(6) Additional Charge
•
The refrigerant gas has already charged into the outdoor unit. For the piping length of 5m. Additional
refrigerant charge after vacuuming is not necessary.
•
When the piping length is more than 5m, please use the table below (unit in gram).
MODEL 7m 10m 15m 20m 35m
020D/ 020DR
30/50
75/125 150/250 225/375
-
025D/ 025DR
76/100
190/250 380/500 570/750
-
030D/
030DR
100 250 500 750 1500
040D/
040DR
100 250 500 750 1500
050D/
050DR
100 250 500 750 1500
061C/CR 220
550 1100 1650 3300
Diagram shows typical charging method.
CAUTION FOR R407C
Avoid prolong exposure of an opened compressor, or the internal part of refrigerant piping to moist air.
The POE oil in the compressor and piping can absorb moisture
from air.
(7) Overall Checking
•
•
•
•
Ensure the following, in particular :
1) The unit is mounted solidly and rigid in position.
2) Piping and connections are leak proof after charging.
3) Proper wiring has been done.
Drainage check - pour some water into drain pan.
Test
run
1) Conduct a test run after water drainage test and gas leakage test.
2) Watch out for the following :
a) Is the electric plug firmly inserted into the socket?
b) Is there any abnormal sound from unit?
c) Is there any abnormal vibration with regard to unit itself or piping?
d) Is there smooth drainage of water?
Check that :
1) Outdoor fan is running, with warm air blowing off the outdoor unit (cooling cycle).
2) Indoor blower is running and discharge cool air (cooling cycle).
3) Suction (low side) pressure is as per recommendations.
4) The remote controller has incorporated a 3 minutes delay in the circuit. Thus, it requires about 3
minutes before the outdoor unit can start up.
Page 73
Содержание MCM 020 D
Страница 21: ...Refrigerant Circuit MODEL MCM020D MLC M4LC020B MODEL MCM025D MLC M4LC025B MCM030D M4LC030B Page 20...
Страница 23: ...MODEL MCM020DR MLC M4LC020BR MODEL MCM025DR MLC M4LC025BR MCM030DR MLC030BR Page 22...
Страница 41: ...MODEL MLC M4LC061 C CR Page 40...
Страница 42: ...Wiring Diagrams COOLING ONLY INDOOR UNIT MODEL MCM020 025D OUTDOOR UNIT MODEL MLC M4LC020 025B Page 41...
Страница 43: ...INDOOR UNIT MODEL MCM030D OUTDOOR UNIT MODEL MLC030B Page 42...
Страница 44: ...INDOOR UNIT MODEL MCM030D OUTDOOR UNIT MODEL MLC M4LC030C Page 43...
Страница 45: ...INDOOR UNIT MODEL MCM040D OUTDOOR UNIT MODEL MLC035C Page 44...
Страница 46: ...INDOOR UNIT MODEL MCM040 050D OUTDOOR UNIT MODEL MLC M4LC040 050C Page 45...
Страница 47: ...INDOOR UNIT MODEL MCM061 062C OUTDOOR UNIT MODEL M4LC060C Page 46...
Страница 48: ...INDOOR UNIT MODEL MCM061 062C OUTDOOR UNIT MODEL MLC M4LC061C Page 47...
Страница 49: ...HEAT PUMP INDOOR UNIT MODEL MCM020 025DR OUTDOOR UNIT MODEL MLC M4LC020 025BR Page 48...
Страница 50: ...INDOOR UNIT MODEL MCM030DR OUTDOOR UNIT MODEL MLC030BR Page 49...
Страница 51: ...INDOOR UNIT MODEL MCM030DR OUTDOOR UNIT MODEL MLC M4LC030CR Page 50...
Страница 52: ...INDOOR UNIT MODEL MCM040DR OUTDOOR UNIT MODEL MLC035CR Page 51...
Страница 53: ...INDOOR UNIT MODEL MCM040 050DR OUTDOOR UNIT MODEL MLC M4LC040 050CR Page 52...
Страница 54: ...INDOOR UNIT MODEL MCM061 062CR OUTDOOR UNIT MODEL MLC M4LC061CR Page 53...
Страница 55: ...INDOOR UNIT MODEL MCM061 062CR OUTDOOR UNIT MODEL MLC M4LC060CR Page 54...
Страница 61: ...LOW AMBIENT UNIT OPTIONAL OUTDOOR UNIT MODEL MLC010B 015B 50HZ OUTDOOR UNIT MODEL MLC020B 025B 50HZ Page 60...
Страница 63: ...SINGLE PHASE FOR 4HP OUDOOT UNIT MODEL MLC M4LC040C COOLING ONLY MODEL MLC M4LC040CR HEATPUMP Page 62...
Страница 68: ...MCM061 062C Figure C Provide the installation space as shown in Figure D MCM D MCM061 062C Figure D Page 67...
Страница 94: ...2004 McQuay International 1 800 432 1342 www mcquay com ISO 9002 REGISTERED...