IOMM AGZB1
AGZ 010B through 034B
3
Introduction
General Description
McQuay air-cooled water chillers are complete, self-contained automatic refrigerating units.
Every unit is completely assembled, factory wired, charged, and tested. Each unit consists of
air-cooled condensers, Copeland Compliant Scroll
hermetic compressor, brazed plate-to-
plate evaporator, and complete refrigerant piping. Liquid line components include sight-
glass/moisture indicator, solenoid valve, and thermal expansion valve. Other features include
a compressor heater, and evaporator heater for chilled water freeze protection.
The electrical control center includes all equipment protection and operating controls
necessary for automatic operation. Condenser fan motors are three-phase (except single-phase
on No. 1 fan with SpeedTrol option) and started by their own contactors and have inherent
overload protection. Each compressor has solid-state motor protection for inherent thermal
overload protection except Model AGZ 010 that has internal line breakage.
Software Version
This manual is based on software version AGZSU0102D. The software version can be
displayed by pressing the Enter and Menu keys simultaneously. Exit by pressing Menu.
Inspection
Check all items carefully against the bill of lading. Inspect all units for damage upon arrival.
Report shipping damage and file a claim with the carrier. Check the unit nameplate before
unloading to be sure it agrees with the power supply available. Units are shipped FOB factory
and McQuay is not responsible for physical damage after unit leaves the factory.
Note:
Unit shipping and operating weights are listed on pages 16 and 17.
Installation
Note:
Installation must be performed by trained, experienced personnel who are
familiar with local codes and regulations, especially concerning refrigerant release
to the atmosphere.
!
WARNING
Sharp edges and coil surfaces can cause personal injury. Avoid contact with them.
Handling
Be careful to avoid rough handling of the unit. Do not push or pull the unit from anything
other than the base. Block the pushing vehicle away from the unit to prevent damage to the
sheet-metal cabinet and end frame (see Figure 1).
To lift the unit, lifting slots are provided in the base of the unit. Arrange spreader bars and
cables to prevent damage to the condenser coils or cabinet (see Figure 2).
H
AZARD
I
DENTIFICATION
I
NFORMATION
!
WARNING
Warnings indicate potentially hazardous situations, which can result in property damage, severe
personal injury, or death if not avoided.
!
CAUTION
Cautions indicate potentially hazardous situations, which can result in personal injury or
equipment damage if not avoided.
Содержание AGZ 010BM
Страница 67: ......