McQuay Enfinity CCH series Скачать руководство пользователя страница 5

IM 742 / Page 5

Electrical Data

1 .  Verify  the  compatibility  between  the  voltage  and  phase 

of the available power and that shown on the unit serial 

plate .  Line  and  low  voltage  wiring  must  comply  with 

local  codes  or  the  National  Electrical  Code,  whichever 

applies .

2 .  Apply correct line voltage to the unit . A 

7

8

" (22mm) hole 

and/or a 1

1

8

" (29 mm) knockout is supplied on the side 

of the unit . A disconnect switch near the unit is required 

by code . Power to the unit must be sized correctly and 

have dual element (Class RK5) fuses or an HACR circuit 

General

breaker for branch circuit overcurrent protection . See the 

nameplate for correct ratings .

3 .  Three phase 50 cycle units, 380/50/3, require a neutral 

wire for 230/50/1 power to the fan circuit .

4 .  Connect  the  thermostat/subbase  wiring  with  the  power 

“off ” to the unit .

5 . 

Field supplied relays installed on the input terminals W1, W2, Y1, 

Y2 or G may introduce electrical noise. Never install relay coils in 

series with the inputs.

230 Volt Operation

Fan Assembly

All  208-230  volt  single-phase  and  three-phase  units  are 

factory wired for 208 volt operation . For 230 phase opera-

tion, the line voltage tap on the 24 volt transformer must be 

All  fan  motors  are  multi-speed,  PSC  type  with  integral 

mounting  brackets  and  thermal  overload  protection .  The 

motor is isolated from the fan housing for minimum vibration 

transmission . Fan motors on 019 thru 070 have a terminal 

strip  on  the  motor  body  for  simple  motor  speed  change 

without going back to the control box . To change fan motor 

speed to high on size 015 through 048, interchange the red 

wire  with  the  black  wire .  For  low  speed,  sizes  012,  024, 

030, 036, 042, 060 and 070, interchange the black wire with 

the red wire . To change the 460 volt motor from high to low 

speed, interchange Black and Red wires, then add jumper 

between Black and Blue wires . All the fan/motor assemblies 

have a removable orifice ring on the housing to accommo-

date motor and fan wheel removal without disconnecting the 

ductwork .  The  fan  housing  protrudes  through  the  cabinet 

allowing  adequate  material  for  connection  of  flexible  duct . 

Each  model  unit  is  shipped  from  the  factory  for  maximum 

performance and minimum sound requirements . Fan sound 

levels  and  performance  can  be  affected  by  external  static 

pressure .

changed . Disconnect and cap the red lead wire and inter-

change it with the orange lead wire on the primary of the 24 

volt transformer .

Piping

  1 .  All units should be connected to supply and return pip-

ing in a two-pipe reverse return configuration . A reverse 

return system is inherently self-balancing and requires 

only  trim  balancing  where  multiple  quantities  of  units 

with  different  flow  and  pressure  drop  characteristics 

exist in the same loop . Check for proper water balance 

by  measuring  differential  temperature  reading  across 

the water connections . To insure proper water flow, the 

differential flow should be 10°F to 14°F (5°C to 8°C) for 

units in cooling mode .

 

A  direct  return  system  may  also  work  acceptably,  but 

proper water flow balancing is more difficult to achieve 

and maintain .

  2 .  The piping can be steel, copper or PVC .
  3 .  Supply and return runouts usually join the unit via short 

lengths of high pressure flexible hose which are sound 

attenuators for both unit operating noise and hydraulic 

pumping  noise .  One  end  of  the  hose  should  have  a 

swivel fitting to facilitate removal for service . Hard pip-

ing can also be brought directly to the unit . This option 

is not recommended since no vibration or noise attenu-

ation can be accomplished . The hard piping must have 

unions to facilitate unit removal . See Figure 5 for typical 

piping setup .

  4 .  Some flexible hose threaded fittings are supplied with 

sealant compound . If not, apply Teflon tape to assure a 

tight seal .

  5 .  Supply and return shutoff valves are required at each 

conditioner . The return valve is used for balancing and 

should have a “memory stop” so that it can always be 

closed off but can only be reopened to the proper posi-

tion for the flow required .

  6 .  No unit should be connected to the supply and return 

piping  until  the  water  system  has  been  cleaned  and 

flushed  completely .  After  the  cleaning  and  flushing 

has  taken  place,  the  initial  connection  should  have 

all  valves  wide  open  in  preparation  for  water  system  

flushing .

Figure 4. CCH, CCW, CRH & CRW Sizes 007 thru 070 

(Factory wired)

Note: For low speed applications a jumper must be installed between the motor's Black and 

Blue terminal.

Figure 4a. CCH, CCW, CRH & CRW Sizes 042 thru 070 

(Factory wired, 460 volt motor only)

Содержание Enfinity CCH series

Страница 1: ...Electrical Data 5 Piping 5 Cleaning Flushing System 6 Start up 7 Operating Limits 8 Typical Wiring Diagrams 9 11 Unit Operation 12 14 Thermostat Connections 16 17 Options for Mark IV AC Units 18 21 Fi...

Страница 2: ...eck the available ceiling height versus the height of the unit 6 Note the location and routing of water piping conden sate drain piping and electrical wiring The locations of these items are clearly m...

Страница 3: ...res 1A and 1B 6 When attaching the hanger rods to the unit a double nut is recommended since vibration could loosen a single nut The installer is responsible for providing the hex nuts when installing...

Страница 4: ...etween the conditioner discharge and the distribution diffusers Return air ducts can be brought in through a low side wall filter grille and then up through the stud pieces to a ceiling plenum or thro...

Страница 5: ...rmance and minimum sound requirements Fan sound levels and performance can be affected by external static pressure changed Disconnect and cap the red lead wire and inter change it with the orange lead...

Страница 6: ...ure 7 Figure 7 Supply return runouts connected together 2 Fill the system at the city water makeup connection with all air vents open After filling close all air vents The contractor should start main...

Страница 7: ...erature rise through the machine should not exceed 35 F 19 C If the air tempera ture exceeds 35 F 19 C then the water flow rate is inadequate 6 Check the elevation and cleanliness of the condensate li...

Страница 8: ...di tion It is assumed that such a start up is for the purpose of bringing the building space up to occupancy temperature temperature and or humidity and equipment performance reliability and service l...

Страница 9: ...ervice personnel should be observed or dam age to controller may result 5 Terminal block on Mark IV AC board provides 24 VAC at terminals R and C All other outputs are 24 VDC 6 Field supplied relays i...

Страница 10: ...is used transformer must be rewired by disconnecting the power lead from the red transformer primary wire and connecting the power lead to the orange transformer primary wire Place an insulation cap...

Страница 11: ...ce an insulation cap on the red transformer primary wire 2 All temperature and pressure switches are normally closed Notes 1 A 208 230V unit is factory wired for 208V operation If 230V power supply is...

Страница 12: ...ad ShedOff Off On Off Off Unoccupied Mode On On Off Off Unit Shutdown Off Flash Off On Page 12 IM 742 Unit Operation The Remote Reset feature provides the means to remotely reset automatic lockouts ge...

Страница 13: ...ts IM 742 Page 13 MicroTech 2000 WSHP Unit Controller MicroTech 2000 Unit Controller LED Indication Status LED State Mode On Continually Occupied Occupied Load Shed On 1 2 sec Off 5 1 2 sec Unoccupied...

Страница 14: ...operation Fan operation can be customized in software to run continuously during occupied mode or to cycle ON or OFF appropriately on a call for heating and cooling Cooling mode On a call for cooling...

Страница 15: ...operation the attained temperature does not meet the software configurable setpoint for heating or cooling as appropriate a software alarm occurs The alarm auto matically resets when the attained tem...

Страница 16: ...G Thermostat Terminals C R 7 Day Programmable Electronic Thermostat P N 107095901 Thermostat Connection Diagrams Mark IV AC Units Unit Sizes 007 070 Non Programmable Electronic Thermostat P N 66805420...

Страница 17: ...t Grn Red Wall Sensor Locate the sensor on a wall where exposure to unrestrict ed air circulation represents the average temperature of the space A common mistake is to mount the sensor too close to t...

Страница 18: ...e Mark IV AC board when using standard off the self relays The auxiliary relay can be used to provide fault signals unit operation signals or to provide a means for remote equipment to control the Mar...

Страница 19: ...Control Panel O W2 G W1 Y1 F E L U A P V R C G W Y C L WSHP Mark IV AC Board Low Voltage Terminal Strip WSHP Mark IV AC Board Low Voltage Terminal Strip O W2 G W1 Y1 F E L U A P V R C 1 2 3 Auxiliary...

Страница 20: ...Override Pot1 Boilerless System Board 43 Ohm 4 pin Plug Water Temperature Sensor Signal to remote duct heater control circuit F L W1 V Mark IV Board Terminals 9 66 245 mm 007 042 14 50 368 mm 048 060...

Страница 21: ...ter Controller Terminals Daisy chain to other Mark IV AC board P and C terminals 64 58 65 WSHP Mark IV AC Board Low Voltage Terminal Strip Circuit 1 Pump Restart Relay 7 6 5 4 3 2 1 O W2 G W1 Y1 F E L...

Страница 22: ...e WSHP chassis 24VAC Pilot Duty Relay by others Terminals Located on Microtech 2000 Auxiliary Board J6 24VAC Pilot Duty Relay by others Use contacts as needed for option Terminals Located on Microtech...

Страница 23: ...cessible to the end user For example HP LT and COF are not available for use by the end user Typically the Mark IV AC board s R 24vac terminal is used to drive the board s thermostat inputs and contro...

Страница 24: ...ing Check compressor wiring for defective wiring or loose connection Check thermostat for improper location Check for defective compressor internal windings with ohm meter Check for bad compressor cap...

Страница 25: ...and atmosphere pressure it can become com bustible under pressure when mixed with air NOTE R 410A should not be mixed with air under pressure for leak testing Pressure mixtures of dry nitrogen and R...

Страница 26: ...ng system to the air to refrigerant heat exchanger coil The liquid then evaporates becoming a gas at the same time absorbing heat and cooling the air passing over the surfaces of the coil The refriger...

Страница 27: ...een through the filter when held up to sunlight or a bright light it should be changed A more critical standard may be desirable 3 The condensate drain pan should be checked annually and cleaned and f...

Страница 28: ...to www mcquay com This document contains the most current product information as of this printing For the most up to date product information please go to www mcquay com Products Manufactured in an I...

Отзывы: