background image

IM 368 / Page 14 of 20 (Rev 11/03)

a. Check supply line fuses, circuit breakers, and be sure the

power is on. Blown fuses would indicate circuit overload-
ing, a short circuit, or a grounded condition in the circuit.
Voltage supply to the equipment should be checked.
Voltage  must be within 10% of voltage given on data
plate.

b. Replace.
c. Tighten.
a. Adjust. Rotate control knob to “Cooler.”
b. Close heat valve.
c. Check as above.
d. Replace.
e. Tighten.
f.

Replace.

g. Tighten.
h. Replace.
i.

Tighten.

j.

Replace.

k. *Ship cooling chassis prepaid to nearest McQuay authorized

warranty station.

a. Check voltage supply. Clean condenser inside and out. Check

at outside face of condenser for recirculation of condenser air.
Put air “splitters” in, if missing. Check to make sure condenser
blower/fan is operating properly. Check compressor for short
circuit. If defective, *ship cooling chassis to nearest McQuay
authorized warranty station.

a. Run separate electric line to equipment. Consult local power

company.

b. Consult local power company.

c. If confirmed, ship cooling chassis prepaid to nearest McQuay

authorized warranty station.

a. Replace.
b. Replace.
c. Adjust blower motor or blower wheel position.
d. Replace motor

e. Tighten.
a. Adjust blower/fan wheel on shaft or blower motor mounting.

b. Adjust blower wheel or motor or replace wheel.

a. Eliminate ground.

a. If the air conditioner is allowed to stand for an extended

length of time without being run on COOL, it is possible for all
the refrigerant to become absorbed in the oil inside the
compressor and refrigeration circuit. If this should happen,
there will be no cooling until the necessary working pressures
have been established. This will take about 5 minutes of
continuous running.

b.

1)  Clean.
2)  Remove obstructions.
3)  Check same as in the case of malfunctioning con-
     ditioner air blower.
4)  Check for correct voltage. Oil blower motor if nec-
     essary.
5)  Adjust blower position and tighten setscrew.
6)  Correct as in No. 3 above.

c.

1)  Clean.
2)  Turn equipment off to let ice melt.
3)  Clean or replace.
4)  Remove obstructions. In case of top discharge equipment,
     make sure books, magazines, etc., are kept off the
     equipment.
5)  Check as in No. 1.
6)  Check for correct voltage.
7)  Adjust motor wheel position and tighten setscrew.

d. Refer to original load calculations; recalculate heat load.
e. Close therm.
f.

*Ship prepaid to nearest McQuay authorized warranty station.

1. Blowers won’t operate on

COOL.

2. Blowers operate on COOL

but compressor doesn’t
start.

3. Blowers run on COOL and

compressor starts but
stops after a short
interval.

4. Blowers run on COOL and

compressor starts and
runs, but compressor
occasionally stops (on
overload device).

5. Compressor starts and

runs on COOL but blowers
do not run.

6. Compressor starts and

runs on COOL but blowers
do not run.

7. Equipment gives electrical

shock.

8. Insufficient cooling

capacity.

a. No power.

b. Faulty pushbutton switch.
c. Loose connections at pushbutton switch.
a. Thermostat set too high.
b. Heat valve is open and heat is on.
c. Low voltage.
d. Fault pushbutton switch.
e. Faulty connection at pushbutton switch.
f.

Defective wiring to thermostat.

g. Loose connections at compressor terminals.
h. Wiring to compressor terminals defective.
i.

Loose connections in compressor overload device.

j.

Starting capacitor malfunctions (open circuited, short
circuited or loss of capacity.

k. Defective compressor motor (short circuited, open

circuited, grounded).

a. Operation of overload device due to overloading

compressor motor.

a. Low voltage due to overloaded circuits within building or

throughout the local power system. Due to varying
power demands, this condition might exist only at
certain times during the day or on very hot days.

b. High voltage due to fluctuations in local power system;

usually occurs at low load periods of the day.

c. Partial short circuit in compressor motor. Under normal

loading a compressor with a partial short circuit might
appear to be operating all right; increased condensing
air temperature might then cause a short.

a. Faulty pushbutton switch.
b. Open circuited blower motor.
c. Blower rubbing against its housing.
d. Bearings on blower motor seized.

e. Loose connection at pushbutton switch.
a. Operation of the internally connected overload device

due to a short circuit in blower motor.

b. Windings, rubbing  of blower wheel or lack of lubrication

in blower motor bearings.

a. Grounded electrical circuit.

a. Equipment standing too long without being run.

b. Insufficient airflow through condenser due to:

1)  Dirty condenser.
2)  Obstructed louvers on outer cabinet or wall box.
3)  Condenser blower/fan not running.

4)  Condenser blower/fan not up to speed.

5)  Condenser blower/fan slipping on motor shaft.
6)  Recirculation of condenser air.

c. Insufficient airflow through evaporator due to:

1)  Dirty evaporator.
2)  Ice on evaporator coils.
3)  Dirty air filter.
4)  Obstructed discharge grilles.

