McQuay Enfinity CCH series Скачать руководство пользователя страница 12

  The Mark IV/AC circuit board is an optional control sys-

tem with built-in features such as random start, compressor 

time delay, night setback, load shed, shutdown, condensate 

overflow protection, defrost cycle, brownout, and LED/fault 

outputs . Figure 11 shows the LED and fault output sequenc-

es . 

  The unit has been designed for operation with a 24 volt 

mercury bulb type wall thermostat or a microelectronic wall 

thermostat selected by the manufacturer . Do not operate the 

unit with any other type of wall thermostat .

  Each unit has a printed circuit board control system . The 

low voltage output from the low voltage terminal strip can be 

either AC voltage or DC voltage to the wall thermostat . This 

is dependent on what terminals you use . R is A/C voltage 

output and F is D/C voltage output to the wall stat .

  The 24 volt low voltage terminal strip is set up so R-G 

or F-G energizes the fan, R-Y1 or F-Y1 energizes the com-

pressor for cooling operation, R-W1 or F-W1 energizes the 

compressor and reversing valve for heating operation . The 

reversing valve is energized in the heating mode . The circuit 

board has a fan interlock circuit to energize the fan when-

ever the compressor’s on if the thermostat logic fails to do 

so . 

  Remember the output to the wall stat can be AC current 

or  DC  current .  Terminal  (R)  on  the  wall  stat  can  be  con-

nected to terminal (R) on the PC board for AC voltage or to 

terminal (F) on the PC board for DC voltage .

  AC current 

DC current

  R to G = fan only  

F to G = fan only

  R to Y1 = cooling 

F to Y1 = cooling

  R to W1 = heat 

F to W1 = heat

 

  The Mark IV/AC control board has a lockout circuit to stop 

compressor operation if any one of its safety switches opens 

(high pressure switch and low pressure switch on units CCH 

& CCW 019 thru 060, R-410A), (CRH & CRW 024 thru 070, 

R-22) . If the low temperature switch opens, the unit will go 

into the cooling mode for 60 seconds to defrost any slush 

in the water-to-refrigerant heat exchanger . After 60 seconds 

the  compressor  is  locked  out .  If  the  condensate  sensor 

detects  a  filled  drain  pan,  the  compressor  operation  will 

be  suspended  only  in  the  cooling  mode . The  unit  is  reset 

by opening and closing the disconnect switch on the main 

power  supply  to  the  unit  in  the  event  the  unit  compressor 

operation  has  been  suspended  due  to  low  temperature 

(freezestat)  switch,  (high  pressure  switch,  or  low  pressure 

switch on units CCH & CCW 019 thru 060, R-410A), (CRH 

& CRW 024 thru 070, R-22) . The unit does not have to be 

reset on a condensate overflow detection .

  The Mark IV/AC control circuit fault output sends a signal 

to an LED on a wall thermostat . Figure 11 shows for which 

functions  the  fault  output  is  “on”  (sending  a  signal  to  the 

LED) .

Figure 11.

   

 

 

LEDs 

 

Fault

   

Indication

 

Yellow 

Green 

Red 

Output

  Normal Mode 

Off 

On 

Off 

Off

  High Pressure Fault 

Off 

Off 

Flash 

On

  Low Temperature Fault* 

Flash 

Off 

Off 

On

  Condensate Overflow 

On 

Dim 

Off 

On

  Brownout  Off 

Flash 

Off 

On 

On

  Load Shed Off 

Off 

On 

Off 

Off

  Unoccupied Mode 

On 

On 

Off 

Off

  Unit Shutdown 

Off 

Flash 

Off 

On

Page 12 / IM 742

Unit Operation

   The  Remote  Reset  feature  provides  the  means  to 

remotely reset automatic lockouts generated by high-pres-

sure  and/or  low-temperature  (in  heating)  faults .  When  the 

Mark IV board is in automatic lockout due to one of these 

faults, and the cause of the fault condition has been allevi-

ated, energizing the O-terminal for 10 seconds or more will 

force the Mark IV board to clear the lockout . A unit power 

cycle can also be used to clear an automatic lockout if the 

conditions causing the fault have been alleviated .

