

Too much cooling.

10. “Sweating”

11. Blowers won’t operate on

HEAT.

12. **Equipment is noisy.

13. Insufficient or no heat.

g. Restricted capillary tube or strainer, indicated by:

1)  Frost on capillary or strainer.
2)  Low wattage.
3)  Condenser not warm.
4)  Evaporator partially frosted, only partially cool or not
     at all.

a. Thermostat set too low.
b. Defective thermostat.
a. Condensate drain from evaporator to condenser plugged.
b. Insulating seals on equipment damaged.
c. Evaporator blower motor not up to speed.
d. Evaporator blower incorrectly positioned.
a. No power.
b. Heat is off (equipment with heat fan lockout).
c. Faulty pushbutton switch.
d. Loose connections at pushbutton switch.
e. Thermostat set too low.
a. Blower rubbing against enclosure.

b. Blower motor bearings are dry.
c. Loose blower hold-down nuts on motor-bracket assembly.
d. Refrigerant absorbed in compressor oil after extended

shutdown.

e. Equipment improperly installed.
f.

Damper solenoid hums.

g. Loose terminal box cover on side of compressor.
h. Loose electrical components.
i.

Copper tubing vibrating.

j.

Harmonics.

k. Loose sheet metal parts.
a. No steam or hot water being applied.
b. No power.

c. Faulty pushbutton switch.
d. Loose connection at pushbutton switch.
e. Thermostat set too high.
f.

Thermostat faulty.

g. No power output on transformer secondary.
h. Inoperative valve.

1)  Steam valve N/C.
2)  Hot water valve N/C.

g. *Ship prepaid to nearest McQuay warranty station.

a. Adjust.
b. Replace.
a. See No. 1.
b. Open heat valve or turn on heating system.
c. Check for correct voltage.
d. Adjust.
a. See No. 1.
b. Open heat valve or turn on heating system.
c. Replace.
d. Tighten.
e. Adjust. Rotate control knob to “Warmer.”
a. Adjust fan position on motor shaft or reposition fan motor

bracket assembly.

b. Replace motor.
c. Align blower assembly and tighten nuts.
d. Noise will disappear after equipment runs awhile.

e. Make necessary adjustments to components.
f.

Check for proper adjustment. Apply silicone oil or grease
to gap between solenoid and armature.

g. Tighten.
h. Fasten securely.
i.

Adjust by bending or applying tape.

j.

Occasionally equipment will have noisy operation for no
apparent reason. Inspection has revealed no loose
components that might be the source of the noise. Due to
the action of the compressor, it is possible to have internal
noise develop if the refrigerant tubing has become bent
even slightly. To distinguish this condition from the simple
rattle producing vibration caused by loose screws, nuts
and other components, grasp the refrigerant tubing at
various points throughout the system until a point is found
where the noise is eliminated or reduced. Bend the copper
tubing very gently until the noise disappears.

k. Tighten.
a. Contact building management.
b. Check power supply line fuses, circuit breakers. Blown

fuses  would indicate circuit overloading, a short circuit, or
a grounded condition in the circuit.

c. Replace.
d. Replace wire or tighten.
e. Adjust. Rotate knob to “Warm.”
f.

Replace.

g. Replace.
h.

1)  Temporary lock valve open; replace.
2)  Replace.

Troubleshooting Chart

These items should be checked by a qualified service techician only.

Notes:
  † This guide was prepared with standard equipment in mind. If equipment is special, it may not be entirely applicable.

* If equipment is still in warranty.

** Note: Before trying to correct the noise,  determine its cause: conditioned air blower, compressor or condenser blower. Operate the conditioned air blowers only. If
this doesn’t cause the noise, operate on cooling. Then disconnect one compressor lead. If the noise stops, the compressor is the source. If not, it is caused by the
condenser blower.

Approximate Shipping Weights

Subbase:

3" (76mm) High Electrical . . . . . . . . . . . . . . . . . .
4" (102mm) High Electrical . . . . . . . . . . . . . . . . . .
8" (203mm) High Hydronic . . . . . . . . . . . . . . . . . .

Extendaire:

Primary Discharge Section . . . . . . . . . . . . . . . . .
36" (914mm) Duct Section . . . . . . . . . . . . . . . . .

10 lbs. (4.5 kg)

12 lbs. (5 kg)
20 lbs. (9 kg)

10 lbs. (4.5 kg)

22 lbs. (10 kg)

Chassis:

Size 007 141 lbs. (64 kg) . . . . . . . . . . . . . . . . . .
Size 009 145 lbs. (66 kg) . . . . . . . . . . . . . . . . . .
Size 012 149 lbs. (68 kg) . . . . . . . . . . . . . . . . . .
Size 015 153 lbs. (69 kg) . . . . . . . . . . . . . . . . . .

Wall Sleeve:

Uninsulated . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Insulated . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Room Cabinet  . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Louvers:

Flush-stamped . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Architectural . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

139 lbs. (63 kg)
143 lbs. (65 kg)
147 lbs. (67 kg)
151 lbs. (69 kg)

36 lbs. (16 kg)
37 lbs. (16 kg)

10 lbs. (4.5 kg)

6 lbs. (3 kg)
8 lbs. (4 kg)

Содержание Suite Incremental

Страница 1: ...Suite Incremental PTAC PTHP Conditioner Installation Maintenance Data Group PTAC Part No 106018472 Date November 2003 IM 368 7 2003 McQuay International...

Страница 2: ...ntacted The unit nameplate should be checked to make sure the voltage agrees with the power supply available Suite II Series Comfort Conditioner is designed and built for through the wall installation...

Страница 3: ...ubbase is 81 4 210mm Each subbase has leveling legs providing for up to 1 25 4mm additional height MCQUAY PTAC PTHP P DES 1 009 E Z 60 Product Category P PTAC Product Identifier see box below Suite De...

Страница 4: ...architectural louver Louver should be flush to exterior surface when complete Note The wall sleeve is not intended to replace the lintel 5 Level cabinet wall sleeve in both directions and secure by a...

Страница 5: ...rpose See Figure B page 7 5 Recess the wall sleeve so that the louver is flush with the exterior of the building 6 Level cabinet wall sleeve in both directions and secure by anchoring with appropriate...

Страница 6: ...te outside louver This recess is 3 8 9 5mm for stamped louvers and 11 4 32mm for architec tural louvers Louver should be flush to exterior surface when completed Note The wall sleeve is not intended t...

Страница 7: ...f the wall sleeve and another bead around the mating side of the wall sleeve extension so that the joint is watertight Be sure to use a resilient caulking such as silicone 3 Assemble the wall sleeve e...

Страница 8: ...e to the incoming power supply Hydronic Subbase A subbase is supplied as standard with all hydronic units This subbase measures 8 203mm in height and includes the hydronic heating coil Refer to IM Bul...

Страница 9: ...ure 14 illustrates the installation of the indoor drain kit The indoor drain kit should be installed before placing the cabinet wall sleeve into the opening Install as follows 1 Locate the drain so th...

Страница 10: ...to make certain they did not loosen during shipment Do not loosen nuts holding down compressor they are factory installed 11 Do not lubricate motors before startup Motors are factory lubricated Consul...

Страница 11: ...n accordance with all local and National Electrical Code requirements The conditioners are supplied as follows Electrical Heating Unit 1 208V and 230V models are supplied with an attachment cord and p...

Страница 12: ...frequent filter maintenance than those areas of relatively clean operating or low usage conditions Unit malfunction may occur if air filters are not kept clean Rinse filters with hot water and a mild...

Страница 13: ...the kinds of parts which McQuay International recommends to be carried in stock together with the quantity of parts recommended per 100 incremental conditioners installed Part Name Cooling Chassis Co...

Страница 14: ...OOL and compressor starts and runs but compressor occasionally stops on overload device 5 Compressor starts and runs on COOL but blowers do not run 6 Compressor starts and runs on COOL but blowers do...

Страница 15: ...ilicone oil or grease to gap between solenoid and armature g Tighten h Fasten securely i Adjust by bending or applying tape j Occasionally equipment will have noisy operation for no apparent reason In...

Страница 16: ...IM 368 Page 16 of 20 Rev 11 03 MODEL AIR CONDITIONER SUITE II 2 MOTOR DES THERMOSTAT UNIT HEAT ELECTRIC CHANGEOVER MANUAL Wiring Diagram Electric Heat Standard Manual Changeover Control...

Страница 17: ...IM 368 Page 17 of 20 Rev 11 03 MODEL HEAT PUMP SUITE II 2 MOTOR DHS THERMOSTAT UNIT HEAT ELECTRIC CHANGEOVER MANUAL Wiring Diagram Heat Pump Standard Manual Changeover Control...

Страница 18: ...age 18 of 20 Rev 11 03 MODEL AIR CONDITIONER SUITE II 2 MOTOR HYD DES DNS THERMOSTAT UNIT HEAT WATER CHANGEOVER MANUAL Wiring Diagram Hot Water Heat with Normally Open Valve Standard Manual Changeover...

Страница 19: ...Page 19 of 20 Rev 11 03 MODEL AIR CONDITIONER SUITE II 2 MOTOR HYD DES DNS THERMOSTAT UNIT HEAT STEAM CHANGEOVER MANUAL Wiring Diagram Steam Heat with Normally Closed Valve Standard Manual Changeover...

Страница 20: ...2003 McQuay International www mcquay com 800 432 1342 Page 20 of 20 IM 368 7 Rev 11 03...

Отзывы: