Product Manual ALR2-3
ALR 110F – 150F
47
C.
Acoustics: Sound pressure levels for the unit shall not exceed the following
specified levels. The manufacturer shall provide the necessary sound treatment to
meet these levels. Sound data shall be provided with the quotation. Test shall be in
accordance with ARI Standard 370.
Octave Band
63
125
250
500
1000
2000 4000 8000 dBA
____ ____ ____ ____ ____ ____ ____ ____ ____
2.04
CHILLER COMPONENTS
A.
Compressors: The compressors shall be accessible hermetic reciprocating type with
suction and discharge service valves, crankcase oil heater and suction strainer.
Compressors shall have a forced feed lubrication system with a reversible oil pump
and initial oil charge. The compressor motor shall be refrigerant gas cooled, high
torque, hermetic induction type, four-pole, with inherent thermal protection on all
three phases and shall be mounted on RIS vibration isolator pads.
B.
Evaporator: The evaporator shall be direct expansion type with carbon steel shell,
water baffles, and high efficiency internally finned copper tubes rolled into steel
tube sheets. Refrigerant heads shall be removable. It shall be insulated with 3/4
inch (19mm) closed cell polyurethane insulation and be heated with an electric
heater to provide freeze protection to -20°F (-29°C) ambient temperature. The
evaporator shall be designed, inspected, and stamped in accordance with ASME
Code requirements.
C.
Condenser: The condenser coils shall be 3/8 inch (10mm) seamless copper tubes
mechanically bonded into plate type fins. The fins shall have full drawn collars to
completely cover the tubes. A subcooling coil shall be an integral part of the main
condenser coil. Condenser fans shall be propeller type arranged for vertical air
discharge and individually driven by direct drive fan motors. Each fan shall be in its
own compartment to eliminate cross flow of condenser air during fan cycling and
shall be equipped with a heavy-gauge fan guard. Fan motors shall be weather
protected, single-phase, direct-drive, 1140 rpm, open drip-proof type. Outside coils
shall be protected by a wire mesh coil guard to prevent fin damage.
D.
Refrigerant Circuit: Each refrigerant circuit shall include a liquid line shutoff valve,
refrigerant filter-drier, sight glass with moisture indicator, liquid line solenoid valve
(no exceptions), thermal expansion valve, discharge gas muffler, insulated suction
line and a 450 psig (3104 kPa) relief valve.