  The Fault Retry feature helps to minimize nuisance trips 

of automatic lockouts caused by high-pressure and/or low-

temperature (in heating) faults . This feature clears faults the 

first two times they occur within a 24-hour period and trig-

gers an automatic lockout on the 3rd fault . The retry count 

is reset to zero every 24 hours .

  The Mark IV/AC control circuit has built-in night setback 

operation .  A  “grounded’  signal  to  the  “U”  terminal  on  the 

low voltage terminal strip puts the unit into the unoccupied 

mode for night setback operation . Fan operation terminates 

and unit control reverts to the night setback terminal on the 

thermostat, W2; day heating and cooling operation is locked 

out . R-W2 energizes the compressor and reversing valve for 

heating operation . Night setback operation can be overrid-

den for two hours by toggling the fan switch (intermittently 

closing the R to O terminals) on the Deluxe Auto Changeover 

thermostat . Day thermostat setpoints then control the heat-

ing and cooling operation . The Mark IV/AC control system 

also accommodates load shed and shutdown operation on 

receipt of a “grounded” signal to the “L” and “E” terminals, 

respectively, on the low voltage terminal strip .

Figure 12.

 

The P and C terminals of the Mark IV/AC board are used 

for  pump  restart .  These  terminals  pass  a  voltage  signal 

whenever  the  unit  compressor  is  turned  on . This  signal  is 

detected by a pump restart relay board providing a N .O . or 

N .C .  set  of  contacts  for  heat  pump  loop  circulation  pump 

control . When used with the Loop Water Controller, the relay 

operation accommodates turning off circulation pumps dur-

ing unoccupied periods with a safety override dependent, at 

minimum, on WSHP’s need . The P and C terminals may be 

“daisy chained” between 200 units . See page 21 .

  Field supplied relays installed on the input terminals W1, 

W2, Y1, Y2 or G may introduce electrical noise . Never install 

relay coils in series with the inputs .

Chassis

Gr

ound

Unit

1

Unit

2

Unit

3

To

Additional

Units

Tim

e

Clock

To activate the unoccupied mode for units on the same clock schedule, 

a single wire can be “daisy chained” between units and simply grounded 

through the time clock contacts . The same system can also be done to 

activate the load shed and unit shutdown modes by running additional 

wires between units to ground .

Two types of units are available: Mark IV/AC control units or units equipped with the new MicroTech 2000 Water Source Heat 

Pump Controller .

Mark IV/AC Control Units

Содержание Enfinity CCH series

Страница 1: ...Electrical Data 5 Piping 5 Cleaning Flushing System 6 Start up 7 Operating Limits 8 Typical Wiring Diagrams 9 11 Unit Operation 12 14 Thermostat Connections 16 17 Options for Mark IV AC Units 18 21 Fi...

Страница 2: ...eck the available ceiling height versus the height of the unit 6 Note the location and routing of water piping conden sate drain piping and electrical wiring The locations of these items are clearly m...

Страница 3: ...res 1A and 1B 6 When attaching the hanger rods to the unit a double nut is recommended since vibration could loosen a single nut The installer is responsible for providing the hex nuts when installing...

Страница 4: ...etween the conditioner discharge and the distribution diffusers Return air ducts can be brought in through a low side wall filter grille and then up through the stud pieces to a ceiling plenum or thro...

Страница 5: ...rmance and minimum sound requirements Fan sound levels and performance can be affected by external static pressure changed Disconnect and cap the red lead wire and inter change it with the orange lead...

Страница 6: ...ure 7 Figure 7 Supply return runouts connected together 2 Fill the system at the city water makeup connection with all air vents open After filling close all air vents The contractor should start main...

Страница 7: ...erature rise through the machine should not exceed 35 F 19 C If the air tempera ture exceeds 35 F 19 C then the water flow rate is inadequate 6 Check the elevation and cleanliness of the condensate li...

Страница 8: ...di tion It is assumed that such a start up is for the purpose of bringing the building space up to occupancy temperature temperature and or humidity and equipment performance reliability and service l...

Страница 9: ...ervice personnel should be observed or dam age to controller may result 5 Terminal block on Mark IV AC board provides 24 VAC at terminals R and C All other outputs are 24 VDC 6 Field supplied relays i...

Страница 10: ...is used transformer must be rewired by disconnecting the power lead from the red transformer primary wire and connecting the power lead to the orange transformer primary wire Place an insulation cap...

Страница 11: ...ce an insulation cap on the red transformer primary wire 2 All temperature and pressure switches are normally closed Notes 1 A 208 230V unit is factory wired for 208V operation If 230V power supply is...

Страница 12: ...ad ShedOff Off On Off Off Unoccupied Mode On On Off Off Unit Shutdown Off Flash Off On Page 12 IM 742 Unit Operation The Remote Reset feature provides the means to remotely reset automatic lockouts ge...

Страница 13: ...ts IM 742 Page 13 MicroTech 2000 WSHP Unit Controller MicroTech 2000 Unit Controller LED Indication Status LED State Mode On Continually Occupied Occupied Load Shed On 1 2 sec Off 5 1 2 sec Unoccupied...

Страница 14: ...operation Fan operation can be customized in software to run continuously during occupied mode or to cycle ON or OFF appropriately on a call for heating and cooling Cooling mode On a call for cooling...

Страница 15: ...operation the attained temperature does not meet the software configurable setpoint for heating or cooling as appropriate a software alarm occurs The alarm auto matically resets when the attained tem...

Страница 16: ...G Thermostat Terminals C R 7 Day Programmable Electronic Thermostat P N 107095901 Thermostat Connection Diagrams Mark IV AC Units Unit Sizes 007 070 Non Programmable Electronic Thermostat P N 66805420...

Страница 17: ...t Grn Red Wall Sensor Locate the sensor on a wall where exposure to unrestrict ed air circulation represents the average temperature of the space A common mistake is to mount the sensor too close to t...

Страница 18: ...e Mark IV AC board when using standard off the self relays The auxiliary relay can be used to provide fault signals unit operation signals or to provide a means for remote equipment to control the Mar...

Страница 19: ...Control Panel O W2 G W1 Y1 F E L U A P V R C G W Y C L WSHP Mark IV AC Board Low Voltage Terminal Strip WSHP Mark IV AC Board Low Voltage Terminal Strip O W2 G W1 Y1 F E L U A P V R C 1 2 3 Auxiliary...

Страница 20: ...Override Pot1 Boilerless System Board 43 Ohm 4 pin Plug Water Temperature Sensor Signal to remote duct heater control circuit F L W1 V Mark IV Board Terminals 9 66 245 mm 007 042 14 50 368 mm 048 060...

Страница 21: ...ter Controller Terminals Daisy chain to other Mark IV AC board P and C terminals 64 58 65 WSHP Mark IV AC Board Low Voltage Terminal Strip Circuit 1 Pump Restart Relay 7 6 5 4 3 2 1 O W2 G W1 Y1 F E L...

Страница 22: ...e WSHP chassis 24VAC Pilot Duty Relay by others Terminals Located on Microtech 2000 Auxiliary Board J6 24VAC Pilot Duty Relay by others Use contacts as needed for option Terminals Located on Microtech...

Страница 23: ...cessible to the end user For example HP LT and COF are not available for use by the end user Typically the Mark IV AC board s R 24vac terminal is used to drive the board s thermostat inputs and contro...

Страница 24: ...ing Check compressor wiring for defective wiring or loose connection Check thermostat for improper location Check for defective compressor internal windings with ohm meter Check for bad compressor cap...

Страница 25: ...and atmosphere pressure it can become com bustible under pressure when mixed with air NOTE R 410A should not be mixed with air under pressure for leak testing Pressure mixtures of dry nitrogen and R...

Страница 26: ...ng system to the air to refrigerant heat exchanger coil The liquid then evaporates becoming a gas at the same time absorbing heat and cooling the air passing over the surfaces of the coil The refriger...

Страница 27: ...een through the filter when held up to sunlight or a bright light it should be changed A more critical standard may be desirable 3 The condensate drain pan should be checked annually and cleaned and f...

Страница 28: ...to www mcquay com This document contains the most current product information as of this printing For the most up to date product information please go to www mcquay com Products Manufactured in an I...

Отзывы: