Page 14 / IM 742

McQuay  Enfinity  horizontal  water  source  heat  pumps 
are  available  with  a  factory  mounted  and  tested   Alerton 
BACnet  unit  controller  as  a  special .  The  unit  controller  is 
factory  programmed  and  tested  with  all  the  logic  required 
to  control  the  unit,  and  is  designed  to  communicate  over 
a  BACnet  MS/TP  communications  network  to  an  Alerton 
BACtalk building automation system (BAS) . Each individual 
controller must be programmed with a unique mac address . 
Each controller must be physically addressed at the board 
using dip switches . The controller operates the compressor, 
fan, and reversing valve as required to maintain the space 
temperature  within  the  current  setpoints .  Data  regarding 
equipment  status,  water  and  air  temperatures,  and  fault 
conditions  can  be  monitored  by  an Alerton  BACtalk  BAS . 
Setpoints and other system preferences must be changed 
remotely  using  an Alerton  BACtalk  workstation  or Alerton 
service tool software .
 
The  controller  makes  operational  data  and  commands 
available  on  the  Alerton  BACtalk  network  using  BACnet 
objects and properties . Each heat pump controller connects 
to the BACtalk network using a BACnet MS/TP LAN, which 
is  a  simple  twisted-pair  communications  connection  that 
operates at up to 76 .8 Kbps . DIP switches on the control-
ler enable the MS/TP MAC address to be set in the range 
0-127 . A  status  LED  on  the  unit  indicates  communication 
activity on the MS/TP LAN .

Each  BACnet-compliant  unit  includes  discharge  air  and 
leaving  water  temperature  sensors,  as  well  as  all  safety 
sensors,  signals,  and  switches .  Wall-mounted  room  sen-
sors are available from Alerton to control heating and cool-
ing  operation .  Available  sensors  include  tamper-resistant 
stainless  steel  wall  sensors  with  optional  push-button  for 
status override; wall-mounted sensors with tenant setpoint 
adjustment  lever  and  timed-override  button;  wall-mounted 
sensors with LED status, timed-override button, tenant set-
point adjustment buttons, password-protected field service 
access  to  operational  data,  and  optional  humidity  sensor; 
and  wall-mounted  sensors  with  LCD  and  programmable 
operation .

BACnet

®

 WSHP unit controller

Each BACnet-compliant controller has the following operat-

ing features:

  Start-up – The unit will not operate until all the inputs and 

safety controls are checked for normal conditions .

 

Fan  operation

  –  Fan  operation  can  be  customized  in 

software to run continuously during occupied mode, or to 

cycle ON or OFF appropriately on a call for heating and 

cooling .

 

Cooling mode

 – On a call for cooling, the compressor 

and fan start immediately . Compressor run-time is cal-

culated as a percent of full cycle time (17 minutes) using 

proportional-integral control to maximize efficiency .

 

Heating mode

 – On a call for heating, the compressor 

and  fan  start  immediately,  and  compressor  run-time 

is  calculated  as  a  percent  of  full  cycle  time  (17  min-

utes)  using  proportional-integral  control  to  maximize  

efficiency .

 

Short  Cycle  Protection  and  Random  Start

  – A  start 

delay  of  180  seconds  plus  the  compressor’s  MAC 

address  in  seconds  prevents  short-cycling  and  simul-

taneous  start-up .  A  minimum  2-minute  on  time  and 

5-minute  off  time  for  the  compressor  further  ensures 

short-cycle protection .

 

Occupied  Mode

  –  A  simple  software  control  signal 

from the building automation system or a wall-mounted 

unit puts the unit into occupied mode . The unit controls 

compressor  and  fan  operation  to  maintain  occupied 

setpoints . High and low limits for occupied setpoints are 

software configurable .

 

Unoccupied  Mode

  – A  simple  software  control  signal 

from the building automation system or a wall-mounted 

unit  puts  the  unit  into  unoccupied  mode  for  night  set-

back  operation .  The  unit  controls  compressor  and  fan 

operation  to  maintain  unoccupied  heating  and  cooling 

setpoints, which are also software configurable .

 

After-hours Override Mode

 – A simple software control 

signal  from  the  building  automation  system  or  a  wall-

mounted unit can initiate after-hours heating or cooling 

in half-hour increments . Maximum override time is soft-

ware configurable up to 9 .5 hours . This feature can also 

be disabled in software .

 

Reversing valve delay

  –  When  the  compressor  turns 

off  after  heating  mode,  the  reversing  valve  remains 

energized for 60 seconds before it returns to the normal 

cooling  position  to  eliminate  swishing .  The  reversing 

valve energizes 10 seconds before the compressor .

 

Load Shed

 – Load shedding can be orchestrated by the 

building automation system using the occupied/unoccu-

pied command in software .

 

Brownout Protection

 – An onboard sensor measures 

input voltage and suspends compressor and fan opera-

tion if the supply voltage drops below 82% of the normal 

line voltage for a minimum of 10 seconds, creating an 

alarm  available  in  software .  The  alarm  automatically 

resets when the supply voltage returns to above 90% of 

normal .

BACnet

®

 WSHP Unit Controller

Содержание Enfinity CCH series

Страница 1: ...Electrical Data 5 Piping 5 Cleaning Flushing System 6 Start up 7 Operating Limits 8 Typical Wiring Diagrams 9 11 Unit Operation 12 14 Thermostat Connections 16 17 Options for Mark IV AC Units 18 21 Fi...

Страница 2: ...eck the available ceiling height versus the height of the unit 6 Note the location and routing of water piping conden sate drain piping and electrical wiring The locations of these items are clearly m...

Страница 3: ...res 1A and 1B 6 When attaching the hanger rods to the unit a double nut is recommended since vibration could loosen a single nut The installer is responsible for providing the hex nuts when installing...

Страница 4: ...etween the conditioner discharge and the distribution diffusers Return air ducts can be brought in through a low side wall filter grille and then up through the stud pieces to a ceiling plenum or thro...

Страница 5: ...rmance and minimum sound requirements Fan sound levels and performance can be affected by external static pressure changed Disconnect and cap the red lead wire and inter change it with the orange lead...

Страница 6: ...ure 7 Figure 7 Supply return runouts connected together 2 Fill the system at the city water makeup connection with all air vents open After filling close all air vents The contractor should start main...

Страница 7: ...erature rise through the machine should not exceed 35 F 19 C If the air tempera ture exceeds 35 F 19 C then the water flow rate is inadequate 6 Check the elevation and cleanliness of the condensate li...

Страница 8: ...di tion It is assumed that such a start up is for the purpose of bringing the building space up to occupancy temperature temperature and or humidity and equipment performance reliability and service l...

Страница 9: ...ervice personnel should be observed or dam age to controller may result 5 Terminal block on Mark IV AC board provides 24 VAC at terminals R and C All other outputs are 24 VDC 6 Field supplied relays i...

Страница 10: ...is used transformer must be rewired by disconnecting the power lead from the red transformer primary wire and connecting the power lead to the orange transformer primary wire Place an insulation cap...

Страница 11: ...ce an insulation cap on the red transformer primary wire 2 All temperature and pressure switches are normally closed Notes 1 A 208 230V unit is factory wired for 208V operation If 230V power supply is...

Страница 12: ...ad ShedOff Off On Off Off Unoccupied Mode On On Off Off Unit Shutdown Off Flash Off On Page 12 IM 742 Unit Operation The Remote Reset feature provides the means to remotely reset automatic lockouts ge...

Страница 13: ...ts IM 742 Page 13 MicroTech 2000 WSHP Unit Controller MicroTech 2000 Unit Controller LED Indication Status LED State Mode On Continually Occupied Occupied Load Shed On 1 2 sec Off 5 1 2 sec Unoccupied...

Страница 14: ...operation Fan operation can be customized in software to run continuously during occupied mode or to cycle ON or OFF appropriately on a call for heating and cooling Cooling mode On a call for cooling...

Страница 15: ...operation the attained temperature does not meet the software configurable setpoint for heating or cooling as appropriate a software alarm occurs The alarm auto matically resets when the attained tem...

Страница 16: ...G Thermostat Terminals C R 7 Day Programmable Electronic Thermostat P N 107095901 Thermostat Connection Diagrams Mark IV AC Units Unit Sizes 007 070 Non Programmable Electronic Thermostat P N 66805420...

Страница 17: ...t Grn Red Wall Sensor Locate the sensor on a wall where exposure to unrestrict ed air circulation represents the average temperature of the space A common mistake is to mount the sensor too close to t...

Страница 18: ...e Mark IV AC board when using standard off the self relays The auxiliary relay can be used to provide fault signals unit operation signals or to provide a means for remote equipment to control the Mar...

Страница 19: ...Control Panel O W2 G W1 Y1 F E L U A P V R C G W Y C L WSHP Mark IV AC Board Low Voltage Terminal Strip WSHP Mark IV AC Board Low Voltage Terminal Strip O W2 G W1 Y1 F E L U A P V R C 1 2 3 Auxiliary...

Страница 20: ...Override Pot1 Boilerless System Board 43 Ohm 4 pin Plug Water Temperature Sensor Signal to remote duct heater control circuit F L W1 V Mark IV Board Terminals 9 66 245 mm 007 042 14 50 368 mm 048 060...

Страница 21: ...ter Controller Terminals Daisy chain to other Mark IV AC board P and C terminals 64 58 65 WSHP Mark IV AC Board Low Voltage Terminal Strip Circuit 1 Pump Restart Relay 7 6 5 4 3 2 1 O W2 G W1 Y1 F E L...

Страница 22: ...e WSHP chassis 24VAC Pilot Duty Relay by others Terminals Located on Microtech 2000 Auxiliary Board J6 24VAC Pilot Duty Relay by others Use contacts as needed for option Terminals Located on Microtech...

Страница 23: ...cessible to the end user For example HP LT and COF are not available for use by the end user Typically the Mark IV AC board s R 24vac terminal is used to drive the board s thermostat inputs and contro...

Страница 24: ...ing Check compressor wiring for defective wiring or loose connection Check thermostat for improper location Check for defective compressor internal windings with ohm meter Check for bad compressor cap...

Страница 25: ...and atmosphere pressure it can become com bustible under pressure when mixed with air NOTE R 410A should not be mixed with air under pressure for leak testing Pressure mixtures of dry nitrogen and R...

Страница 26: ...ng system to the air to refrigerant heat exchanger coil The liquid then evaporates becoming a gas at the same time absorbing heat and cooling the air passing over the surfaces of the coil The refriger...

Страница 27: ...een through the filter when held up to sunlight or a bright light it should be changed A more critical standard may be desirable 3 The condensate drain pan should be checked annually and cleaned and f...

Страница 28: ...to www mcquay com This document contains the most current product information as of this printing For the most up to date product information please go to www mcquay com Products Manufactured in an I...

Отзывы: