52
Chilled Water Fan Coil Unit
Model
Board
Handset
WM 05 – 25FW, 301W
W1V3
CK 20 – 50AW/AWH
W1V3
CK 15 – 25BW
W1V3
CK 10 – 20CW
W1V3
CE 20 – 50DW/CBW
W1V3
CC 10 – 60CW
W1V3
SLM3 / Netware 3
SB 75 – 150BW
N/A
No Controller
Self Diagnostic Table – W1V3
Fault Indication
POWER LED / COOL LED
Other LEDs
Seven Segments
Room sensor missing
Blinks 4 times
FAN blinks
E1 blinking
Indoor coil sensor missing
Blinks 4 times
SLEEP blinks
E2 blinking
Pump fault
Blinks 2 times
COOL & FAN blink
E6 blinking
Pipe water temperature poor
Blinks 3 times
COOL & DRY blink
E4 blinking
Pipe water temperature fault
Blink 1 time
COOL blinks
E5 blinking
Model
Board
Handset
WM 07 – 25GW
W2
WM 301W
W2
CK 20 – 50AW/AWH
W2
CK 15 – 25BW
W2
CK 10 – 20CW
W2
CE 07 – 15CBW
W2
CE 20 – 50DW
W2
CE 15 – 25EW
W2
CC 10 – 60CW
W2
SLM3 / Netware 3
SB 75 – 150BW
N/A
No Controller
Self Diagnostic Table – W2
Fault Indication
COOOL LED
Seven Segments
Room sensor error (short/open)
Blink 1 time
E1
Pipe water sensor error (short/open)
Blink 2 times
E2
Water pump error
Blink 6 times
E6
Pipe water temperature fault
Blink 5 times
E5
Window open activated*
Blink 3 times
-
Antifreeze mode activated*
Blink 7 times
-
Load shedding activated*
Blink 8 times
-
*Applicable for 4 pipes applications only.
G7 / SLM3 / Netware 3
G7 / SLM3 / Netware 3
G7 / SLM3 / Netware 3
G7 / SLM3 / Netware 3
G7 / SLM3 / Netware 3
G11 / SLM3 / Netware 3
G7 / SLM3 / Netware 3
G7 / SLM3 / Netware 3
G7 / SLM3 / Netware 3
G7 / SLM3 / Netware 3
G7 / SLM3 / Netware 3
G7 / SLM3 / Netware 3
G11 / SLM3 / Netware 3
Содержание M4LC