c) Ensure that the compressor is not exposed to open air for more than the recommended time
specified by its manufacturer (typically less than 10 minutes). Removed the seal-plugs only when the
compressor is about to be brazed.
d) The system should be thoroughly vacuumed to 1.0 Pa (-700mmHg) or lower. This vacuuming level is
more stringent than R22 system so as to ensure no incompressible gas and moisture in the system.
e) When charging R407C, ensure that only liquid is being withdrawn from the cylinder or can. This is to
ensure that only the original composition of R407C is being delivered into the system. The liquid
composition can be different from the vapor composition.
23% / 25% / 52%
33% / 33% / 34%
R32/R125/R134
Composition of R407C in vapor
phase is different from liquid phase.
f) Normally, the R407C cylinder or can is being equipped with a dip-pipe for liquid withdrawal. However, if
the dip-pipe is not available, invert the cylinder or can so as to withdraw liquid from the valve at the
bottom.
Liquid
withdrawal
Invert cylinder
without dip-pipe
Dip-pipe
g) When servicing leak, the top-up method, commonly practiced for R22 system, is not recommended for
R407C system. Unlike R22 where the refrigerant is of a single component, the composition of R407C,
which made-up of three different components, may have changed during the leak. Consequently, a
top-up may not ensure that the R407C in the system is of original composition. This composition shift
may adversely affect the system performance. It is recommended that the system should be evacuated
thoroughly before recharging with R407C.
73
Содержание MCK 010C
Страница 19: ...CK20B BR NC Curves CK15B BR NC Curves 18...
Страница 20: ...CK30B BR NC Curves CK25B BR NC Curves 19...
Страница 44: ...Outdoor Unit MLC030 040 050C CR M4LC030 040 050C CR 43...
Страница 46: ...Indoor Unit Cooling Only Model MCK030A Outdoor Unit Model MLC030B 45...
Страница 47: ...Indoor Unit Cooling Only Model MCK030A Outdoor Unit Model MLC M4LC030C 46...
Страница 48: ...Indoor Unit Cooling Only Model MCK040A Outdoor Unit Model MLC035C 47...
Страница 49: ...Indoor Unit Cooling Only Model MCK040 050A Outdoor Unit Model MLC M4LC040 050C 48...
Страница 51: ...Indoor Unit Heat Pump Model MCK030AR Outdoor Unit Model MLC030BR 50...
Страница 52: ...Indoor Unit Heat Pump Model MCK030AR M4LC030CR Outdoor Unit Model MLC 51...
Страница 53: ...Indoor Unit Heat Pump Model MCK040AR Outdoor Unit Model MLC035CR 52...
Страница 54: ...Indoor Unit Heat Pump Model MCK040 050AR Outdoor Unit Model MLC M4LC040 050CR 53...
Страница 55: ...Indoor Unit Cooling Only Model MCK015B Outdoor Unit Model MLC015B 54...
Страница 56: ...Indoor Unit Cooling Only Model MCK020 025B Outdoor Unit Model MLC020 025B 55...
Страница 57: ...Indoor Unit Cooling Only Model MCK030B Outdoor Unit Model MLC030C 56...
Страница 58: ...Indoor Unit Cooling Only Model MCK030B Outdoor Unit Model MLC030B 57...
Страница 59: ...Indoor Unit Heat Pump Model MCK015BR Outdoor Unit Model MLC015BR 58...
Страница 60: ...Indoor Unit Heat Pump Model MCK020 025BR Outdoor Unit Model MLC020 025BR 59...
Страница 61: ...Indoor Unit Heat Pump Model MCK030BR Outdoor Unit Model MLC030BR 60...
Страница 62: ...Indoor Unit Heat Pump Model MCK030BR Outdoor Unit Model MLC030CR 61...
Страница 63: ...Indoor Unit Cooling Only Model MCK010 015C Outdoor Unit Model MLC010 015B 62...
Страница 64: ...Indoor Unit Cooling Only Model MCK020C Outdoor Unit Model MLC020B 63...
Страница 67: ...Model MLC M4LC020 025BR Heat Pump 3 Phase 50HZ 380 415V Model MLC M4LC030CR Heat Pump 3 Phase 50HZ 380 415V 66...
Страница 70: ...Low Ambient Unit Optional Outdoor Unit Model MLC010B 015B 50HZ Outdoor Unit Model MLC020B 025B 50HZ 69...
Страница 72: ...Single Phase for 4HP Outdoor Unit Model MLC M4LC040C Cooling Only Model MLC M4LC040CR Heat Pump 71...
Страница 100: ...Fresh Air Kit for MCK C Models 99...
Страница 101: ...2004 McQuay International 1 800 432 1342 www mcquay com ISO 9002 REGISTERED...