ALR 110F – 150F
Product Manual ALR2-3
Part Load Data
Table 6, Part Load Data R-22,
Unit
Size
% Load
Capacity
Tons
Unit Power
kW
EER
IPLV
100.00
110.9
135.6
9.8
110F
75.00
83.5
79.9
12.5
14.0
50.00
55.6
44.9
14.9
25.00
27.9
21.1
15.9
100.00
122.2
152.8
9.6
120F
75.00
92.4
89.9
12.3
14.0
50.00
61.6
48.7
15.2
25.00
30.8
24.1
15.3
100.00
129.6
161.0
9.7
130F
75.00
97.2
95.9
12.2
13.6
50.00
64.8
54.0
14.4
25.00
32.4
24.8
15.7
100.00
133.7
168.0
9.6
135F
75.00
100.3
100.3
12.0
13.4
50.00
66.8
55.3
14.5
25.00
33.4
28.2
14.2
100.00
139.7
174.8
9.6
140F
75.00
104.7
102.5
12.3
13.7
50.00
69.8
56.9
14.7
25.00
34.9
27.0
15.5
100.00
143.2
178.2
9.6
145F
75.00
107.5
104.4
12.4
13.5
50.00
71.6
61.3
14.0
25.00
35.9
27.7
15.5
100.00
149.5
186.0
9.6
150F
75.00
112.1
109.4
12.3
13.4
50.00
74.7
64.4
13.9
25.00
37.4
29.4
15.3