background image

IM 950-1 / Page 32 of 38

10. Clean any rust spots with steel wool and paint with  

 

rust inhibiting paint.

11.  Clean insulation or replace if necessary.

12.  Check insulation on refrigeration piping and  

 

replace if necessary.

13.  Check all fasteners and tighten as required.

14.  Clean and oil damper door and linkage.

15.  Test run chassis before reinstalling.

Equipment Protection From The

Environment

The metal parts of this unit may be subject to rust or 

deterioration in adverse environmental conditions. 

This oxidation could shorten the equipment’s useful 

life. Salt spray, fog or mist in seacoast areas, sulphur 

or chlorine from lawn watering systems, and various 

chemical contaminants from industries such as paper 

mills and petroleum refineries are especially corrosive.

If the unit is to be installed in an area where 
contaminants are likely to be a problem, special 
attention should be given to the equipment location 
and exposure.

1   Avoid having lawn sprinkler heads spray directly 

in or on the outdoor louver.

2   In coastal areas, the units must have the corrosion 

protection package to maintain the warranty 

coverage.

Regular maintenance will reduce the buildup of 
contaminants and help to protect the outdoor 
section of the unit.

1   Frequent washing of the outdoor section,    

 

condenser fan blade and condenser coil with  

 

fresh water will remove most of the salt or other  

 

contaminants that build up in the outdoor section  

 

of the unit

2   Regular cleaning of the cabinet with a good non- 

 

abrasive polish will provide protection and keep it  

 

in good condition.

3   A mild liquid cleaner may be used several times a 

year to remove matter that will not wash off with 

water.

The best protection is frequent cleaning, 
maintenance and minimal exposure to contaminant.

Maintenance (Scheduled)

Incremental conditioners are built to last. With 

proper care, the unit should provide uninterrupted 

service for many years. Scheduled maintenance of 

this equipment as described below, is the key to the 

equipment’s longevity.
A.  Air filters must be cleaned at regular intervals.  

 

Twice annually may be adequate in some areas  

 

while twice monthly may be required in others.  

 

Areas with high dirt and lint content or heavy  

 

usage of units require more frequent filter    

 

maintenance than those areas of relatively clean  

 

operating or low usage conditions. Unit  

 

 

malfunction will occur if air filters are not kept  

 

clean. Rinse filter with hot water and a mild   

 

detergent.

B.   McQuay recommends that every year the chassis  

 

be removed for a thorough checkup. This should  

 

be completed as follows:

1.   Unplug unit from power source.

2.   Remove front panel.

3.   Remove chassis from cabinet and move it to the  

 

maintenance department. Replace with spare  

 

chassis or weather plate.

4.   Check all seals and insulation and repair as    

 

required.

5.  Check all wiring and controls for hazardous   

 

conditions.

6.   Thoroughly clean discharge grilles.

7.   Cover motors and control module with water tight  

 

material and wash evaporator coil, condenser coil  

 

and base pan using hot water and a mild soap.

CAUTION

Residential and institutional cleaning compounds can 
cause permanent damage to the packaged terminal 
unit. To avoid damage to unit controls and heat transfer 
surfaces, do not spray cleaning compounds onto the 
discharge grille, return air opening, or unit controls. 
Normal cleaning can be accomplished by wiping the 
unit surface with a damp cloth. When using cleaning 

compounds on carpets, floors or walls, turn the unit off 

to avoid drawing potentially damaging vapors into the 
package terminal unit.

8.   Check condensate removal system and assure  

 

proper operation. Pour at least two (2) cups of  

 

water into evaporator drain pan and verify proper  

 

operation. Clean condensate drain and clear weep  

 

holes located at the bottom rear of wall sleeve.

9.   Dry equipment thoroughly, especially electric  

 

parts and installation. 

Содержание PDAE

Страница 1: ...ho are familiar with local codes and regula tions and are experienced with this type of equipment Caution Sharp edges and coil surfaces are potential injury hazards Installation Maintenance Data IM 95...

Страница 2: ...9 Room Cabinet Wall Sleeve 10 11 Heating Cooling Chassis 12 Heat Fan Lock Out Control 12 Equipment Start up 13 Start up Report Audit 14 Controls 15 26 Standard Digital Touchpad Control 15 17 Modes of...

Страница 3: ...ight bill or carrier s receipt and signed by the carrier s agent Failure to adequately describe such external evidence of loss or damage may result in the carrier s refusal to honor a damage claim The...

Страница 4: ...Heat Type S Steam Top Mount Normally Closed H Hot Water Top Mount Normally Open Y None SKU A Stock B Build to Order P DAE 1 009 E M R H A B D M A A E Controls Control Board Type B Basic Control P Pre...

Страница 5: ...c Heat 163 8 416mm 447 8 1140mm 411 2 1054mm 111 16 43mm 3 76mm or 4 102mm 101 2 267mm Minimum Finished Wall Line 61 4 159mm 41 4 108mm to 133 4 349mm 20 508mm 1 2 13mm A A Louver thickness 3 8 10mm s...

Страница 6: ...ers Overhangs that do not allow discharge air to rise Installation of bug screen of any kind 5 Heating Cooling Chassis Shipped in palletized carton Figure 1 Panel Wall Thin Construction Figure 3 Frame...

Страница 7: ...eptacle is generally mounted beneath the conditioner on or recessed in the wall so it is concealed by the conditioner overhang see Figure 5 The chassis cord has a 18 inch usable length from where it e...

Страница 8: ...installed to the wall sleeve extension 5 Continue wall sleeve installation according to instructions on page 10 11 Preparing Unit for Installation Note first install the louver frame following steps 1...

Страница 9: ...two 2 5 32 pilot holes for the mounting screws These holes can be located using the drain kit as a pattern 4 Assemble the drain kit as shown in Figure 10 and securely fasten it to the wall sleeve with...

Страница 10: ...base The rear face of the cabinet should be recessed from the outside edge of the louver frame by the depth of the louver to be installed see Figure 12 4 Level the subbase with leveling bolts provided...

Страница 11: ...bubble to the outside secure it and the louver frame to the wall with screws driven through the sides and top of the room cabinet wall sleeve outward through the louver frame Never secure the frame t...

Страница 12: ...s Report any shipping damage to the carrier immediately 2 Check the interior of the installed room cabinet wall sleeve Clean out any dirt or debris that may have accumulated If Replacement chassis is...

Страница 13: ...equipment leaves the McQuay factory it may become damaged or maladjusted during transportation or on the job Sometimes wires are disconnected accidentally or fan motors move on their bases due to roug...

Страница 14: ...er Air Free of Obstruction Cycle Continuous Fan if so equipped Other Conditions Found ___________________________________________________________ ______________________________________________________...

Страница 15: ...tP Touchpad Control t Time Ts Temperature Setpoint Rf Room Freeze Condition CF Coil Freeze Protection F Fahrenheit C Celsius LC Control Lockout Mode Remote Thermostat Control The Remote Thermostat ca...

Страница 16: ...trol shall start with the last settings used prior to power down These settings are saved in a non volatile memory Factory set mode is OFF On Off Triggering Control can be turned On Off via LUI Remote...

Страница 17: ...d Controls Standard Digital Touchpad Control Modes of Operation Cool Mode In Cool Mode the compressor will start if the temperature at the space temperature sensor is 1 F or higher than the set point...

Страница 18: ...perature differential between the room temperature and the set point is less than 2 F This will also occur after a Cold Start or a Mode change from Cool to Cool Dry During this time the fan will opera...

Страница 19: ...tion will be deactivated by Power on reset or by pressing any button on the Touchpad except Sleep 4 Fan Mode In the Fan Mode the fan will operate continuously at the user s speed setting The compresso...

Страница 20: ...fan can be started only if the following conditions are met 1 after the 3 minute delay on break AND 2 the indoor coil reaches 49 F or above and remains there for at least 1 minute OR 3 another Mode is...

Страница 21: ...76mm or 4 102mm height and can be furnished with factory mounted fused disconnect option 3 On all 265V models an electrical subbase is required The chassis is supplied with a short cord which is just...

Страница 22: ...ey are of 560 Ohm and 3W value These resistors are meant to load thermostat solid state outputs in order for the output voltage to be either 0 or 24VAC i e no floating voltage These resistors are conn...

Страница 23: ...by pressing Mode button 2 1 Once in the configuration mode the default temperature scale will be displayed as shown below Toggle the temperature scale to degree Celsius by pressing either or button 2...

Страница 24: ...e thermostat for each period of the day repeat steps 3 3 through 3 7 Further the thermostat can be programmed for each individual day of the week or use the SimplesetTM feature as described below 3 9...

Страница 25: ...ackup SC2001 Temperature Control Ranges 45o F to 90o F Accuracy 1o F System Configurations 1 stage heat 1 stage cool or single stage electric heat pump Terminations R C W Y O B G Specifications Electr...

Страница 26: ...s There are two basic types of thermostats manufactured today those with relay contacts and those with solid state triacs If you open the thermostat and don t see relays then you can assume it to be s...

Страница 27: ...ement are as follows 1 When wiring the low voltage plug and receptacle disconnect provide enough wire to move harness out of the way for chassis removal Remote Wall Mounted Thermostats 2 If subbase is...

Страница 28: ...e room temperature 3 Jumper Placement to Select Controller Type A Place jumper across LUI to select unit mounted touchpad Local User Interface B Place jumper across secondary SEC to select secondary c...

Страница 29: ...door Fan Motor OCS Outdoor Coil Sensor OAS Outdoor Air Sensor ICS Indoor Coil Sensor IAS Indoor Air Sensor LUI Local User Interface REV Reversing Valve EHC Eletric Heat Contactor 1 Jumper Placement to...

Страница 30: ...the premium control board For the latest drawing version refer to the wiring diagram located on the inside of the controls access panel of the unit Wire Color Voltage WH 120V RD 208V OR 240V BN 277V...

Страница 31: ...emium control board For the latest drawing version refer to the wiring diagram located on the inside of the controls access panel of the unit Wire Color Voltage WH 120V RD 208V OR 240V BN 277V Drawing...

Страница 32: ...With proper care the unit should provide uninterrupted service for many years Scheduled maintenance of this equipment as described below is the key to the equipment s longevity A Air filters must be c...

Страница 33: ...t of the system A further advantage is that a failed part can be quickly and easily replaced thus minimizing the inoperative time of the equipment This is so however only if a replacement part is quic...

Страница 34: ...t LA Low Ambient Lockout Outdoor air temperature is below 35 F Fault and Protection Codes for Applied PTAC PTHP Control Board Fault code Description Cause for the fault LC Control Lockout Displays for...

Страница 35: ...Obstructed discharge grilles 5 Evaporator blower motor not running 6 Evaporator blower motor not up to speed 7 Evaporator motor slipping on motor shaft d Heat load in room exceeds capacity of equipme...

Страница 36: ...Noise will disappear after equipment runs awhile e Make necessary adjustments to components f Check for proper adjustment Apply silicone oil or grease to gap between solenoid and armature g Tighten h...

Страница 37: ...ged 129 5 137 0 137 9 145 6 145 6 PDHE Chassis 116 0 123 5 124 4 132 1 PDAE Chassis 114 5 122 0 122 9 130 6 130 6 Louvers Flush stamped 6 lbs 3kg Architectural 8 lbs 3kg Subbase 3 76mm High Electrical...

Страница 38: ...m and click on training or call 540 248 9646 and ask for the Training Department Warranty All McQuay equipment is sold pursuant to its standard terms and conditions of sale including Limited Product W...

Отзывы: