Special Precautions for R407C
Special precautions when dealing with refrigerant R407C unit
1) What is New Refrigerant R407C?
R407C is a zeotropic refrigerant mixture which has zero ozone depletion potential and thus conformed
to the Montreal Protocol regulation. It requires Polyol ester oil (POE) oil for its compressor's lubricant.
Its refrigerant capacity and performance are about the same as the refrigerant R22.
2) Components
Mixture weight composition R32(23%), R125(25%), R134a(52%)
3) Characteristic
•
R407C liquid and vapor components have different compositions when the fluid evaporates or
condenses. Hence, when leak occurs and only vapor leaks out, the composition of the refrigerant
mixture left in the system will change and subsequently affect the system performance. If just additional
refrigerant is added to leaked system, system performance will drop. It is recommended that the system
should be evacuated thoroughly before recharging with R407C.
•
When refrigerant R407C is used, the composition will differ depending on whether it is in gaseous or
liquid phase. Hence when charging R407C, ensure that only liquid is being withdrawn from the cylinder
or can. This is to make certain that only original composition of R407C is being charged into the
system.
•
POE oil is used as lubricant for R407C compressor, which is different from the mineral oil used for R22
compressor. Extra precaution must be taken not to expose the R407C system too long to moist air.
4) Check List Before Installation / Servicing
•
Tubing
Refrigerant R407C is more easily affected by dust of moisture compared with R22, make sure to
temporarily cover the ends of the tubing prior to installation
•
Compressor
oil
No additional charge of compressor oil is permitted.
•
Refrigerant
No other refrigerant other that R407C
•
Tools
Tools specifically for R407C only (must not be used for R22 or other refrigerant)
i)
Manifold gauge and charging hose
ii)
Gas leak detector
iii)
Refrigerant cylinder/charging cylinder
iv)
Vacuum pump c/w adapter
v)
Flare tools
vi)
Refrigerant recovery machine
5) Handling and Installation Guidelines
Like R22 system, the handling and installation of R407C system are closely similar. All precautionary
measures; such as ensuring no moisture, no dirt or chips in the system, clean brazing using nitrogen, and
thorough leak check and vacuuming are equally important requirements. However, due to zeotropic nature
of R407C and its hydroscopic POE oil, additional precautions must be taken to ensure optimum and
trouble-free system operation.
a) Filter-dryer must be installed along the liquid line for all R407C air conditioners. This is to minimise the
contamination of moisture and dirt in the refrigerant system. Filter-dryer must be of molecular sieve
type. For a heat-pump system, install a two-way flow filter dryer along the liquid line.
b) During installation or servicing, avoid prolong exposure of the internal part of the refrigerant system to
moist air. Residual POE oil in the piping and components can absorb moisture from the air.
72
Содержание MCK 010C
Страница 19: ...CK20B BR NC Curves CK15B BR NC Curves 18...
Страница 20: ...CK30B BR NC Curves CK25B BR NC Curves 19...
Страница 44: ...Outdoor Unit MLC030 040 050C CR M4LC030 040 050C CR 43...
Страница 46: ...Indoor Unit Cooling Only Model MCK030A Outdoor Unit Model MLC030B 45...
Страница 47: ...Indoor Unit Cooling Only Model MCK030A Outdoor Unit Model MLC M4LC030C 46...
Страница 48: ...Indoor Unit Cooling Only Model MCK040A Outdoor Unit Model MLC035C 47...
Страница 49: ...Indoor Unit Cooling Only Model MCK040 050A Outdoor Unit Model MLC M4LC040 050C 48...
Страница 51: ...Indoor Unit Heat Pump Model MCK030AR Outdoor Unit Model MLC030BR 50...
Страница 52: ...Indoor Unit Heat Pump Model MCK030AR M4LC030CR Outdoor Unit Model MLC 51...
Страница 53: ...Indoor Unit Heat Pump Model MCK040AR Outdoor Unit Model MLC035CR 52...
Страница 54: ...Indoor Unit Heat Pump Model MCK040 050AR Outdoor Unit Model MLC M4LC040 050CR 53...
Страница 55: ...Indoor Unit Cooling Only Model MCK015B Outdoor Unit Model MLC015B 54...
Страница 56: ...Indoor Unit Cooling Only Model MCK020 025B Outdoor Unit Model MLC020 025B 55...
Страница 57: ...Indoor Unit Cooling Only Model MCK030B Outdoor Unit Model MLC030C 56...
Страница 58: ...Indoor Unit Cooling Only Model MCK030B Outdoor Unit Model MLC030B 57...
Страница 59: ...Indoor Unit Heat Pump Model MCK015BR Outdoor Unit Model MLC015BR 58...
Страница 60: ...Indoor Unit Heat Pump Model MCK020 025BR Outdoor Unit Model MLC020 025BR 59...
Страница 61: ...Indoor Unit Heat Pump Model MCK030BR Outdoor Unit Model MLC030BR 60...
Страница 62: ...Indoor Unit Heat Pump Model MCK030BR Outdoor Unit Model MLC030CR 61...
Страница 63: ...Indoor Unit Cooling Only Model MCK010 015C Outdoor Unit Model MLC010 015B 62...
Страница 64: ...Indoor Unit Cooling Only Model MCK020C Outdoor Unit Model MLC020B 63...
Страница 67: ...Model MLC M4LC020 025BR Heat Pump 3 Phase 50HZ 380 415V Model MLC M4LC030CR Heat Pump 3 Phase 50HZ 380 415V 66...
Страница 70: ...Low Ambient Unit Optional Outdoor Unit Model MLC010B 015B 50HZ Outdoor Unit Model MLC020B 025B 50HZ 69...
Страница 72: ...Single Phase for 4HP Outdoor Unit Model MLC M4LC040C Cooling Only Model MLC M4LC040CR Heat Pump 71...
Страница 100: ...Fresh Air Kit for MCK C Models 99...
Страница 101: ...2004 McQuay International 1 800 432 1342 www mcquay com ISO 9002 REGISTERED...