For Heat Pump Models
By means of pressure readings :
PRESSURE PROBABLE
CAUSE
Data
Circuit
T
o
o
Low
A Little
Low
Nor
m
al
A Little
High
T
o
o
High
High Side
Low Side
1. Overcharged with refrigerant.
2. Non-condensable gases in refrigerant circuit (e.g. oil).
3. Obstructed air-intake/discharge.
4. Short circuiting of hot air at outdoor unit.
High Side
Low Side
1. Poor compression/no compression (compressor defective.)
2. Check valve stick in open position.
3. Reversing valve leaking.
High Side
Low Side
1. Undercharged with refrigerant.
2. Refrigerant leakage.
3. Air filter clogged/dirty (indoor unit).
4. Indoor fan locked (Cooling).
5. Defective defrost control, outdoor coil freeze up (heating).
6. Outdoor fan locked (heating).
High Side
Low Side
1. Outdoor fan blocked (cooling).
2. Outdoor coil dirty (cooling).
3. Indoor fan locked (heating).
4. Indoor filter clogged/dirty (heating).
5. Non-condensable gases in refrigerant circuit (e.g. air)
High Side
Low Side
1. Air intake temperature of indoor unit too high.
By Means Of Diagnosis Flow Chart
Generally, there are two kind of problems, i.e. starting failure and insufficient cooling/heating. "Starting Failure" is
caused by electrical defect while "Insufficient Cooling/Heating" is caused by improper application or defects in
refrigerant circuit
.
No Cooling / Heating
Unit fail to start
Check power supply
- voltage
- phase
- frequency
Check settings of remote control box
Compressor fails to start
Check circuit breaker & fuse
Check power source cord
Fan fails to start
Fan Motor Capacitor defective
Loose Connections,
Contactors
Irregular motor resistance (
Ω
)
& insulation (M
Ω
)
Replace Fan Motor
Compressor Motor damaged ( to replace compressor)
Thermostat setting too high
Protection Device Actuated
Reset
Compressor locked (to replace compressor)
Voltage supply not within range
Check motor resistance (
Ω
) and insulation (M
Ω
)
Compressor
Capacitor Defective
Loose Connections,
Improper wiring
Regular but fails
to start
Irregular
i) Diagnosis of Electric Circuit
Page 85
Содержание MCM 020 D
Страница 21: ...Refrigerant Circuit MODEL MCM020D MLC M4LC020B MODEL MCM025D MLC M4LC025B MCM030D M4LC030B Page 20...
Страница 23: ...MODEL MCM020DR MLC M4LC020BR MODEL MCM025DR MLC M4LC025BR MCM030DR MLC030BR Page 22...
Страница 41: ...MODEL MLC M4LC061 C CR Page 40...
Страница 42: ...Wiring Diagrams COOLING ONLY INDOOR UNIT MODEL MCM020 025D OUTDOOR UNIT MODEL MLC M4LC020 025B Page 41...
Страница 43: ...INDOOR UNIT MODEL MCM030D OUTDOOR UNIT MODEL MLC030B Page 42...
Страница 44: ...INDOOR UNIT MODEL MCM030D OUTDOOR UNIT MODEL MLC M4LC030C Page 43...
Страница 45: ...INDOOR UNIT MODEL MCM040D OUTDOOR UNIT MODEL MLC035C Page 44...
Страница 46: ...INDOOR UNIT MODEL MCM040 050D OUTDOOR UNIT MODEL MLC M4LC040 050C Page 45...
Страница 47: ...INDOOR UNIT MODEL MCM061 062C OUTDOOR UNIT MODEL M4LC060C Page 46...
Страница 48: ...INDOOR UNIT MODEL MCM061 062C OUTDOOR UNIT MODEL MLC M4LC061C Page 47...
Страница 49: ...HEAT PUMP INDOOR UNIT MODEL MCM020 025DR OUTDOOR UNIT MODEL MLC M4LC020 025BR Page 48...
Страница 50: ...INDOOR UNIT MODEL MCM030DR OUTDOOR UNIT MODEL MLC030BR Page 49...
Страница 51: ...INDOOR UNIT MODEL MCM030DR OUTDOOR UNIT MODEL MLC M4LC030CR Page 50...
Страница 52: ...INDOOR UNIT MODEL MCM040DR OUTDOOR UNIT MODEL MLC035CR Page 51...
Страница 53: ...INDOOR UNIT MODEL MCM040 050DR OUTDOOR UNIT MODEL MLC M4LC040 050CR Page 52...
Страница 54: ...INDOOR UNIT MODEL MCM061 062CR OUTDOOR UNIT MODEL MLC M4LC061CR Page 53...
Страница 55: ...INDOOR UNIT MODEL MCM061 062CR OUTDOOR UNIT MODEL MLC M4LC060CR Page 54...
Страница 61: ...LOW AMBIENT UNIT OPTIONAL OUTDOOR UNIT MODEL MLC010B 015B 50HZ OUTDOOR UNIT MODEL MLC020B 025B 50HZ Page 60...
Страница 63: ...SINGLE PHASE FOR 4HP OUDOOT UNIT MODEL MLC M4LC040C COOLING ONLY MODEL MLC M4LC040CR HEATPUMP Page 62...
Страница 68: ...MCM061 062C Figure C Provide the installation space as shown in Figure D MCM D MCM061 062C Figure D Page 67...
Страница 94: ...2004 McQuay International 1 800 432 1342 www mcquay com ISO 9002 REGISTERED...