Refrigerant Piping Work
Refrigerant piping is important in particular. Refrigeration cycle of the split air
conditioner is realized by the perfect piping work.
Piping Length and Elevation
If the piping is too long, both the capacity and reliability of the unit will drop. As the number of bends
increase, resistance to flow of refrigerant increases, thus lowering the cooling capacity and as a result
overloading the compressor which may cause the compressor to become defective. Always choose the
shortest path and follow the recommendation as tabulated below.
Indoor
MCK015B/BR
MCK020A/AR
MCK020B/BR
MCK025A/AR
MCK025B/BR
MCK030A/AR
MCK030B/BR
MCK040A/AR MCK050A/AR
Model
Outdoor
MLC/ M4LC
015B/BR
MLC/M4LC
020B/BR
MLC/ M4LC
025B/BR
MLC030B/BR
MLC/ M4LC
030C/CR
MLC035C/CR
MLC/ M4LC
040C/CR
MLC/ M4LC
050C/CR
Max. length (m)
10 15 15 15 35 35 35 35
Max. elevation (m)
5 8 8 8 15
15
15
15
Max. no. of bends
10 10 10 10 10 10 10 10
Liquid pipe size
1/4" 1/4" 3/8’’ 3/8’’ 3/8’’ 3/8" 3/8" 3/8’’
Gas pipe size
1/2” 5/8” 5/8’’ 5/8’’ 5/8’’ 3/4'’ 3/4'’ 3/4'’
Indoor MCK010C/CR MCK015C/CR MCK020C/CR
Model
Outdoor MLC00B/BR MLC015B/BR MLC020B/BR
Max. length (m)
12
12
15
Max. elevation (m)
5
5
8
Max. no. of bends
10
10
10
Liquid pipe size
1/4"
1/4"
1/4"
Gas pipe size
3/8"
3/8"
5/8"
Remark: The refrigerant pre-charged in the outdoor unit is for piping length up to 7.62m
Piping Connection
Do not use contaminated or damaged copper tubing. If piping for evaporator or condenser are exposed or
had been opened for 15 seconds or more, vacuum and purge with field supplied refrigerant. Generally, do
not remove plastic, rubber plugs and brass nuts from valves, fittings, tubing and coils until it is ready to do
the connection for suction and liquid line.
If any brazing work is required, ensure that nitrogen gas is passed through coil and joints while brazing work
is being carried out. This will eliminate soot formation on the inside wall of copper tubing.
Cut the pipe stage by stage, advance the blade of pipe cutter slowly. Extra force and deep cut will cause
more distortion of pipe and therefore produce extra burr.
Remove burrs from cut edges of pipes with a remover. This will avoid unevenness on the flare face which
will cause gas leak.
Align the center of the piping and sufficiently tighten the flare nut with fingers. Finally, tighten the flare nut
with torque wrench until the wrench clicks.
Be sure to execute heat insulation (polyurethane form with thickness more than 15 mm).
Except the outdoor unit which is pre-charged with refrigerant, the indoor unit and the refrigerant connection
pipes must be purged because the air that contain moisture remaining in the refrigerant cycle may cause
malfunction to the compressor.
Additional Charge
The refrigerant is pre-charged in the outdoor unit, but additional charge of refrigerant after vacuuming is
necessary. Follow the recommendation as tabulated below.
78
Содержание MCK 010C
Страница 19: ...CK20B BR NC Curves CK15B BR NC Curves 18...
Страница 20: ...CK30B BR NC Curves CK25B BR NC Curves 19...
Страница 44: ...Outdoor Unit MLC030 040 050C CR M4LC030 040 050C CR 43...
Страница 46: ...Indoor Unit Cooling Only Model MCK030A Outdoor Unit Model MLC030B 45...
Страница 47: ...Indoor Unit Cooling Only Model MCK030A Outdoor Unit Model MLC M4LC030C 46...
Страница 48: ...Indoor Unit Cooling Only Model MCK040A Outdoor Unit Model MLC035C 47...
Страница 49: ...Indoor Unit Cooling Only Model MCK040 050A Outdoor Unit Model MLC M4LC040 050C 48...
Страница 51: ...Indoor Unit Heat Pump Model MCK030AR Outdoor Unit Model MLC030BR 50...
Страница 52: ...Indoor Unit Heat Pump Model MCK030AR M4LC030CR Outdoor Unit Model MLC 51...
Страница 53: ...Indoor Unit Heat Pump Model MCK040AR Outdoor Unit Model MLC035CR 52...
Страница 54: ...Indoor Unit Heat Pump Model MCK040 050AR Outdoor Unit Model MLC M4LC040 050CR 53...
Страница 55: ...Indoor Unit Cooling Only Model MCK015B Outdoor Unit Model MLC015B 54...
Страница 56: ...Indoor Unit Cooling Only Model MCK020 025B Outdoor Unit Model MLC020 025B 55...
Страница 57: ...Indoor Unit Cooling Only Model MCK030B Outdoor Unit Model MLC030C 56...
Страница 58: ...Indoor Unit Cooling Only Model MCK030B Outdoor Unit Model MLC030B 57...
Страница 59: ...Indoor Unit Heat Pump Model MCK015BR Outdoor Unit Model MLC015BR 58...
Страница 60: ...Indoor Unit Heat Pump Model MCK020 025BR Outdoor Unit Model MLC020 025BR 59...
Страница 61: ...Indoor Unit Heat Pump Model MCK030BR Outdoor Unit Model MLC030BR 60...
Страница 62: ...Indoor Unit Heat Pump Model MCK030BR Outdoor Unit Model MLC030CR 61...
Страница 63: ...Indoor Unit Cooling Only Model MCK010 015C Outdoor Unit Model MLC010 015B 62...
Страница 64: ...Indoor Unit Cooling Only Model MCK020C Outdoor Unit Model MLC020B 63...
Страница 67: ...Model MLC M4LC020 025BR Heat Pump 3 Phase 50HZ 380 415V Model MLC M4LC030CR Heat Pump 3 Phase 50HZ 380 415V 66...
Страница 70: ...Low Ambient Unit Optional Outdoor Unit Model MLC010B 015B 50HZ Outdoor Unit Model MLC020B 025B 50HZ 69...
Страница 72: ...Single Phase for 4HP Outdoor Unit Model MLC M4LC040C Cooling Only Model MLC M4LC040CR Heat Pump 71...
Страница 100: ...Fresh Air Kit for MCK C Models 99...
Страница 101: ...2004 McQuay International 1 800 432 1342 www mcquay com ISO 9002 REGISTERED...