Multiple Unit Control (up to 2 units) (P/N 106059801)

This multiple unit control board is an accessory used when 

you need to control up to 2-units from a single thermostat . 

The board is typically mounted in the unit control box closest 

to the thermostat . The “G”, “W”, “Y”, “C”, and “L” connections 

are short flying leads pre-attached to the board . A maximum 

of 3 boards may be used together if up to 4-units must be 

connected and controlled from a single thermostat .
This  version  of  the  board  uses  VDC  relays  and  should 

not  be  used  in  combination  with  any  other  accessories  

or equipment that require VAC connections to the “G”, “W1”, 

or  “Y1”  terminals  (i .e .  Boilerless  System  Kit) .  Do  not  use 

the  unoccupied  (U-terminal)  feature  with  the  multiple  unit 

control board .
The  multiple  unit  control  board  provides  the  components 

necessary  to  protect  the  Mark  IV/AC  board  from  electrical 

damage  that  may  occur  when  using  standard  off-the-shelf 

relays .

WSHP Mark IV/AC Board Low Voltage Terminal Strip

O W 2 G W1 Y1 F

E L

U A P V

R C

R

Y

G

W

L

G W1 Y1 R Rc C

Thermostat Terminals 

Multiple Unit 

Control Panel

O W 2 G W1 Y1 F

E L

U A P V

R C

G W Y

C L

WSHP Mark IV/AC Board Low Voltage Terminal Strip

WSHP Mark IV/AC Board Low Voltage Terminal Strip

O W2 G W1 Y1 F E L U A P V R C

1

2
3

Auxiliary Relay

Orange

Yellow

White

6 3 1

Ti

me Clock

(by others)

Daisy-chain to

additional Mark IV/AC

board “U” terminals

B

L

GN

Motorized Valve & Relay for Unit Sizes 007 thru 070

Wired as shown below the motorized valve will open on a 

call for compressor operation . Valves for unit sizes 007 to 

019 are 

1

2

" power-open spring-return while unit sizes 024 

to 070 are 

3

4

" power-open spring return . Other thermostat 

combinations  may  be  used .  Valve  and  auxiliary  relay  are 

purchased separately .

Note: The wiring shown below can only be used when the “P” 

terminal is not being used as a pump restart signal to other equip-

ment . If the “P” terminal must be used as a pump restart signal to 

other equipment, then wire the auxiliary relay’s yellow wire to “Y1”, 

white wire to “W1”, and orange wire to “C”, then the valve will 

open on a call for occupied heating or cooling from the thermostat .

6

3

1

Black to 6 

White to 1 

Plug

Pins,

Female

Conduit

Anti-Short

Bushing

Connector

Valve

36" (915 mm)

Lead Length

P/N 060977401 - 1/2" Motorized Valve Kit

P/N 060977301 - 3/4" Motorized Valve Kit

P/N 859004354 - Valve Relay Kit

Содержание Enfinity CCH series

Страница 1: ...Electrical Data 5 Piping 5 Cleaning Flushing System 6 Start up 7 Operating Limits 8 Typical Wiring Diagrams 9 11 Unit Operation 12 14 Thermostat Connections 16 17 Options for Mark IV AC Units 18 21 Fi...

Страница 2: ...eck the available ceiling height versus the height of the unit 6 Note the location and routing of water piping conden sate drain piping and electrical wiring The locations of these items are clearly m...

Страница 3: ...res 1A and 1B 6 When attaching the hanger rods to the unit a double nut is recommended since vibration could loosen a single nut The installer is responsible for providing the hex nuts when installing...

Страница 4: ...etween the conditioner discharge and the distribution diffusers Return air ducts can be brought in through a low side wall filter grille and then up through the stud pieces to a ceiling plenum or thro...

Страница 5: ...rmance and minimum sound requirements Fan sound levels and performance can be affected by external static pressure changed Disconnect and cap the red lead wire and inter change it with the orange lead...

Страница 6: ...ure 7 Figure 7 Supply return runouts connected together 2 Fill the system at the city water makeup connection with all air vents open After filling close all air vents The contractor should start main...

Страница 7: ...erature rise through the machine should not exceed 35 F 19 C If the air tempera ture exceeds 35 F 19 C then the water flow rate is inadequate 6 Check the elevation and cleanliness of the condensate li...

Страница 8: ...di tion It is assumed that such a start up is for the purpose of bringing the building space up to occupancy temperature temperature and or humidity and equipment performance reliability and service l...

Страница 9: ...ervice personnel should be observed or dam age to controller may result 5 Terminal block on Mark IV AC board provides 24 VAC at terminals R and C All other outputs are 24 VDC 6 Field supplied relays i...

Страница 10: ...is used transformer must be rewired by disconnecting the power lead from the red transformer primary wire and connecting the power lead to the orange transformer primary wire Place an insulation cap...

Страница 11: ...ce an insulation cap on the red transformer primary wire 2 All temperature and pressure switches are normally closed Notes 1 A 208 230V unit is factory wired for 208V operation If 230V power supply is...

Страница 12: ...ad ShedOff Off On Off Off Unoccupied Mode On On Off Off Unit Shutdown Off Flash Off On Page 12 IM 742 Unit Operation The Remote Reset feature provides the means to remotely reset automatic lockouts ge...

Страница 13: ...ts IM 742 Page 13 MicroTech 2000 WSHP Unit Controller MicroTech 2000 Unit Controller LED Indication Status LED State Mode On Continually Occupied Occupied Load Shed On 1 2 sec Off 5 1 2 sec Unoccupied...

Страница 14: ...operation Fan operation can be customized in software to run continuously during occupied mode or to cycle ON or OFF appropriately on a call for heating and cooling Cooling mode On a call for cooling...

Страница 15: ...operation the attained temperature does not meet the software configurable setpoint for heating or cooling as appropriate a software alarm occurs The alarm auto matically resets when the attained tem...

Страница 16: ...G Thermostat Terminals C R 7 Day Programmable Electronic Thermostat P N 107095901 Thermostat Connection Diagrams Mark IV AC Units Unit Sizes 007 070 Non Programmable Electronic Thermostat P N 66805420...

Страница 17: ...t Grn Red Wall Sensor Locate the sensor on a wall where exposure to unrestrict ed air circulation represents the average temperature of the space A common mistake is to mount the sensor too close to t...

Страница 18: ...e Mark IV AC board when using standard off the self relays The auxiliary relay can be used to provide fault signals unit operation signals or to provide a means for remote equipment to control the Mar...

Страница 19: ...Control Panel O W2 G W1 Y1 F E L U A P V R C G W Y C L WSHP Mark IV AC Board Low Voltage Terminal Strip WSHP Mark IV AC Board Low Voltage Terminal Strip O W2 G W1 Y1 F E L U A P V R C 1 2 3 Auxiliary...

Страница 20: ...Override Pot1 Boilerless System Board 43 Ohm 4 pin Plug Water Temperature Sensor Signal to remote duct heater control circuit F L W1 V Mark IV Board Terminals 9 66 245 mm 007 042 14 50 368 mm 048 060...

Страница 21: ...ter Controller Terminals Daisy chain to other Mark IV AC board P and C terminals 64 58 65 WSHP Mark IV AC Board Low Voltage Terminal Strip Circuit 1 Pump Restart Relay 7 6 5 4 3 2 1 O W2 G W1 Y1 F E L...

Страница 22: ...e WSHP chassis 24VAC Pilot Duty Relay by others Terminals Located on Microtech 2000 Auxiliary Board J6 24VAC Pilot Duty Relay by others Use contacts as needed for option Terminals Located on Microtech...

Страница 23: ...cessible to the end user For example HP LT and COF are not available for use by the end user Typically the Mark IV AC board s R 24vac terminal is used to drive the board s thermostat inputs and contro...

Страница 24: ...ing Check compressor wiring for defective wiring or loose connection Check thermostat for improper location Check for defective compressor internal windings with ohm meter Check for bad compressor cap...

Страница 25: ...and atmosphere pressure it can become com bustible under pressure when mixed with air NOTE R 410A should not be mixed with air under pressure for leak testing Pressure mixtures of dry nitrogen and R...

Страница 26: ...ng system to the air to refrigerant heat exchanger coil The liquid then evaporates becoming a gas at the same time absorbing heat and cooling the air passing over the surfaces of the coil The refriger...

Страница 27: ...een through the filter when held up to sunlight or a bright light it should be changed A more critical standard may be desirable 3 The condensate drain pan should be checked annually and cleaned and f...

Страница 28: ...to www mcquay com This document contains the most current product information as of this printing For the most up to date product information please go to www mcquay com Products Manufactured in an I...

Отзывы: