Special Precautions for R407
Special Precautions When Dealing With Refrigerant R407C Unit
1) What is new refrigerant R407C?
R407C is a zeotropic refrigerant mixture which has Zero Ozone Depletion Potential (ODP = 0) and thus
conformed to the Montreal Protocol regulation. It requires Polyol-ester oil (POE) oil for its compressor's
lubricant. Its refrigerant capacity and performance are about the same as the refrigerant R22.
2) Components
Mixture weight composition R32(23%), R125(25%), R134a(52%)
3) Characteristic
•
R407C liquid and vapor components have different compositions when the fluid evaporates or
condenses. Hence, when leak occurs and only vapor leaks out, the composition of the refrigerant
mixture left in the system will change and subsequently affect the system performance.
DO NOT
add
new refrigerant to leaked system. It is recommended that the system should be evacuated thoroughly
before recharging with R407C.
•
When refrigerant R407C is used, the composition will differ depending on whether it is in gaseous or
liquid phase. Hence when charging R407C, ensure that only liquid is being withdrawn from the cylinder
or can. This is to make certain that only original composition of R407C is being charged into the
system.
•
POE oil is used as lubricant for R407C compressor, which is different from the mineral oil used for R22
compressor. Extra precaution must be taken not to expose the R407C system too long to moist air.
4) Check list before installation/servicing
•
Tubing
Refrigerant R407C is more easily affected by dust of moisture compared with R22, make sure to
temporarily cover the ends of the tubing prior to installation
•
Compressor
oil
No additional charge of compressor oil is permitted.
•
Refrigerant
No other refrigerant other that R407C
•
Tools
Tools specifically for R407C only (must not be used for R22 or other refrigerant)
i)
Manifold gauge and charging hose
ii)
Gas leak detector
iii)
Refrigerant cylinder/charging cylinder
iv)
Vacuum pump c/w adapter
v)
Flare tools
vi)
Refrigerant recovery machine
5) Handling and installation guidelines
Like R22 system, the handling and installation of R407C system are closely similar. All precautionary
measures; such as ensuring no moisture, no dirt or chips in the system, clean brazing using nitrogen, and
thorough leak check and vacuuming are equally important requirements. However, due to zeotropic nature
of R407C and its hydroscopic POE oil, additional precautions must be taken to ensure optimum and
trouble-free system operation.
a) Filter-dryer must be installed along the liquid line for all R407C air conditioners. This is to minimise the
contamination of moisture and dirt in the refrigerant system. Filter-dryer must be of molecular sieve
type. For a heat-pump system, install a two-way flow filter dryer along the liquid line.
b) During installation or servicing, avoid prolong exposure of the internal part of the refrigerant system to
moist air. Residual POE oil in the piping and components can absorb moisture from the air.
Page 63
Содержание MCM 020 D
Страница 21: ...Refrigerant Circuit MODEL MCM020D MLC M4LC020B MODEL MCM025D MLC M4LC025B MCM030D M4LC030B Page 20...
Страница 23: ...MODEL MCM020DR MLC M4LC020BR MODEL MCM025DR MLC M4LC025BR MCM030DR MLC030BR Page 22...
Страница 41: ...MODEL MLC M4LC061 C CR Page 40...
Страница 42: ...Wiring Diagrams COOLING ONLY INDOOR UNIT MODEL MCM020 025D OUTDOOR UNIT MODEL MLC M4LC020 025B Page 41...
Страница 43: ...INDOOR UNIT MODEL MCM030D OUTDOOR UNIT MODEL MLC030B Page 42...
Страница 44: ...INDOOR UNIT MODEL MCM030D OUTDOOR UNIT MODEL MLC M4LC030C Page 43...
Страница 45: ...INDOOR UNIT MODEL MCM040D OUTDOOR UNIT MODEL MLC035C Page 44...
Страница 46: ...INDOOR UNIT MODEL MCM040 050D OUTDOOR UNIT MODEL MLC M4LC040 050C Page 45...
Страница 47: ...INDOOR UNIT MODEL MCM061 062C OUTDOOR UNIT MODEL M4LC060C Page 46...
Страница 48: ...INDOOR UNIT MODEL MCM061 062C OUTDOOR UNIT MODEL MLC M4LC061C Page 47...
Страница 49: ...HEAT PUMP INDOOR UNIT MODEL MCM020 025DR OUTDOOR UNIT MODEL MLC M4LC020 025BR Page 48...
Страница 50: ...INDOOR UNIT MODEL MCM030DR OUTDOOR UNIT MODEL MLC030BR Page 49...
Страница 51: ...INDOOR UNIT MODEL MCM030DR OUTDOOR UNIT MODEL MLC M4LC030CR Page 50...
Страница 52: ...INDOOR UNIT MODEL MCM040DR OUTDOOR UNIT MODEL MLC035CR Page 51...
Страница 53: ...INDOOR UNIT MODEL MCM040 050DR OUTDOOR UNIT MODEL MLC M4LC040 050CR Page 52...
Страница 54: ...INDOOR UNIT MODEL MCM061 062CR OUTDOOR UNIT MODEL MLC M4LC061CR Page 53...
Страница 55: ...INDOOR UNIT MODEL MCM061 062CR OUTDOOR UNIT MODEL MLC M4LC060CR Page 54...
Страница 61: ...LOW AMBIENT UNIT OPTIONAL OUTDOOR UNIT MODEL MLC010B 015B 50HZ OUTDOOR UNIT MODEL MLC020B 025B 50HZ Page 60...
Страница 63: ...SINGLE PHASE FOR 4HP OUDOOT UNIT MODEL MLC M4LC040C COOLING ONLY MODEL MLC M4LC040CR HEATPUMP Page 62...
Страница 68: ...MCM061 062C Figure C Provide the installation space as shown in Figure D MCM D MCM061 062C Figure D Page 67...
Страница 94: ...2004 McQuay International 1 800 432 1342 www mcquay com ISO 9002 REGISTERED...