background image

IM 950-1 / Page 16 of 38

Controls

Standard Digital Touchpad Control

Indoor and Outdoor Fan Operation

The indoor fan can be set to operate on High 

or Low speed with the Fan Speed Button on the 

touchpad. It can also be set for Continuous or Cycle 

operation on the touchpad. When set for Continuous, 

the “CONT” LED will be on and the fan will run 

continuously. When set for Cycle, the “CYCLE” LED 

will be on and the fan will turn on at a call for heat or 

cooling.

Fan Cycle Operation 

On a call for Heating or Cooling, the indoor fan 

and the heating source or the compressor will be 

activated. When the call is satisfied and the heating 

source or the compressor is deactivated, the indoor fan 

will repeatedly run for 2 minutes on and the number 

of minutes selected on the PC Board off, until the next 

cut-in cycle. The number of cycles with timing as 

described above is determined based on the OFF FAN 

CYCLE jumper setting. 

Remote T’Stat Mode  

The unit can be jumper configured to take 

commands from a Remote Thermostat. The Remote 

Thermostat will call for Heat and Cool through the 

electronic controller. 

1.  The Remote T’stat will control through the board  

 

the work of the compressor, indoor and outdoor  

 

fans, the reversing valve, and the heater 

2.  System will run in Cool mode when Y signal is  

 

high. In cool mode compressor (therefore    

 

outdoor fan) shall turn on

3.  Cold start feature (see Modes of Operation – Cold  

 

Start), Cool dry mode (see Cold Dry Mode) and  

 

Sleep feature (see Sleep Feature) are not available  

 

in Remote T’stat cool mode

Operation

Memory Recall

The digital control shall start with the last settings 

used prior to power down. These settings are saved in a 

non-volatile memory. Factory set mode is OFF. 

On/Off Triggering 

Control can be turned On/Off via LUI, Remote 

T’stat, or Sleep feature. The control will show the 

temperature set point when the mode is Cool, Cool 

Dry, or Heat. The display will be blank in Fan mode.

1.

 

On/Off triggering with LUI

 

 

Control shall turn On or Off when the On/Off  

 

button is pressed in LUI. Once turned on control  

 

shall start on the last mode used before it was  

 

turned Off.

2.

 

On/Off triggering with the Remote T’stat 

 

Control shall be turned On if it was Off from the  

 

Remote T’stat when it is set up to be controlled by  

 

a Remote T’stat. A call for heat or cool from the  

 

Remote T’stat will be used to turn the control on.  

 

Control remains on until manually turned Off.

3.

 

On/Off triggering with the Sleep feature

 

Sleep feature works in combination with the Timer  

 

setting. Sleep time setting shall be user adjustable  

 

from 1 to 15 hours via the Touchpad. The timer  

 

will count down and when it reaches “0” it will  

 

turn the control Off if control was previously On  

 

and vice versa, if it was Off it will turn On after  

 

time expires. As mentioned in 

protections

 section  

 

of this spec the Sleep operation is overridden by  

 

room freeze protection.

Control Off

When the control is in the Off Mode, relay outputs 

will be disabled with the exception of the indoor 

fan (blower).  It will stay on to meet the 

Hot Keep 

specification. Indicator LED’s are all off.

Temperature Range

The maximum operating temperature range is 

selectable via the Touchpad and is 60°F to 85°F with 

the limits included. The Remote Thermostat selectable 

operating range is 60°F to 90°F with limits included. 

The range is set in the Set-up menu. 

Содержание PDAE

Страница 1: ...ho are familiar with local codes and regula tions and are experienced with this type of equipment Caution Sharp edges and coil surfaces are potential injury hazards Installation Maintenance Data IM 95...

Страница 2: ...9 Room Cabinet Wall Sleeve 10 11 Heating Cooling Chassis 12 Heat Fan Lock Out Control 12 Equipment Start up 13 Start up Report Audit 14 Controls 15 26 Standard Digital Touchpad Control 15 17 Modes of...

Страница 3: ...ight bill or carrier s receipt and signed by the carrier s agent Failure to adequately describe such external evidence of loss or damage may result in the carrier s refusal to honor a damage claim The...

Страница 4: ...Heat Type S Steam Top Mount Normally Closed H Hot Water Top Mount Normally Open Y None SKU A Stock B Build to Order P DAE 1 009 E M R H A B D M A A E Controls Control Board Type B Basic Control P Pre...

Страница 5: ...c Heat 163 8 416mm 447 8 1140mm 411 2 1054mm 111 16 43mm 3 76mm or 4 102mm 101 2 267mm Minimum Finished Wall Line 61 4 159mm 41 4 108mm to 133 4 349mm 20 508mm 1 2 13mm A A Louver thickness 3 8 10mm s...

Страница 6: ...ers Overhangs that do not allow discharge air to rise Installation of bug screen of any kind 5 Heating Cooling Chassis Shipped in palletized carton Figure 1 Panel Wall Thin Construction Figure 3 Frame...

Страница 7: ...eptacle is generally mounted beneath the conditioner on or recessed in the wall so it is concealed by the conditioner overhang see Figure 5 The chassis cord has a 18 inch usable length from where it e...

Страница 8: ...installed to the wall sleeve extension 5 Continue wall sleeve installation according to instructions on page 10 11 Preparing Unit for Installation Note first install the louver frame following steps 1...

Страница 9: ...two 2 5 32 pilot holes for the mounting screws These holes can be located using the drain kit as a pattern 4 Assemble the drain kit as shown in Figure 10 and securely fasten it to the wall sleeve with...

Страница 10: ...base The rear face of the cabinet should be recessed from the outside edge of the louver frame by the depth of the louver to be installed see Figure 12 4 Level the subbase with leveling bolts provided...

Страница 11: ...bubble to the outside secure it and the louver frame to the wall with screws driven through the sides and top of the room cabinet wall sleeve outward through the louver frame Never secure the frame t...

Страница 12: ...s Report any shipping damage to the carrier immediately 2 Check the interior of the installed room cabinet wall sleeve Clean out any dirt or debris that may have accumulated If Replacement chassis is...

Страница 13: ...equipment leaves the McQuay factory it may become damaged or maladjusted during transportation or on the job Sometimes wires are disconnected accidentally or fan motors move on their bases due to roug...

Страница 14: ...er Air Free of Obstruction Cycle Continuous Fan if so equipped Other Conditions Found ___________________________________________________________ ______________________________________________________...

Страница 15: ...tP Touchpad Control t Time Ts Temperature Setpoint Rf Room Freeze Condition CF Coil Freeze Protection F Fahrenheit C Celsius LC Control Lockout Mode Remote Thermostat Control The Remote Thermostat ca...

Страница 16: ...trol shall start with the last settings used prior to power down These settings are saved in a non volatile memory Factory set mode is OFF On Off Triggering Control can be turned On Off via LUI Remote...

Страница 17: ...d Controls Standard Digital Touchpad Control Modes of Operation Cool Mode In Cool Mode the compressor will start if the temperature at the space temperature sensor is 1 F or higher than the set point...

Страница 18: ...perature differential between the room temperature and the set point is less than 2 F This will also occur after a Cold Start or a Mode change from Cool to Cool Dry During this time the fan will opera...

Страница 19: ...tion will be deactivated by Power on reset or by pressing any button on the Touchpad except Sleep 4 Fan Mode In the Fan Mode the fan will operate continuously at the user s speed setting The compresso...

Страница 20: ...fan can be started only if the following conditions are met 1 after the 3 minute delay on break AND 2 the indoor coil reaches 49 F or above and remains there for at least 1 minute OR 3 another Mode is...

Страница 21: ...76mm or 4 102mm height and can be furnished with factory mounted fused disconnect option 3 On all 265V models an electrical subbase is required The chassis is supplied with a short cord which is just...

Страница 22: ...ey are of 560 Ohm and 3W value These resistors are meant to load thermostat solid state outputs in order for the output voltage to be either 0 or 24VAC i e no floating voltage These resistors are conn...

Страница 23: ...by pressing Mode button 2 1 Once in the configuration mode the default temperature scale will be displayed as shown below Toggle the temperature scale to degree Celsius by pressing either or button 2...

Страница 24: ...e thermostat for each period of the day repeat steps 3 3 through 3 7 Further the thermostat can be programmed for each individual day of the week or use the SimplesetTM feature as described below 3 9...

Страница 25: ...ackup SC2001 Temperature Control Ranges 45o F to 90o F Accuracy 1o F System Configurations 1 stage heat 1 stage cool or single stage electric heat pump Terminations R C W Y O B G Specifications Electr...

Страница 26: ...s There are two basic types of thermostats manufactured today those with relay contacts and those with solid state triacs If you open the thermostat and don t see relays then you can assume it to be s...

Страница 27: ...ement are as follows 1 When wiring the low voltage plug and receptacle disconnect provide enough wire to move harness out of the way for chassis removal Remote Wall Mounted Thermostats 2 If subbase is...

Страница 28: ...e room temperature 3 Jumper Placement to Select Controller Type A Place jumper across LUI to select unit mounted touchpad Local User Interface B Place jumper across secondary SEC to select secondary c...

Страница 29: ...door Fan Motor OCS Outdoor Coil Sensor OAS Outdoor Air Sensor ICS Indoor Coil Sensor IAS Indoor Air Sensor LUI Local User Interface REV Reversing Valve EHC Eletric Heat Contactor 1 Jumper Placement to...

Страница 30: ...the premium control board For the latest drawing version refer to the wiring diagram located on the inside of the controls access panel of the unit Wire Color Voltage WH 120V RD 208V OR 240V BN 277V...

Страница 31: ...emium control board For the latest drawing version refer to the wiring diagram located on the inside of the controls access panel of the unit Wire Color Voltage WH 120V RD 208V OR 240V BN 277V Drawing...

Страница 32: ...With proper care the unit should provide uninterrupted service for many years Scheduled maintenance of this equipment as described below is the key to the equipment s longevity A Air filters must be c...

Страница 33: ...t of the system A further advantage is that a failed part can be quickly and easily replaced thus minimizing the inoperative time of the equipment This is so however only if a replacement part is quic...

Страница 34: ...t LA Low Ambient Lockout Outdoor air temperature is below 35 F Fault and Protection Codes for Applied PTAC PTHP Control Board Fault code Description Cause for the fault LC Control Lockout Displays for...

Страница 35: ...Obstructed discharge grilles 5 Evaporator blower motor not running 6 Evaporator blower motor not up to speed 7 Evaporator motor slipping on motor shaft d Heat load in room exceeds capacity of equipme...

Страница 36: ...Noise will disappear after equipment runs awhile e Make necessary adjustments to components f Check for proper adjustment Apply silicone oil or grease to gap between solenoid and armature g Tighten h...

Страница 37: ...ged 129 5 137 0 137 9 145 6 145 6 PDHE Chassis 116 0 123 5 124 4 132 1 PDAE Chassis 114 5 122 0 122 9 130 6 130 6 Louvers Flush stamped 6 lbs 3kg Architectural 8 lbs 3kg Subbase 3 76mm High Electrical...

Страница 38: ...m and click on training or call 540 248 9646 and ask for the Training Department Warranty All McQuay equipment is sold pursuant to its standard terms and conditions of sale including Limited Product W...

Отзывы: