Product Manual ALR2-3
ALR 110F – 150F
23
Table 13, ALR 110F - 150F, Field Wiring Data, Single Point Power
Wiring to
Standard Power Block
Wiring to Optional Factory Mounted
Disconnect Switch
ALR
Unit
Size
Volts
Terminal
Amps
Connector Wire Range/Phase
(Copper Wire Only)
Terminal
Amps
Connector Wire Range/Phase
(Copper Wire Only)
208
840
(2 qty.) 1/0 - 600 MCM
600
(2 qty.) 250 - 500 MCM
230
840
(2 qty.) 1/0 - 600 MCM
600
(2 qty.) 250 - 500 MCM
460
335
(1 qty.) #4 - 400 MCM
400
(1 qty.) 250 - 500 MCM
110F
575
335
(1 qty.) #4 - 400 MCM
250
(1qty.) #4 - 350 MCM
208
840
(2 qty.) 1/0 - 600 MCM
600
(2 qty.) 250 - 500 MCM
230
840
(2 qty.) 1/0 - 600 MCM
600
(2 qty.) 250 - 500 MCM
460
335
(1 qty.) #4 - 400 MCM
400
(1 qty.) 250 - 500 MCM
120F
575
335
(1 qty.) #4 - 400 MCM
250
(1qty.) #4 - 350 MCM
208
840
(2 qty.) 1/0 - 600 MCM
N/A
230
840
(2 qty.) 1/0 - 600 MCM
N/A
460
335
(1 qty.) #4 - 400 MCM
400
(1 qty.) 250 - 500 MCM
130F
575
335
(1 qty.) #4 - 400 MCM
250
(1qty.) #4 - 350 MCM
208
840
(2 qty.) 1/0 - 600 MCM
N/A
230
840
(2 qty.) 1/0 - 600 MCM
N/A
460
335
(1 qty.) #4 - 400 MCM
400
(1 qty.) 250 - 500 MCM
135F
575
335
(1 qty.) #4 - 400 MCM
250
(1qty.) #4 - 350 MCM
208
840
(2 qty.) 1/0 - 600 MCM
N/A
230
840
(2 qty.) 1/0 - 600 MCM
N/A
460
335
(1 qty.) #4 - 400 MCM
400
(1 qty.) 250 - 500 MCM
140F
575
335
(1 qty.) #4 - 400 MCM
400
(1 qty.) 250 - 500 MCM
208
840
(2 qty.) 1/0 - 600 MCM
N/A
230
840
(2 qty.) 1/0 - 600 MCM
N/A
460
335
(1 qty.) #4 - 400 MCM
400
(1 qty.) 250 - 500 MCM
145F
575
335
(1 qty.) #4 - 400 MCM
400
(1 qty.) 250 - 500 MCM
208
840
(4 qty.) 1/0 - 600 MCM
N/A
230
840
(4 qty.) 1/0 - 600 MCM
N/A
460
840
(2 qty.) 1/0 - 600 MCM
400
(1 qty.) 250 - 500 MCM
150F
575
840
(2 qty.) 1/0 - 600 MCM
400
(1 qty.) 250 - 500 MCM
See page 25 for other Electrical Data notes.