5)  Evaporator blower motor not running.
6)  Evaporator blower motor not up to speed.
7)  Evaporator blower slipping on motor shaft.

d. Heat load in room exceeds capacity of equipment.
e. Windows and doors in room are open.
f.

Compressor not pumping, indicated by:
1)  Low wattage.
2)  Condenser not warm, evaporator only partially cool
     or not at all.

Troubleshooting Chart

These items should be checked by a qualified service techician only.

TROUBLE

CAUSE

CURE

Continued on next page

Содержание Suite Incremental

Страница 1: ...Suite Incremental PTAC PTHP Conditioner Installation Maintenance Data Group PTAC Part No 106018472 Date November 2003 IM 368 7 2003 McQuay International...

Страница 2: ...ntacted The unit nameplate should be checked to make sure the voltage agrees with the power supply available Suite II Series Comfort Conditioner is designed and built for through the wall installation...

Страница 3: ...ubbase is 81 4 210mm Each subbase has leveling legs providing for up to 1 25 4mm additional height MCQUAY PTAC PTHP P DES 1 009 E Z 60 Product Category P PTAC Product Identifier see box below Suite De...

Страница 4: ...architectural louver Louver should be flush to exterior surface when complete Note The wall sleeve is not intended to replace the lintel 5 Level cabinet wall sleeve in both directions and secure by a...

Страница 5: ...rpose See Figure B page 7 5 Recess the wall sleeve so that the louver is flush with the exterior of the building 6 Level cabinet wall sleeve in both directions and secure by anchoring with appropriate...

Страница 6: ...te outside louver This recess is 3 8 9 5mm for stamped louvers and 11 4 32mm for architec tural louvers Louver should be flush to exterior surface when completed Note The wall sleeve is not intended t...

Страница 7: ...f the wall sleeve and another bead around the mating side of the wall sleeve extension so that the joint is watertight Be sure to use a resilient caulking such as silicone 3 Assemble the wall sleeve e...

Страница 8: ...e to the incoming power supply Hydronic Subbase A subbase is supplied as standard with all hydronic units This subbase measures 8 203mm in height and includes the hydronic heating coil Refer to IM Bul...

Страница 9: ...ure 14 illustrates the installation of the indoor drain kit The indoor drain kit should be installed before placing the cabinet wall sleeve into the opening Install as follows 1 Locate the drain so th...

Страница 10: ...to make certain they did not loosen during shipment Do not loosen nuts holding down compressor they are factory installed 11 Do not lubricate motors before startup Motors are factory lubricated Consul...

Страница 11: ...n accordance with all local and National Electrical Code requirements The conditioners are supplied as follows Electrical Heating Unit 1 208V and 230V models are supplied with an attachment cord and p...

Страница 12: ...frequent filter maintenance than those areas of relatively clean operating or low usage conditions Unit malfunction may occur if air filters are not kept clean Rinse filters with hot water and a mild...

Страница 13: ...the kinds of parts which McQuay International recommends to be carried in stock together with the quantity of parts recommended per 100 incremental conditioners installed Part Name Cooling Chassis Co...

Страница 14: ...OOL and compressor starts and runs but compressor occasionally stops on overload device 5 Compressor starts and runs on COOL but blowers do not run 6 Compressor starts and runs on COOL but blowers do...

Страница 15: ...ilicone oil or grease to gap between solenoid and armature g Tighten h Fasten securely i Adjust by bending or applying tape j Occasionally equipment will have noisy operation for no apparent reason In...

Страница 16: ...IM 368 Page 16 of 20 Rev 11 03 MODEL AIR CONDITIONER SUITE II 2 MOTOR DES THERMOSTAT UNIT HEAT ELECTRIC CHANGEOVER MANUAL Wiring Diagram Electric Heat Standard Manual Changeover Control...

Страница 17: ...IM 368 Page 17 of 20 Rev 11 03 MODEL HEAT PUMP SUITE II 2 MOTOR DHS THERMOSTAT UNIT HEAT ELECTRIC CHANGEOVER MANUAL Wiring Diagram Heat Pump Standard Manual Changeover Control...

Страница 18: ...age 18 of 20 Rev 11 03 MODEL AIR CONDITIONER SUITE II 2 MOTOR HYD DES DNS THERMOSTAT UNIT HEAT WATER CHANGEOVER MANUAL Wiring Diagram Hot Water Heat with Normally Open Valve Standard Manual Changeover...

Страница 19: ...Page 19 of 20 Rev 11 03 MODEL AIR CONDITIONER SUITE II 2 MOTOR HYD DES DNS THERMOSTAT UNIT HEAT STEAM CHANGEOVER MANUAL Wiring Diagram Steam Heat with Normally Closed Valve Standard Manual Changeover...

Страница 20: ...2003 McQuay International www mcquay com 800 432 1342 Page 20 of 20 IM 368 7 Rev 11 03...

Отзывы: