background image

McQuay IM 777-1

27

Service and Maintenance

To remove the fan assembly:

1

Remove the side panels and any intermediate supports 
(follow instructions for side panel removal)

2

Once the panels and any intermediate supports are 
removed, disconnect the neoprene bulk head seal that is 
attached to the fan discharge

3

Remove the four discharge angles that hold the neoprene 
canvas in place around the discharge opening

4

Disconnect the fan sled from each of the corner mounts and 
pull the entire assembly out the side of the unit

5

After the fan sled is out, loosen the fan bearings and pull 
out the shaft

6

Disconnect the fan housing from the fan sled, and bearing 
support by removing the attaching bolts

7

Replace the new fan, reconnect the shaft and bearings and 
put the fan assembly in the cabinet.

8

Replace panels and fasteners.

Removing and Replacing the Coil

Removing Single Coils

Note –

Single coils are bolted to the unit on the connection end. 
The connection end is held in place with a clamp. 

See

Figure 39

.

1

Disconnect all piping and remove the brass plugs for the 
vents and drains located in the connections. 

2

Remove all screws and remove the access panel.

3

Remove the screws holding the coil in place

4

Lift and pull the coil out the side.

Installing Single Coils

1

Slide the coil through the opening in the coil section onto 
the bottom coil rests.

2

To prevent any air bypass around the coil, place coils up 
against the coil bulkheads. See Figure 39

.

3

Once the coil is in place, fasten the coil to the section. 

4

Caulk the seams between the coil casings and bulkheads

.

See Figure 39

.

5

If this is an additional coil being installed and not a 
replacement, locate the coil supply and return connections 
dimensionally. Carefully drill holes in the end panels of the 
unit.

6

Remove the brass plugs for the vents and drains on the 
connections.

7

Slip the panel over the connections. 

8

Replace the brass plugs and panel fasteners.

Figure 39: Single coil installation/removal

Removing Stacked Coils

Note –

Top and bottom stacked coils are held together with steel 
plate and screws on one side and drain trough and 
screws on the other side. Remove the plate and trough 
before removing the coils. The coils cannot be removed 
attached together.

1

Disconnect all piping and remove the brass plugs for the 
vents and drains located in the connections. 

2

Remove all screws and remove the access panel.

3

Remove the bolts holding the coil in place and then lift and 
pull out the coil from the side.

4

Remove the steel plate and the drain trough that hold the 
coils together.

5

Remove the bolts on both ends of the top coil holding it in 
place and then lift and slide the coil out.

6

Remove the bolts on both ends of the bottom coil holding it 
in place and then lift and slide the coil out.

Installing Stacked Coils

1

Slide the bottom coil through the opening in the coil section 
onto the bottom coil rests. 

2

Place the coil up against the coil bulkheads to prevent any 
air bypass around the coil. 

3

Once the coil is in place, bolt the coil to the section.

4

Caulk the mounting surface of the steel plate and install the 
plate on the coils.

5

Caulk the mounting surface of the drain trough and install 
the drain trough on the coils.

6

Caulk the seams between the coil casings and blockoffs

.

Coil

Connection end

Coil

Opposite connection  end

Coil 
Bulkhead

Coil 
Rests

Содержание Skyline IM 777-1

Страница 1: ...McQuay IM 782 1 1 Installation and Maintenance Manual IM 777 1 Group Applied Air Part Number IM 777 Date June 2005 2005 McQuay International Skyline Air Handler Sizes 003 090...

Страница 2: ...ater Cooling Coils 8 Direct Expansion Coils 8 Steam Coils see Figure 18 on page 10 9 Water Heating Coils 11 Drain Pan Traps 11 Internal Isolation Assembly Adjustment 12 Electrical Installation 13 Oper...

Страница 3: ...fore unit installation to verify this has not happened 4 Screws bolts etc for assembling sections are supplied in a bag attached to each section All necessary gasketing is applied in the factory for s...

Страница 4: ...igure 2 Figure 1 Servicing space requirements Figure 2 Service clearance for electrical power devices Rigging Skyline air handlers ship as separate sections completely assembled or in modules of assem...

Страница 5: ...all assembly joints of the unit Before joining the sections apply at least 1 4 inch diameter bead of sealant to the mating faces of the cabinet Use the splice joint as a guide for applying the sealan...

Страница 6: ...slip the splice cap over the top panel flanges Bend the ends of the splice cap down to secure in place 6 Assemble the small splice plate at the top rail to secure the sections together at the top Use...

Страница 7: ...the jam nuts Figure 10 Opening fan section door Injected Foam Insulated Panels Skyline air handlers now are furnished with double wall injected foam insulated panels Foam panels are stronger more rig...

Страница 8: ...ctions are necessary See Figure 12 Figure 12 Discharge plenum If the unit has a top mixing box or economizer damper or a top duct connection field fabricate and install flashing to divert moisture fro...

Страница 9: ...same actuator if the dampers are the same size If the dampers are different sizes they must be driven by separate actuators and controlled appropriately Exhaust dampers are always driven by a separate...

Страница 10: ...e coils to freezing temperatures Water supply water return drain and vent connections extend through the end panel of the coil section All connections are labeled on the end panel Water supply and wat...

Страница 11: ...Use thermostatic traps only for air venting Use bucket traps for on off control only Locate traps at least 12 inches below the coil return connection Multiple coil installation Individually trap each...

Страница 12: ...aker 1 2 check valve Steam main Return main 12 min Vacuum breaker 1 2 check valve Steam main Return main 12 min Full size of return conn Check Valve Strainer Gate Valve Control valve modulating two po...

Страница 13: ...n pan trap to allow condensate to drain freely On both blow through and draw through units the trap depth and the distance between the trap outlet and the drain pan outlet must be twice the static pre...

Страница 14: ...he cap screw when adjustments are completed For models 040 through 090 the isolators should be at equal height during fan operation 6 Center the fan outlet in the outlet panel opening If adjustment is...

Страница 15: ...m of the fan motor junction box See Figure 22 Figure 22 Electrical conduit location CAUTION The base section of each cabinet has a drip pan installed below every panel that drains to the outside frame...

Страница 16: ...t m me la mort L alimentation lectrique du moteur du ventilateur de m me que la mise la terre du ch ssis du moteur doivent tre faits conform ment aux codes d nstallations lectriques en vigueur WARNING...

Страница 17: ...wheel s axially as needed and retightening setscrews 3 To obtain dimension B loosen screw and washer fasteners around periphery of funnel s shifting funnel radially as required and re torquing fastene...

Страница 18: ...5 440 24 5 500 27 560 30 620 33 750 36 5 810 40 25 880 44 5 940 49 1 000 54 25 1 060 60 1 120 Overlap Table 5 Wheel to inlet funnel relationship inline fans Wheel funnel overlap Size Overlap 150 375 1...

Страница 19: ...1 56 24 00 Maximum rpm Class I 3000 3000 2300 2000 1700 1500 Maximum rpm Class Il 4335 3918 3457 2858 2427 2255 300 250 200 150 100 90 80 Torque in lb 350 400 450 500 600 650 700 750 800 850 1000 1500...

Страница 20: ...00 AF30 00 500 600 700 800 2000 1000 1500 1500 2000 3000 2500 Torque in lb Table 9 Operating limits plenum fans Fan operating limits Plenum fans Diameter 13 5 15 16 5 18 25 20 22 25 24 5 27 30 33 36...

Страница 21: ...ble pitch sheaves Axial and radial runout of flanges uneven groove spacing out of balance Also similar faults in driven sheave b Bad V belts lumpy or mismatched belt tension too tight or too loose 4 B...

Страница 22: ...the air balance replace the variable pitched motor sheave with a properly sized fixed sheave A matching fixed sheave provides longer belt and bearing life and minimizes vibration Initially it is best...

Страница 23: ...number of turns from closed position 7 Verify that all keys are in place and that all se screws are tight before starting drive Check setscrews and belt tension after 24 hours service Figure 32 VP typ...

Страница 24: ...t on page 24 9 Before starting the drive ensure that all keys are in place and all setscrews and all capscrews are tight Check and retighten all screws and retension belts after approximately 24 hours...

Страница 25: ...hs L less than dia Seating torque Seating torque Seating torque Seating torque Length L Seating torque in lbs in lbs in lbs in lbs in lbs in lbs in lbs 1 4 20NC 150 12 5 100 87 7 3 3 16 50 5 16 11NC 3...

Страница 26: ...oving belt and fan can cause severe personal injury or death During installation and filter maintenance Verify that the belt and fan guards on plenum fan units are always in place Lock and tag out fan...

Страница 27: ...Filter gauge Table 15 Belt deflection force per Browning specifications Cross section Sheave diameter in Deflection force lbs Smallest sheave diameter range rpm range Cross section A B 5V Cross secti...

Страница 28: ...reezing of coils Removing and Replacing Components See Access Doors and Panels on page 5 for instructions on removing panels and opening fan access doors to remove or replace components Removing the F...

Страница 29: ...s See Figure 39 5 If this is an additional coil being installed and not a replacement locate the coil supply and return connections dimensionally Carefully drill holes in the end panels of the unit 6...

Страница 30: ...and remove the brass plugs for the vents and drains located in the connections 2 To access bolts holding the coils in place remove the panels on both the connection and opposite connection end of the...

Страница 31: ...must be prepaid The return of the part does not constitute an order for replacement Therefore a purchase order must be entered through the nearest McQuay representative The order should include part...

Страница 32: ...30 McQuay IM 777 1...

Страница 33: ...McQuay IM 777 1 31...

Страница 34: ...32 McQuay IM 777 1...

Страница 35: ......

Страница 36: ...ipment its care should be a high priority For training information on all McQuay HVAC products please visit us at www mcquay com and click on training or call 540 248 9646 and ask for the Training Dep...

Отзывы:

Похожие инструкции для Skyline IM 777-1