c) Ensure that the compressor is not expose to open air for more than the recommended time specified by
its manufacturer (typically less than 10 minutes). Removed the seal-plugs only when the compressor is
about to be brazed.
d) The system should be thoroughly vacuumed to 1.0 Pa (-700mmHg) or lower. This vacuuming level is
more stringent than R22 system so as to ensure no incompressible gas and moisture in the system.
e) When charging R407C, ensure that only liquid is being withdrawn from the cylinder or can. This is to
ensure that only the original composition of R407C is being delivered into the system. The liquid
composition can be different from the vapor composition.
33% / 33% / 34%
23% / 25% / 52%
R32/R125/R134
Composition of R407C in vapour phase
is different from liquid phase.
f) Normally, the R407C cylinder or can is being equipped with a dip-pipe for liquid withdrawal. However, if
the dip-pipe is not available, invert the cylinder or can so as to withdraw liquid from the valve at the
bottom.
Liquid
withdrawal
Invert cylinder
without dip-pipe
Dip-pipe
g) When servicing leak, the top-up method, commonly practiced for R22 system, is not recommended for
R407C system. Unlike R22 where the refrigerant is of a single component, the composition of R407C,
which made-up of three different components, may have changed during the leak. Consequently, a
top-up may not ensure that the R407C in the system is of original composition. This composition shift
may adversely affect the system performance. It is recommended that the system should be evacuated
thoroughly before recharging with R407C.
Page 64
Содержание MCM 020 D
Страница 21: ...Refrigerant Circuit MODEL MCM020D MLC M4LC020B MODEL MCM025D MLC M4LC025B MCM030D M4LC030B Page 20...
Страница 23: ...MODEL MCM020DR MLC M4LC020BR MODEL MCM025DR MLC M4LC025BR MCM030DR MLC030BR Page 22...
Страница 41: ...MODEL MLC M4LC061 C CR Page 40...
Страница 42: ...Wiring Diagrams COOLING ONLY INDOOR UNIT MODEL MCM020 025D OUTDOOR UNIT MODEL MLC M4LC020 025B Page 41...
Страница 43: ...INDOOR UNIT MODEL MCM030D OUTDOOR UNIT MODEL MLC030B Page 42...
Страница 44: ...INDOOR UNIT MODEL MCM030D OUTDOOR UNIT MODEL MLC M4LC030C Page 43...
Страница 45: ...INDOOR UNIT MODEL MCM040D OUTDOOR UNIT MODEL MLC035C Page 44...
Страница 46: ...INDOOR UNIT MODEL MCM040 050D OUTDOOR UNIT MODEL MLC M4LC040 050C Page 45...
Страница 47: ...INDOOR UNIT MODEL MCM061 062C OUTDOOR UNIT MODEL M4LC060C Page 46...
Страница 48: ...INDOOR UNIT MODEL MCM061 062C OUTDOOR UNIT MODEL MLC M4LC061C Page 47...
Страница 49: ...HEAT PUMP INDOOR UNIT MODEL MCM020 025DR OUTDOOR UNIT MODEL MLC M4LC020 025BR Page 48...
Страница 50: ...INDOOR UNIT MODEL MCM030DR OUTDOOR UNIT MODEL MLC030BR Page 49...
Страница 51: ...INDOOR UNIT MODEL MCM030DR OUTDOOR UNIT MODEL MLC M4LC030CR Page 50...
Страница 52: ...INDOOR UNIT MODEL MCM040DR OUTDOOR UNIT MODEL MLC035CR Page 51...
Страница 53: ...INDOOR UNIT MODEL MCM040 050DR OUTDOOR UNIT MODEL MLC M4LC040 050CR Page 52...
Страница 54: ...INDOOR UNIT MODEL MCM061 062CR OUTDOOR UNIT MODEL MLC M4LC061CR Page 53...
Страница 55: ...INDOOR UNIT MODEL MCM061 062CR OUTDOOR UNIT MODEL MLC M4LC060CR Page 54...
Страница 61: ...LOW AMBIENT UNIT OPTIONAL OUTDOOR UNIT MODEL MLC010B 015B 50HZ OUTDOOR UNIT MODEL MLC020B 025B 50HZ Page 60...
Страница 63: ...SINGLE PHASE FOR 4HP OUDOOT UNIT MODEL MLC M4LC040C COOLING ONLY MODEL MLC M4LC040CR HEATPUMP Page 62...
Страница 68: ...MCM061 062C Figure C Provide the installation space as shown in Figure D MCM D MCM061 062C Figure D Page 67...
Страница 94: ...2004 McQuay International 1 800 432 1342 www mcquay com ISO 9002 REGISTERED...