6
AGZ 010B through 034B
IOMM AGZB1
Vibration Isolators
Vibration isolators are recommended for all roof-mounted installations or wherever vibration
transmission is a consideration.
The unit should be initially placed on shims or blocks at the listed free height. When all
piping, wiring, flushing, charging, etc. is completed, the springs are adjusted upward to
loosen the blocks or shims that are then removed.
A rubber anti-skid pad is part of the isolator. Installation of spring isolators requires flexible
piping connections and at least three feet of flexible conduit to avoid straining the piping and
transmitting vibration and noise. These units cannot be bolted to isolators.
Table 1, Recommended Vibration Isolators
Neoprene-in-Shear
AGZ Model
RF
LF
RB
LB
Kit P/N
010, 013, 017
RP-3 Red
RP-3 Red
RP-3 Red
RP-3 Red
350014858
020, 025, 029, 034
RP-3 Green
RP-3 Green
RP-3 Red
RP-3 Red
350014857
Spring
AGZ Model
RF
LF
RB
LB
Kit P/N
010
CP 1-24 Brown
CP 1-24 Brown
CP 1-24 Brown
CP 1-24 Brown
350014832
013, 017
CP 1-25 Red
CP 1-25 Red
CP 1-25 Red
CP 1-25 Red
350014834
020, 025
CP1-26 Purple
CP1-27 Orange
CP 1-24 Brown
CP 1-24 Brown
350014836
029
CP1-27 Orange
CP1-27 Orange
CP 1-25 Red
CP 1-25 Red
350014838
034
CP1-27 Orange
CP1-28 Green
CP 1-25 Red
CP 1-25 Red
350014840
Note
: See dimension drawing for location of isolators
Corner Weights
Packaged Chiller
AGZ-
BS
RF
LF
RB
LB
010A
279
275
267
263
013A
315
297
288
271
017A
344
323
316
297
020A
502
475
271
257
025A
531
496
301
282
029A
583
238
353
326
034A
779
761
369
361
CP-1, Spring Isolator
RP-3 Neoprene-in-Shear Isolator
R B
I
L B
I
R F
I
L F
I
Control
Panel
Remote Evaporator
AGZ-
BM
LF
RF
LB
RB
010A
257
264
236
243
013A
290
286
246
243
017A
312
309
266
263
020A
446
443
241
240
025A
453
449
245
243
029A
488
487
296
295
034A
656
703
297
318