51
Inverter Outdoor Unit
Model
SLX 10/15/20/25C/CR
MSV 25/35A
MSX 20/25/30A/AR
Normal running / compressor running RED LED blinking
No. of Blinks
Blinking Indication
1
Normal running, with no limitation
2
Voltage limit
3
Cooling unit: outdoor coil temperature limit
Heating unit: indoor coil temperature limit
4
Total current limit
5
Discharge temperature limit
6
Cooling unit: indoor coil temperature limit
7
Indoor fan control
8
Outdoor frequency adjustment
Compressor stopped RED LED blinking
No. of
Blinks
Faulty Indication
No. of
Blinks
Faulty Indication
1
Outdoor ambient sensor error
15
DC fan motor feedback error
2
Outdoor coil sensor error
16
AC peak current error
3
Outdoor discharge sensor error /
compressor overheat
17
Outdoor suction sensor error
4
DC compressor feedback error
18
None
5
Communication error
19
DC compressor speed control error
6
Over current error
20
None
7
No load
21
Outdoor suction pipe A sensor error
8
Over / under voltage
22
Outdoor suction pipe B sensor error
9
DC compressor start failure
23
Outdoor suction pipe C sensor error
10
Cooling overload
24
Outdoor suction pipe D sensor error
11
Defrost
31
Communication error with indoor A
12
IPM protection
32
Communication error with indoor B
13
Read EEPROM error
33
Communication error with indoor C
14
Write EEPROM error
34
Communication error with indoor D