 IM 368 / Page 3 of 20 (Rev. 11/03)

Figure 2. Suite Unit with Electric Subbase

Notes:

Unit pictured with subbase installed. Subbase is optional on 208V and 230V units. Subbase is standard on all 265V units and units with hydronic heat.

Subbase extends to front edge of unit when furnished with hydronic heat.

Opening needs to be 16 

5

/

8

" (422mm) x 42

5

/

8

" (1083mm) when using a louver frame. See page 7.

Subbase side channels are adjustable from 4

3

/

8

" to 13

3

/

4

" (111mm to 349mm).

Wall Opening Requirement

Before installing the unit, check the wall opening to be sure the
cabinet/wall sleeve will slide into the opening unobstructed. For
masonry walls, a lintel must be used to provide support over each
opening. The rough opening should measure 16

1

/

4

" (413mm) X

42

1

/

4

" (1073mm) wide (see note 

). When no subbase is used,

the opening should be a minimum of 3" (76mm) off the floor. This

distance may vary when a subbase is supplied. The standard
subbase is available in 3" (76mm) or 4" (102mm) heights. For
units with hydronic heat, the subbase is 8

1

/

4

" (210mm). Each

subbase has leveling legs providing for up to 1" (25.4mm)
additional height.

MCQUAY PTAC/PTHP

P   DES   1   009   E   Z   60

Product Category
P = PTAC

Product Identifier
see box below (Suite)

Design Series
1 = A Design

Nominal Capacity
007 = 7,000
009 = 9,000
012 = 12,000
015 = 15,000

Heating Options
35 = 2.5 kw
41 = 3.5 kw
48 = 5.0 kw
62 = Hydronic, normally open
63 = Hydronic, normally closed

Coil Options
(None)

Voltage
A = 115 - 60 - 1
C = 208 - 60 - 1
J = 265 - 60 - 1

DEA = Suite II, 2 motor, automatic damper
DEC = A/C & Elec/Hyd Htg Chassis w/Corr. Protection
DEH = Suite II, 2 motor, hydronic w/standby
DEI

= Suite II, 2 motor, IAQ

DES = A/C & Heating (Elec/Hyd) Chassis
DHA = Suite II, 2 motor, heat pump, automatic damper
DHC = H/P w/ Electric Heat & Corrosion Protection
DHI

= Suite II, 2 motor, heat pump, IAQ

DHS = H/P w/ Electric Heat

McQuay PTAC/PTHP Product Identifiers

SEA = A/C w/Electric Heat & Automatic OA Damper
SEC = A/C w/Electric Heat & Corrosion Protection
SEH = A/C w/Hydronic Heat & Standby(Emergency) Power
SEI

= A/C w/Electric Heat & IAQ Power Vent Kit

SES = A/C & Heating (Elec/Hyd) Chassis
SHA = A/P w/Electric Heat & Automatic OA Damper
SHC = H/P w/ Electric Heat & Corrosion Protection
SHI

= H/P w/ Electric Heat & IAQ Power Vent Kit

SHS = H/P w/Electric Heat

Содержание Suite Incremental

Страница 1: ...Suite Incremental PTAC PTHP Conditioner Installation Maintenance Data Group PTAC Part No 106018472 Date November 2003 IM 368 7 2003 McQuay International...

Страница 2: ...ntacted The unit nameplate should be checked to make sure the voltage agrees with the power supply available Suite II Series Comfort Conditioner is designed and built for through the wall installation...

Страница 3: ...ubbase is 81 4 210mm Each subbase has leveling legs providing for up to 1 25 4mm additional height MCQUAY PTAC PTHP P DES 1 009 E Z 60 Product Category P PTAC Product Identifier see box below Suite De...

Страница 4: ...architectural louver Louver should be flush to exterior surface when complete Note The wall sleeve is not intended to replace the lintel 5 Level cabinet wall sleeve in both directions and secure by a...

Страница 5: ...rpose See Figure B page 7 5 Recess the wall sleeve so that the louver is flush with the exterior of the building 6 Level cabinet wall sleeve in both directions and secure by anchoring with appropriate...

Страница 6: ...te outside louver This recess is 3 8 9 5mm for stamped louvers and 11 4 32mm for architec tural louvers Louver should be flush to exterior surface when completed Note The wall sleeve is not intended t...

Страница 7: ...f the wall sleeve and another bead around the mating side of the wall sleeve extension so that the joint is watertight Be sure to use a resilient caulking such as silicone 3 Assemble the wall sleeve e...

Страница 8: ...e to the incoming power supply Hydronic Subbase A subbase is supplied as standard with all hydronic units This subbase measures 8 203mm in height and includes the hydronic heating coil Refer to IM Bul...

Страница 9: ...ure 14 illustrates the installation of the indoor drain kit The indoor drain kit should be installed before placing the cabinet wall sleeve into the opening Install as follows 1 Locate the drain so th...

Страница 10: ...to make certain they did not loosen during shipment Do not loosen nuts holding down compressor they are factory installed 11 Do not lubricate motors before startup Motors are factory lubricated Consul...

Страница 11: ...n accordance with all local and National Electrical Code requirements The conditioners are supplied as follows Electrical Heating Unit 1 208V and 230V models are supplied with an attachment cord and p...

Страница 12: ...frequent filter maintenance than those areas of relatively clean operating or low usage conditions Unit malfunction may occur if air filters are not kept clean Rinse filters with hot water and a mild...

Страница 13: ...the kinds of parts which McQuay International recommends to be carried in stock together with the quantity of parts recommended per 100 incremental conditioners installed Part Name Cooling Chassis Co...

Страница 14: ...OOL and compressor starts and runs but compressor occasionally stops on overload device 5 Compressor starts and runs on COOL but blowers do not run 6 Compressor starts and runs on COOL but blowers do...

Страница 15: ...ilicone oil or grease to gap between solenoid and armature g Tighten h Fasten securely i Adjust by bending or applying tape j Occasionally equipment will have noisy operation for no apparent reason In...

Страница 16: ...IM 368 Page 16 of 20 Rev 11 03 MODEL AIR CONDITIONER SUITE II 2 MOTOR DES THERMOSTAT UNIT HEAT ELECTRIC CHANGEOVER MANUAL Wiring Diagram Electric Heat Standard Manual Changeover Control...

Страница 17: ...IM 368 Page 17 of 20 Rev 11 03 MODEL HEAT PUMP SUITE II 2 MOTOR DHS THERMOSTAT UNIT HEAT ELECTRIC CHANGEOVER MANUAL Wiring Diagram Heat Pump Standard Manual Changeover Control...

Страница 18: ...age 18 of 20 Rev 11 03 MODEL AIR CONDITIONER SUITE II 2 MOTOR HYD DES DNS THERMOSTAT UNIT HEAT WATER CHANGEOVER MANUAL Wiring Diagram Hot Water Heat with Normally Open Valve Standard Manual Changeover...

Страница 19: ...Page 19 of 20 Rev 11 03 MODEL AIR CONDITIONER SUITE II 2 MOTOR HYD DES DNS THERMOSTAT UNIT HEAT STEAM CHANGEOVER MANUAL Wiring Diagram Steam Heat with Normally Closed Valve Standard Manual Changeover...

Страница 20: ...2003 McQuay International www mcquay com 800 432 1342 Page 20 of 20 IM 368 7 Rev 11 03...